Propus UPS manual

 

 

User Manual

 

Uninterruptible Power Supply System

 

Model: Propus 6K-30KVA online industrial UPS

Summary of Contents for Propus PPS10KLR

Page 1: ...Propus UPS manual User Manual Uninterruptible Power Supply System Model Propus 6K 30KVA online industrial UPS ...

Page 2: ... Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 1 CONTENTS CONTENTS 1 1 INTRODUCTION 2 2 SAFETY 3 3 APPEARANCE 4 4 POSITIONING 7 5 INSTALLATION 10 6 OPERATION 14 7 STATUS HANDLING 17 8 WORKING FLOW 25 9 Monitoring software 27 10 Propus Technical specification 29 11 Shipping list 31 ...

Page 3: ...troduction Propus series on line UPS is a new generation intelligent type UPS specially designed for finance system telecom system electric power system intelligent building working station to meet the high quality and high reliability requirement of the system to power supply 1 4 Characteristic computer port UPS intelligent monitoring function can be got by the computer port The detail refers to ...

Page 4: ...scharged Safety 2 SAFETY To reduce the danger of electric shock caused because load equipment isn t good connected to the grounding when installing computer port signal cable please switch off the AC input power only after all signal cables have good connected you can connect the power There must be proper branch protector Breaker on UPS connecting to AC input power with grounding That of connecti...

Page 5: ...ed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 4 3 APPEARANCE 3 1 Display Control panel Figure 1 1 Welcome screen WELCOME TO 2 Display of system status KVA 3 Display of input voltage value ON LINE AC IN 220V 4 Display of input frequency value ON LINE AC FRE 50Hz ...

Page 6: ... display in machine ON LINE TEMP 33 Note ON BYPASS mode the output voltage and frequency are displayed be 0 LED would display only after the unit is switched on These parameters vary with machine model 10 LCD cycle display switch button digital signal display items switch button 11 UPS switch button UPS general switch button 1 Turn on UPS inverter by pressing the ON key UPS convert to UPS inverter...

Page 7: ...n hole The ventilation hole and other small long elliptic ventilation holes all need to keep good ventilation 3 RS232 communication interface receptacle The standard communication interface between UPS and computer 4 Air blower 5 Battery Switch 6 MAIN INPUT switch 7 Wiring Terminal support Power wiring Terminal support of input output and battery 8 Wiring inlet outlet hole Wiring inlet outlet hole...

Page 8: ...Please dismantle all barge connecting cable firstly Perform after turn off 2 Careful and light placement forbid any hit 3 Please do not move UPS inverted 4 2 Placement 1 Do not place the UPS on slope or scraggy land Figure 3 Figure 3 2 Please place the UPS in the place where keeps good ventilation UPS s back face and side face should be more than 10cm away from the room wall Figure 4 3 Do not posi...

Page 9: ...ax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 8 Figure 4 Figure 5 Figure 6 4 Please keep UPS away from fire source and high temperature avoiding over high temperature Figure 7 5 Do not lay goods on the UPS Figure 8 ...

Page 10: ...971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 9 6 Do not position UPS in the place where contains caustic gas Figure 9 7 Running environment temperature 0 40 Figure 7 Figure 8 Figure 9 ...

Page 11: ...g general household receptacle because the Max current of general receptacle is 15A the socket may be burned down for overload 2 Please connect UPS input terminal to utility power switchboard close Figure 10 Figure 10 Note Don t make anti connection of polarity 3 Simple identification way of power polarity 1 Firing line R S T There is 380V voltage between Line and Line 2 Neutral N there is 220V vo...

Page 12: ...is more than 5V or can t meet the system requirement please reinstall good grounding system to maintain operating safety of system 5 The power cable and the impaction terminal must be quality goods prohibit wrapping power cable on the terminal support directly 6 Please follow the electrician principle when installation 7 Avoid using same a switch with other equipment when connect to switchboard tr...

Page 13: ...ding to load current do not use over thin cable 3 Avoid short circuit and overload 4 The grounding to the unit only acts as reference point if the grounding isn t good that may cause disturbance and false datum management and affect UPS and computer please ask professional personnel for handling immediately 5 User offers a good grounding system 6 Try to make the grounding close to connection point...

Page 14: ...er to figure 14 5 4 Connecting position and way 1 Remove the cover screw on wiring terminal support with Philip Head 2 Remove the cover and find the wiring terminal plate below the power switch 3 According to connecting guide draw AC power input cable output cable and battery pack power cable though the wiring outlet inlet then connect to relevant terminal 4 After connection please carefully confi...

Page 15: ... position 2 Verify the installation place again Figure 4 to 10 3 Rock power cable with hand and see if there is any looseness if looseness retighten the seizure screw 4 Do not connect load 5 Inspect input voltage is to meet the demand of UPS 220V 10 with ammeter 6 2 Operation process at first start up After verify above items are correct please start up UPS according to the following ways 1 Please...

Page 16: ... is lit Utility supplies power to output via bypass Figure 16 3 After 20s input indicator light on front panel is lit bypass ind icator light is off output indica tor light is on the welcoming inf ormation is displayed on LCD UPS inverter supplies power to output Figure 17 4 Shutdown input power of UPS utility indicator light is off the welcoming information is displayed on LCD UPS inverter suppli...

Page 17: ...yed is more than 100 please dismantle the unimportant load till the value displayed is less than 100 6 3 Daily switch ON OFF operation procedure If you want to switch on off during daily using please operate UPS according to the following ways 1 If you want to switch off UPS you can switch off UPS by plugging the OFF button located on front panel At the time UPS is under bypass condition utility s...

Page 18: ...or and handling ways when normal Please refer to indicator LCD indicator value and buzzer sound on the panel you can see if UPS running is normal if UPS is abnormal please refer to the handling thing according to panel indicator status 1 Panel indicator status is as the right 1 UPS running status Utility is normal UPS runs normally and UPS is used under full load 2 Handling way needless handling 2...

Page 19: ...nel indicator status is right 1 UPS running status Utility supplies power normally UPS runs normally and battery voltage is low 2 Handling way needless handling The charger is fault please replace charging board Note the indicated material parameters vary with the machine type 5 panel indicator status is right 1 UPS running status Utility power is normal and it is transferred to utility mode UPS d...

Page 20: ...se load to ensure the indicated percent of LCD output power is less than 100 If the thing Figure 24 is still present after removing load please refer to flow chart 3 of status handling 7 Panel indicator status is right 1 UPS running status Utility power is normal UPS runs abnormally and transfers to be supplied power by utility 2 Handling way Please refer to flow chart 4 of Figure 25 status handli...

Page 21: ...indicator status is right 1 UPS running status Utility power is disconnected and UPS is supplied power by battery Buzzer beeps once every one sec ond when the battery power will be exhausted 2 Handling way UPS will shutdown at once please save files as you could Figure 27 10 Panel indicator status is right 1 UPS running status Utility power may have been disconnected and battery power has been exh...

Page 22: ...ch Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 21 Flow chart 1 of status handing ...

Page 23: ...s UPS manual Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 22 ...

Page 24: ... O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 23 Flow chart 2 of status handing Flow chart 3 of status handing ...

Page 25: ...s UPS manual Tech Novitas FZC P O BOX No 8073 SAIF Zone U A E Phone 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 24 ...

Page 26: ...uns normally When Propus UPS runs normally after high frequency harmonic noise in utility power is filtered by the filter on the one hand utility power charges battery pack via the inverter and keeps battery power on full voltage level and on the other hand utility power is converted into direct current via the rectifier and is transferred into pure sine ware power via the inverter finally power i...

Page 27: ...y the battery and then is transmitted to user equipment for using via the static switch and the filter to avoid the case that load isn t supplied power 8 4 UPS running way when UPS supplies power on bypass mode There are five kinds of status when UPS supplies power on bypass mode As figure 32 1 overload 2 inverter failure 3 when switch on UPS is in the course of slow startup during pressing the SW...

Page 28: ...nected the computer system protected by UPS finally still is closed lawless because of losing power when battery has been exhausted Through monitoring software UPS can communicate with computer system so as to inform computer system to close computer systematically when UPS battery will be exhausted 9 2 Software When the server is unguarded the power thing record and the function of informing turn...

Page 29: ...us at support technovitas com 28 Figure 33 9 3 port component To computer system with built in UPS monitoring software the port component can connect UPS into your system Each component includes relevant port cable that convert UPS status signal into identifiable signal to system only using UPS monitoring cable supplied by factory PIN2 RS232 RXD PIN3 RS232 TXD PIN5 GND Figure 34 ...

Page 30: ...A 16A 20A 24A 32A 40A 56A AC output Voltage 220V Frequency 50 60 Hz Voltage stability 1 frequency stability 0 5 When disconnection Wave form SPWM sine wave Power factor 0 8 Later distortion 3 linear load Battery Voltage 192VDC 240VDC Model Lead acid free maintenance Charging time 90 capacity after 8 10 hours Alarm Utility disconnect Buzzer beeps once every four seconds Battery exhausted Buzzer bee...

Page 31: ...s if UPS internal temperature 85 Output short circuit Limit current automatic shutdown fuse and there no fuse switch protection UPS abnormal Automatically transfer to bypass and supplied power by utility Noise filter 10 100KHz at 40Db 100KHz 100MHz at 70dB LCD display input output voltage frequency battery voltage output power temperature Battery BVL One LED it lit on when battery low voltage Envi...

Page 32: ...ne 971 6 5529892 Fax 971 6 5529897 Designed by Tech Novitas Corp LLC Wyoming U S A www technovitas com Email us at support technovitas com 31 11 Shipping list code Content Number 1 UPS 1 2 UPS use manual 1 3 Intelligent monitoring software 1 4 Computer port cable RS232 1 ...