Astra-BRA 

 

Addressable Relay Unit

 

User guide

 

 

 
 

 

 

This operating manual is intended to study the  principle of  operation, proper 
use,  storage  and  maintenance  of  the  Astra-BRA  addressable  relay  unit.The 
manufacturer  reserves  the  right  to  make  changes  to  the  design,  firmware, 
circuit solutions and product packaging that do not worsen its technical char-
acteristics,  do  not  violate  mandatory  regulatory  requirements,  without  prior 
notice to the consumer. 

Abbreviations

:  

SLC

 

– Signaling line circuit; 

ARM

 

– Monitoring software; 

IU 

-

 

indication unit Astra-863; 

BRA

– Addressable relay unit Astra-BRA

 

Zone

 

– notification source; 

Tutorial 

- User guide built into the PKM Astra Pro or Astra-812 Pro setup 

instructions (available on the website www.teko.biz);

 

Control  Panel 

 

control  panel  Astra-8945  Pro  or  Astra-812  Pro  with  firm-

ware version 5_0 and higher;

  

PKM  Astra  Pro 

–  Astra  Pro  monitoring  software  package  (available  on  the 

website www.teko.biz); 

Keypad

 

– 

Astra-814 Pro control keypad; 

RPA

 

– signalling line extender "Astra-A RPA»; 

LP

– Laser pointer Astra-942»; 

NC

 

– normally closed; 

NO

 

– normally open; 

AL

 

– alarm loop. 

 

1  Function 

 

1.1 

 

BRA is  designed to  control  smoke  ventilation  dampers, fire  dampers 

of  general  ventilation,  deluge  dampers  and  other  actuators  powered  by 
220 V. The BRA is designed to operate in the SLC formed by the RPA. 

1.2 

 BRA provides: 

 

possibility  to  control  the  damper  of  fire  dampers  of  types:  electro-
mechanical with return spring, reversible, electromagnetic by command of 
the Control Panel received via SLC; 

 

monitoring  the  load  of  the  relay  for  open  and  short  circuits  and  trans-
ferring  information  about  the  integrity  of  the  load  line  to  the  Control 
Panel; 

 

valve position control by limit switches; 

 

LED indication of BRA operation, valve status, outputs and SLC; 

 

Valve test 

1.3 

The BRA can operate in two modes: 

 

“Valve”  mode,  in  which  the  BRA  implements  special  valve  control  algo-
rithms,  

 

"Relay unit" mode, in which the BRA provides operation 

 

one relay output with load circuit control. 

In both modes, the BRA can operate with or  without load continuity su-
pervision (depending on configuration) 

1.4 

The sources of notifications for the BRA are partitions of the Control 

Panel.  

1.5 

BRA can only be controlled by one Control Panel. 

1.6 

BRA  provides  configuring  of  operating  modes  using  the  menu  of  the 

PKM Astra Pro configuration module. 

1.7 

 The BRA (signal part) is powered from the SLC power line (terminals "+" 

and "-"), the power part (L1, N, L2) - from the 220 V AC network.  

1.8 

 The power supply of the power part of the BRA (relay, AL) is carried out 

from the main (terminals L1, N) and backup (terminals L2, N) 220 V power 
supplies. In the absence  of the main power supply, the BRA automatically 
switches to the backup; when the main power is restored - switches to the 
main power. 

Attention!   
ONLY  1  AND  THE  SAME  PHASE  CAN  BE  SUPPLIED  TO  INPUTS  L1 
AND L2! SUPPLY OF DIFFERENT PHASES IS FORBIDDEN! 

2  Specifications 

 

Power supply voltage, V

:

 

- power unit ..................................................................from 187 to 242 AC 
- signal part (from SLC) ............................................... from 6.0 to 27.6 DC 
(power and signal parts are galvanically isolated) 
Current consumption from 220 V, mA, not more .................................... 20 
Current consumption from SLC, mA, not more ...................................... 0.5 
Power consumption from 220 V (excluding consumption 
valve),W, not more ................................................................................... 5 
SLC interface cable length from BRA to RPA, m, max ....................... 1000 
Number of relays ..................................................................................... 1 

Relay specification (in "Relay unit" mode) (terminals 
RAB and Ncl)

:  

Maximum switching voltage, V.............................................................. 250 

Maximum switching current at a voltage of 250 V, A ............................... .1 
Minimum switching current, mA *...................................... ....................  0.6 

AL Specification 

(terminals 

+Zone1- , +Zone2-, +TST-

): 

Standby voltage, V*...................................... ......................... from 8.5 to 14 
ripple voltage value on terminals AL, mV, no more ................................ 50 
Short circuit current AL, mA, no more .................................................... 20 
AL integration time, msec ...............................................................

300±30 

AL wire resistance (excluding remote element), Ohm, no more ........... 150 
Leakage resistance between loop wires or each 
wire and "Ground", kOhm, not less than .................................................... 50 
Loop resistance, kOhm ....................................................... see tables 7, 8 

Boot time, sec, not more ........................................................................ 10 
Overall dimensions, mm ........................................................ 216

×135×39 

Weight, kg, not more .......................................................................... 0.35 

Operation conditions 

Temperature range

, ºС ...................................................... from -30 to +55 

Relative humidity      ..................................................... up to  93 at +40 

0

С 

                                                                           

without moisture condensation 

 

3  Delivery set

 

 

Relay unit wired address "Astra-BRA" ............................................ 1 pcs 
Resistor 3.9 kOhm .......................................................................... 6 pcs 
Screw ............................................................................................. 4 pcs 
Dowel ............................................................................................. 4 pcs 
Sticker ............................................................................................ 2 pcs 

 

4  Design 

4.1 

Structurally, the BRA is made in the form of a unit consisting of a base 

and  a  removable  cover.  PCB  with  radio  elements  is  mounted  inside  the 
unit.  

 

4.2 

The PCB has indicators for monitoring the state of power supply and 

outputs of the BRA: 

OPERATING

 LED 

– is for indicate the power supply status of the BRA  

OUTPUT

 LED - to display the status of the valve control outputs; 

STATUS

 LED - to display valve position and faults;  

SLC

 LED - status indication SLC BRA with RPA. 

4.3 

The  PCB  has  a  tampering  switch  to  control  the  state  of  the  case 

(opened / closed).  

4.4 

The PCB has screw terminal units, the purpose of which is given in 

the table 1. 

Table 1  

Terminal 

Terminal function 

А, В  

Connection to the data L1 (L2) RPA

 

+,  -   

Connection to the power L1 (L2) RPA

 

 +Zone1- 

Connecting the valve limit switch

 

 +Zone2- 

Connecting the valve limit switch

 

+TST- 

Connecting the TEST button

 

РАБ 

Valve connection

 

N

кл 

ИСХ

 

L1, N

 

Input for connecting the main power supply 220 V 

L2, N

 

Input for connecting the main power supply 220 V 

 
 
 
 
 
 
 
 
 
________________________________

 

 

* for relay in load circuit monitoring mode

 