TAMCO MEDIUM-DUTY BACKDRAFT DAMPER   |  

Installation Guidelines

For Series 7000, 7000 WT, 7000 CW

FRONT VIEW

BACK VIEW

GENERAL INSTALLATION NOTES  

&

 

>

Backdraft dampers must be kept clean and dry. Store indoors to 

protect from dirt, dust and weather. Do not store at temperatures 

in excess of 100°F 

(38

°

C)

.

 

>

Do not stack backdraft dampers on top of or against each other.

 

>

Backdraft dampers are to be handled and lifted by the frames only. 

Do not use the blades or linkage to lift backdraft dampers. 

 

>

Do not drop, drag or twist.

 

>

Multiple-section assemblies will require sufficient people and 

appropriate rigging to lift units safely and without causing damage.

 

>

Ensure that the opening or duct work is free of any obstructions 

and is adequately supported, so that damper operation is not 

adversely affected.

 

>

The system must support the damper. The damper cannot support 

the system. Do not use the damper to square up duct. The opening 

must be plumb, straight, level, square, and sized correctly for the 

backdraft damper.

 

>

The backdraft damper must not be twisted, compressed or 

stretched to fit the opening. Once installed, the blades must be 

free to move without binding. Use shims between the damper 

frame and the opening to prevent distortion or stretching of the 

backdraft damper.

 

>

When installing fasteners (provided by others), they should be 

located so as not to  interfere with linkage parts or blade operation.

 

>

Consult engineering plans prior to installation to confirm airflow 

direction. 

 

>

TAMCO recommends that backdraft dampers be installed at a 

minimum distance of one (1) fan diameter away from the fan, for 

custom air handler exhaust applications. AMCA 200 and AMCA 

201 recommend a distance of one (1) duct diameter for each 1000 

fpm in order to achieve uniform air at the backdraft damper. The 

type of fan and distance allowed between the fan and the damper 

will determine the air velocity profile the backdraft damper will be 

subjected to. 

 

>

When backdraft dampers are installed in the vertical plane, blades 

must always be horizontal.

 

>

Series 7000, 7000 WT, and 7000 CW Backdraft Dampers can 

be installed in the vertical plane (Airflow Horizontal), or in the 

horizontal plane (Airflow Up).

 

>

Only Series 7000 CW Counterweighted Backdraft Dampers can be 

installed in the horizontal plane with Airflow Down.

TAMCO’s all-aluminum backdraft dampers are constructed with maintenance-free bearing and linkage components.

Caution: 

Never use any lubricants, such as grease or silicone, on TAMCO backdraft dampers. 

In applications where the humidity level is unusually elevated, or where there are extremely high levels of dust and dirt 

particles, TAMCO recommends that the damper linkage and bearing system should be cleaned once a year. This can be 

done by blowing away dust using compressed air. If needed, a domestic-strength steam cleaner can be used to loosen 

dirt, which can then be blown out with compressed air, along with any remaining water droplets

Note that all technical information available on TAMCO’s website at www.tamcodampers.com 

supersedes and takes precedence over all information contained within the printed catalog.

CALL TAMCO CUSTOMER SERVICE WITH ANY QUESTIONS CONCERNING TAMCO BACKDRAFT DAMPERS

1-800-561-3449

DO NOT ADJUST LINKAGE MECHANISM. IF PROBLEM STILL EXISTS  

AFTER VERIFICATION AND CORRECT ACTION,  

CALL TAMCO CUSTOMER SERVICE.

Summary of Contents for 7000 Series

Page 1: ...istance of one 1 fan diameter away from the fan for custom air handler exhaust applications AMCA 200 and AMCA 201 recommend a distance of one 1 duct diameter for each 1000 fpm in order to achieve uniform air at the backdraft damper The type of fan and distance allowed between the fan and the damper will determine the air velocity profile the backdraft damper will be subjected to When backdraft dam...

Page 2: ...and back damper frames securing clips angles to duct work TAMCO recommends that the clips angles should be fastened to the duct work only and not to the backdraft damper This will prevent the fasteners from binding or twisting the damper If access to both sides of the backdraft damper is limited install clips angles to the duct work around the perimeter of either the front or the back frames Then ...

Page 3: ...raight even and aligned with each other 2 Install the bottommost sections of the backdraft damper assembly first 3 T bars are to be installed on the back sticker side of the damper Each T bar will be shorter than the height of a single section This is to ensure that a full T bar piece can be centered across the intersection where four damper sections meet 4 To pierce alignment holes in the damper ...

Page 4: ...ide 19 mm aluminum counterweight bar attached to the back of the blades with the exception of the top blade The aluminum bar bracket is centered along the length of the blade This is designed to apply even pressure across each blade Do not move the bar bracket away from the factory aligned center of the blade Counterweights can be set to relieve air pressure differentials less than 01 in w g 3 Pa ...

Reviews: