D 031

06/00

Timer 031

- Data Brochure

6 AM 9 AM

5 PM

10 PM

Temporary UnOccupied

Override at 1 PM

Temporary UnOccupied

Override at 7:30 AM

6 AM 9 AM

5 PM

10 PM

Temporary Occupied

Override at 1 PM

Temporary Occupied

Override at 7:30 AM

Su

Sa

Mo

We Th Fr

Tu

T I M E

PM

OCC

1

Su

Sa

Mo

We Th Fr

Tu

Temporary

Override

Permanent

Override

T I M E

PM

OCC
OVR

1

OVR

6 AM 9 AM

5 PM

Occupied

10 PM

Occupied / UnOccupied Schedule

Su

Sa

Mo

We Th Fr

Tu

SCHD

AM

OCC

1

UnOccupied

Su

Sa

Mo

We Th Fr

Tu

SCHD

PM

OCC

2

SCHD

UNOCC

2

Su

Sa

Mo

We Th Fr

Tu

PM

SCHD

UNOCC

1

AM

Su

Sa

Mo

We Th Fr

Tu

POWERING UP THE TIMER

After the Timer 031 is powered up, a number indicating
the software version is displayed for 1 second. Following
this, all elements are displayed for 4 seconds. If the
Timer has been turned off for more than 24 hours, the
Timer flashes 12:00 AM, the 

OCC element, and the Su

pointer to indicate that the clock must be set. Setting of
the clock is described in the Settings section of this
brochure. When power is removed from the Timer, the
display is turned off; however, the time clock continues
to operate on the backup battery for up to 24 hours. The
battery is generally good for forty 24 hour shut down
periods.

Occupied / UnOccupied mode

The Timer 031 has an internal relay which switches on
and off according to a programmed schedule of Occu-
pied and UnOccupied events. The Timer 031 allows up
to two schedules for each day of the week. During the
first schedule, the Timer turns on the 

1 display element

and during the second schedule, the Timer turns on the
2 display element. Each schedule has an Occupied and
UnOccupied event. When the Timer is in Occupied
mode, the 

OCC element is displayed and the internal

relay is turned off.

With the relay turned off, the contacts between terminals 

N/O — Com (3 and 4) are opened and the

relay contacts between terminals 

Com — N/C (4 and 5) are closed. If the Timer 031 switches to

UnOccupied mode, the 

UNOCC element is displayed and the internal relay is turned on. With the

relay turned on, the contacts between terminals 

N/O — Com (3 and 4) are closed and the relay

contacts between terminals 

Com — N/C (4 and 5) are opened.

Schedule Override

The Timer 031 allows the user to override a given event temporarily or permanently. During a
temporary Override the Timer skips one single event. With a permanent Override, the Timer
remains continuously in either the Occupied or UnOccupied mode until the Override is manually
cancelled. The Override options are described in the Settings section in this brochure.

Temporary Occupied Override

When the Timer 031 is in Occupied mode and a Temporary Occupied Override is selected, the
OVR element is flashed and the Timer skips the next UnOccupied event.
When the Timer is in UnOccupied mode and a Temporary Occupied Override is selected, the
OVR element is flashed and the Timer immediately switches to Occupied mode.

Note: 

The OVR element turns off when the Temporary Override is terminated at the next event.

Temporary UnOccupied Override

When the Timer 031 is in Occupied mode and a Temporary UnOccupied Override is selected,
the 

OVR element is flashed and the Timer immediately switches to UnOccupied mode.

When the Timer is in UnOccupied mode and a Temporary UnOccupied Override is selected,
the 

OVR element is flashed and the Timer skips the next Occupied event.

Note: 

The OVR element turns off when the Temporary Override is terminated at the next event.

Su

Sa

Mo

We Th Fr

Tu

T I M E

AM

OCC

1

Su

Sa

Mo

We Th Fr

Tu

T I M E

AM

1

OCC

Su

Sa

Mo

We Th Fr

Tu

SCHD

T I M E

AMPM

UNOCC

OVR

1

2

On Power-up

Timer 031

Item

Power

24 V (ac) 

±

10% 2 VA 

32 V (dc) 

±

20 % 0.04A

Relay

240 V (ac) 8 A 1/4 hp
pilot duty 240 VA 2 A

1

N/C

SCHD

Su

T I M E

AMPM

UNOCC

OVR

Sa

Mo

We Th Fr

Tu

1

2

2

3

4

5

Power

N/O Com

C-

R+

Cut jumper
for non-60 Hz

Override

Menu

 Optimum Start / Stop

Lithium CR1620
POS (+) up

On

Off

Made in Canada

R

C    US

158033

Wiring must be rated at least 300V

Sequence of Operation

The tekmar Timer 031 is a microprocessor-based timer which can be programmed to provide up to
two Occupied and two UnOccupied events per day for each day of the week. The Timer 031 operates
its internal SPDT relay based on the programmed schedule. The Timer 031 allows the user to over-
ride any programmed event temporarily or permanently.
In case of power shut down, the programmed information is retained in memory for at least 10 years.
The clock continues to operate using a backup battery for up to 24 hours, at which time it automati-
cally shuts itself down.
When used with a tekmar control, the Timer 031 has a special function which synchronizes the Occu-
pied / UnOccupied schedule with the Optimum Start / Stop feature on the tekmar control.
By cutting the jumper in the wiring chamber, the Timer 031 can be used in a non-60 Hz power system.