background image

 

CI-3K472001 Project 2215 Rev.0 04/03/13 

 

 

Installation Instructions 
 

M series Analogue DIN Panel Meters 

 

 

M242-05*, M242-15*, M244-13*, M242-41*   
M243-05*, M243-15*, M244-21*, M243-41* 
M244-05*, M244-15*, M244-31*, M244-41* 

 

 

 

Introduction 

 

This product range includes a wide range of functions, 
including AC Ammeters and maximum demand meters; AC 
Voltmeters; DC Ammeters and milliammeters; DC 
Voltmeters and millivoltmeters; Elapsed time meters; 
Frequency meters; AC wattmeters and var meters and 
Power factor meters. 

 

Marking and ratings 

 

Body side labels show function, electrical rating, and 
connection diagram, where there are more than two 
terminals on the unit. For two terminal units, the terminals 
are connected directly across the input to be measured. 
Terminal numbers are moulded into the base adjacent to 
each terminal stud and corresponding numbers appear on 
the connection diagram. Note that the electrical rating may 
differ from the dial scale marking, and the unit side label is 
definitive.  
These meters are intended for a rated temperature range, is 
-20/+60 deg C and up to 80% relative humidity, and only for 
indoor use at an altitude of less than 2000m. Shock 
maximum level is 30g. 
 

Installation 

 

The meter should be installed in line with the requirements 
of the local electrical code. It should be installed in a dry 
position, not in direct sunlight and where the ambient 
temperature is reasonably stable and within ratings above. 
These units are only for built in use and with terminals 
inaccessible to users after installation and should be 
mounted to a DIN panel cut-out up to a maximum thickness 
of 5 mm. Mounting is by 2 opposed corner clamps. It may 
be convenient to use a 7mm screwdriver style nut driver to 
engage the barrel nuts on those models with plastic nuts, 
particularly when starting the thread, but great care must be 
taken not to over tighten. It is very easy to cause damage 
with excessive torque when using a nut driver, so final 
tightening should be performed with finger pressure only.  
 

Fusing and connections 

 

External voltage transformers and current transformers may 
be used where appropriate to extend the range, provided 
that the ratings marked on the side label are not exceeded 
at point of connection to meter. These products are 
designed for permanently connected use, normal condition 
measurement category III, pollution degree 2 (e.g. non 
ventilated panels or ventilated panels with filters, without 
condensation occurring), basic insulation, for rated voltage.  
Connection diagrams shown on the unit side label should 
be carefully followed to ensure correct polarity and phase 
rotation where applicable. Terminals are intended for use 
with insulated ring lugs. Ensure a minimum spacing of 
5.5mm (0.21”) between uninsulated parts of adjacent ring 
lugs. Tighten terminal screws to 2Nm (1.5 ft/Lb) only.  

These products do not have internal fuses therefore 
external fuses 

must 

be used for safety protection under 

fault conditions. Voltage input lines where required must be 
fused with a quick blow fuse 1A maximum. Auxiliary supply 
lines, where required must be fused with a slow blow fuse 
rated 1A maximum. Current metering circuits directly 
connected in line with the load must be fused at the rated 
current for the meter. Where fitted, current transformer (CT) 
secondaries must be connected to protective earth in 
accordance with local regulations. Do not fuse CT circuits.  
 
The equipment into which this meter is installed must have 
a clearly marked adjacent means of isolating the supply 
voltage to permit safe access for subsequent maintenance.  
Ensure supply circuits are rated for meter VA: >4.5VA  

 

 
Choice of associated components 

 

Choose fuses of a voltage rating equal to or exceeding the 
rated voltage of the circuit into which the meter is connected 
and of a type and with a breaking capacity appropriate to 
the supply to which the fuse is connected.  Connection 
wires and ring lugs should be rated for at least 1A for 
voltage and auxiliary lines and to at least the rated current 
for current measuring circuits. Additionally, wires for DC 
current meters rated over 50mA must be rated at 75 deg C 
or greater. Ensure cables and ring lugs have a voltage 
insulation rating equal to or greater than the rated voltage of 
the circuit to which they are connected.  
CT cable impedance should ensure that CT VA rating is not 
exceeded and it’s accuracy impaired.  
 

Cleaning and maintenance 

 

As required, wipe the front face with a damp cloth, ensuring 
that no moisture enters the unit or penetrates behind the 
mounting panel. No maintenance is required beyond 
periodically checking the mechanical zero of the meter as 
described overleaf in “commissioning”, if necessary 
removing any accumulations of dust or other foreign matter 
from the terminal area and ensuring that connections 
remain tight.  

 

 
 
 
 
 
 
 
 
 

Warnings  

  

 

 

During normal operation, voltages hazardous to life may be 
present at some of the terminals of this unit. 

  These instructions contain important safety information: Read 

before starting installation or servicing of the equipment  

  Installation  and  maintenance  should  be  performed  only  by 

qualified,  properly  trained  personnel'  abiding  by  local 
regulations.  

  Ensure  all  supplies  are  de-energised  before  attempting 

connection or other procedures.   

  Never  open  circuit  the  secondary  winding  of  an  energised 

current transformer.   

  If  this  equipment  is  used  in  a  manner  not  specified  by  the 

manufacturer,  protection  provided  by  the  equipment  may  be 
impaired.  

 

Measurement categories 600V CAT III.  

Caution: Risk of 

Electric Shock 

Reviews: