background image

 

 

 

 

 

 

 

2022-02-21 

 

 

 

 

 

 

User Manual

 

DALI Gateway S64 KNX 

DALI Gateway S128 KNX  

Version 2.0

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 4940301

Page 1: ...2022 02 21 User Manual DALI Gateway S64 KNX DALI Gateway S128 KNX Version 2 0 ...

Page 2: ...ur channels RGBWAF 13 5 Manual Mode 14 5 1 1 channel device 14 5 2 2 channel device 15 6 Operating modes 18 6 1 Normal mode 18 6 2 Permanent mode 18 6 3 Staircase mode 18 6 4 Night mode 18 6 5 Panic mode exceptional case 19 6 6 Operating mode hierarchy 19 7 Analysis and service functions 20 7 1 Recording operating hours 20 7 2 Individual fault recognition at ECG level 20 7 3 Fault analysis at grou...

Page 3: ...store of DALI configuration 73 12 Scenes 74 12 1 Configuration 74 12 2 Colour entries 76 12 3 Programming scenes 77 12 4 Testing a scene event 77 12 5 Testing the whole scene 77 12 6 Export import delete 77 13 Time control 78 13 1 Configuration 78 13 2 Action types 80 13 3 Disabling enabling 82 13 4 Manual override 83 13 5 Timer 83 13 6 Export import 83 14 Extras 85 14 1 Menu edit descriptions 85 ...

Page 4: ...I Manufacturer Theben AG Name DALI gateway S64 KNX 1 channel gateway KNX Order number 4940301 Number of communication objects 566 Number of group addresses 830 Number of associations 830 Product family Gateways Product type DALI Manufacturer Theben AG Name DALI gateway S128 KNX 2 channel gateway KNX Order number 4940302 Number of communication objects 1130 Number of group addresses 1280 Number of ...

Page 5: ...address between 0 and 63 is assigned during the further commissioning process As the address assignment is automatic the device order is random The individual ECGs lights therefore need to be identified during the further commissioning process see below The addressing of individual ECGs in the system is either based upon the short address individual addressing or upon a DALI group address group ad...

Page 6: ...om the connected KNX system into DALI telegrams and status information from the DALI bus into KNX telegrams The DALI gateways KNX are Category 1 devices in accordance with EN 62386 103 This means the device must only be used in DALI segments with connected ECGs and not with other DALI control devices within the segment no multi master function Power supply for the up to 64 resp 128 connected ECGs ...

Page 7: ...ction for easy replacement of individual faulty ECGs Manual control of group and broadcast telegrams via control buttons on the device Indication of a fault status via LEDs on the device The special surface for the configuration of DALI segments is designed as a DCA Device Configuration App for the ETS5 Please remember to install the corresponding ETS App in addition to the product database knxpro...

Page 8: ...port and import of scenes In order to be able to use configured scenes easily in other projects the possibility of importing and ex porting has been implemented 2 4 5 Editing and exporting importing description texts All description texts of the groups or the single ECGs can be edited now additionally centrally There the texts can also be easily imported or exported from other file formats 2 4 6 M...

Page 9: ...ponding ETS App installed in the ETS5 see chapter 3 3 ETS app DCA 3 2 ETS app DCA The application for the DALI gateway KNX is based on the standard surface for the configuration of communication objects and parameters as well as a special surface for configuring the DALI bus system This special surface is designed as a DCA Device Configuration App for the ETS5 All required program data are automat...

Page 10: ...iguration is performed in the DCA tab First the assignment of the ECGs to the desired groups should be carried out This work can be carried out offline without connection to the KNX or without connection to the DALI gateway KNX The actual DALI commissioning is only possible online that means a connection to the device is necessary In this step all connected ECGs are searched and found and can then...

Page 11: ...s solution has the disadvantage that each of these devices is assigned a separate DALI short address This means that two tunable white three RGB or even four short addresses are required to control a module With a maximum number of 64 available short addresses per DALI segment the number of lights that can be used is greatly reduced With a DT 8 de vice however only one short address is required fo...

Page 12: ... is practically possible In practice it is common to set the value which is closest Please pay attention to the instructions of the ECG or light manufacturer Usually the XY values which are supported by the lamp are specified here Values outside of the specified range can generate non reproducible colours 4 3 Colour dislay via colour temperature A subset of all possible colours in the colour space...

Page 13: ...islay via 3 or 4 colour channels RGBWAF Principally a colour is created by mixing different individual colours different white tones RGB or RGBW A colour can therefore also be displayed based on the mixing ratio of different single colours e g 50 red 0 green 60 blue The colour definition in this case is not exact but depends greatly on the specific physical attributes of the LEDs used to create th...

Page 14: ...t hand corner The manual mode automatically ends 60 seconds after the last time the button has been activated If manual mode is active shortly press the same button again to toggle between the different manual mode levels The RGB LED on the Man button shows which level you are currently on The individual levels have the following meaning Manual mode level 1 LED on Man button lights up permanently ...

Page 15: ...ioning and installation process to prevent constant emergency lighting and battery discharge If the gateway detects a fault the LEDs on buttons 2 10 to 4 12 and 7 15 to 8 16 show the exact type of fault The LED is constantly lit up in red The faults are as follows LED Button 2 10 Converter fault LED Button 3 11 ECG fault LED Button 4 12 Lamp fault LED Button 7 15 DALI short circuit LED Button 8 16...

Page 16: ...t the ETS see chapter 11 5 ECG easy replacement A long keypress on button 6 14 activates the converter inhibit mode If the power supply for the connected emergency lights is turned off within 15 minutes after activating the converter inhibit mode the lights are turned off instead of changing into emergency mode This operating mode may be necessary during the commissioning and installation process ...

Page 17: ...If the power supply for the connected emergency lights is turned off within 15 minutes after activating the converter inhibit mode the lights are turned off instead of changing into emergency mode This operating mode may be necessary during the commissioning and installation process to prevent constant emergency lighting and battery discharge If the gateway detects a fault the LEDs on buttons 2 10...

Page 18: ...ification process on the device display or fault e g ECG was without power when the gateway was started the light level is automatically corrected after 60 seconds 6 3 Staircase mode The staircase mode is only available for groups In this mode the value set via a switch dim or value telegram is automatically changed to the switch off value after a programmable time The lights can be switched off i...

Page 19: ... off value and can again be controlled individually If panic mode is active scenes and time scheduling are deactivated 6 6 Operating mode hierarchy Some of the individual operating modes described above have higher functions and roles for the operation of the system as a whole A prioritisation or hierarchy of operating modes is therefore required The panic mode has the highest priority The permane...

Page 20: ...ght errors The scanning cycles can be configured If the cycle is 1 second standard setting and 64 ECGs are connected the complete process of scanning for ECG and light errors takes 128 seconds 1 second per ECG and type of error It can therefore take up to about 2 minutes before a fault that has occurred is recognised For each ECG a communication object is available to send the information to the K...

Page 21: ...error rate or number of faulty ECG in the whole DALI segment can be made available via communication objects In contrast to the group level at gateway level the percentage and number of errors can be broken down further according to error type The alarm threshold for the error rate can be individually set for ECG light and converter errors For further details regarding the communication objects pl...

Page 22: ...ccor dingly The object numbers of the 2nd channel can be calculated via an offset of 640 8 1 General objects The date and time are defined across all channels for the whole device In the 1 channel device object number 21 and 22 has been used This was changed for the 2 channel device to object number 1 and 2 The general communication objects exist for each channel and apply to the function of those...

Page 23: ... groups or ECGs are disregarded Note This object is only visible if you select GENERAL Special function Enable broadcast in the parameters 4 Broadcast Set Value Value 1 Byte 5 001 CW This object is used to simultaneously set all connected lights to a certain value However any connected ECGs that are in special mode Panic Mode are excluded and the DALI bus is addressed sequentially A delay between ...

Page 24: ...ECG and converter errors are hereby taken into account Please remember that for each connected device a fault is counted just once If an ECG or converter error has been detected a simultaneous light error will no longer be detected or counted 16 Lamp Failure Exceeds Threshold Yes No 1 Bit 1 005 CRT This object is used to report that the total of all lamp failures recognised by the gateway exceeds ...

Page 25: ...k Bit 23 22 21 20 19 18 17 16 1 1 1 1 1 1 1 1 Bit 31 30 29 28 27 26 25 24 1 1 1 1 1 1 1 1 22 Failure Status Lamp ECG Status 8 Bit 238 600 CWT This object is used to send the error status of lamp or ECG errors in the DALI segment when the system is started or when a change has taken place Bit 0 5 refer to the number of the ECG Bit 6 represents a lamp error Bit 7 an ECG error For example Bit 7 6 5 4...

Page 26: ...ich can be assigned to groups resp ECGs in the corresponding parameters Therefore it is possible to activate and deactivate the ECG power with an additional switching actuator 55 Energy Saving Object 1 On Off 1 Bit 1 001 CRT With the appropriate assignment in the parameters this object is switched off when associated groups or ECGs are switched off This allows a separate power supply to be switche...

Page 27: ...ement size Bit 1 to 3 deleted is interpreted as a stop telegram 73 G1 Set Value Value 1 Byte 5 001 CW Sets the value of group 1 Object 73 is shown for the following parameter G1 behaviour additional value setting object with dim time 74 G1 Set Value Value Time 3 Byte 225 001 CW Group 1 can bet set to a certain value and dim time via this object For this data point time is defined as a multiple of ...

Page 28: ... for the following parameter G1 Analysis and maintenance Type of error status object 78a G1 Failure Status Yes No 1 Bit 1 005 CRT Sends the error status for a light or ECG failure in the group 78b G1 Failure Status Status 1 Byte 5 x CRT Sends the error status for a light or ECG failure in the group as a 1 Byte object Meaning Bit 0 Light error Bit 1 ECG error 79 G1 Failure Status Status 4 Byte CRT ...

Page 29: ... 1 via this object 96 G1 Operating Hours Value 4 Byte 13 100 CW Counts the operating hours in the group This value is transmitted in seconds according to DTP 13 100 97 G1 Life Time Exceeded Yes No 1 Bit 1 005 CW This object shows whether the maximum life span set in the parameters has been exceeded Note If the treshold has been exceeded an alarm is issued via this object by sending 1 This status i...

Page 30: ...0 is automatically converted into the possible colour temperature range 86 G1 Colour Temperature Warmer Cooler 4 Bit 3 007 CW Changes the colour temperature in the group Bit 3 is set to dim up and deleted to dim down Bits 0 to 2 refer to the increment size Bit 0 to 2 deleted is interpreted as a stop telegram 90 G1 Colour Temperature Status 2 Byte 7 600 CRT Sends the set colour temperature as statu...

Page 31: ...e transferred 84 G1 Colour RGB Blue Value 1 Byte 5 001 CW Sets the colour of the group Here the values for blue B are transferred 86 G1 Colour RGB Red Brighter Cooler 4 Bit 3 007 CW Changes the colour red in the group Bit 3is set to increase the percentage of red and deleted to reduce the percentage of red Bits 0 to 2 refer to the increment size Bit 0 to 2 deleted is interpreted as a stop telegram...

Page 32: ...s an HSV value The hue values are transferred as values between 0 and 360 Please note that only a resolution of approx 1 4 is possible with the 5 003 data type used 83 G1 Colour Saturation Value 1 Byte 5 001 CW Sets the saturation level The saturation values are transferred as values between 0 and 100 86 G1 Colour HSV Fading Hue Brighter Cooler 4 Bit 3 007 CW Changes the hue within the group Bit 3...

Page 33: ... CW Sets the colour of the group The values for red R are transferred here 83 G1 Colour RGB Green Value 1 Byte 5 001 CW Sets the colour of the group The values for green G are transferred here 84 G1 Colour RGb Blue Value 1 Byte 5 001 CW Sets the colour of the group The values for blue B are transferred here 85 G1 Colour White Value 1 Byte 5 001 CW Sets the colour of the group The values for white ...

Page 34: ...green as status of the group 93 G1 Colour RGB Blue Status 1 Byte 5 001 CRT Sends the selected colour blue as status of the group 94 G1 Colour White Status 1 Byte 5 001 CRT Sends the selected colour white as status of the group HSVW separate objects See chapter HSV page 33 XY DPT 242 600 The colour is identified through an XY value between 0 and 1 This value range is converted into a range from 0 t...

Page 35: ...o 100 2 Bits in the lower Byte show whether the XY values and brightness levels are valid 90 G1 Colour Temperature XY Status 6 Byte 242 600 CRT Sends the selected colour via the XY values as status of the group XY separate objects Obj Object name Function Type Flags 81 G1 Colour X Value 2 Byte 7 001 CW Sets the X value in a range from 0 to 65535 82 G1 Colour Y Value 2 Byte 7 001 CW Sets the Y valu...

Page 36: ...s panic emergency mode Bit 3 is set to dim up and deleted to dim down Bits 0 to 2 refer to the increment size Bit 0 to 2 deleted is interpreted as a stop telegram 521 ECG 1 Set Value Value 1 Byte 5 001 CW Sets the value of ECG1 unless it is in special mode test mode emergency lights panic emergency mode 522 ECG1 Enable Yes No 1 Bit 1 003 CW Note Object 522 is shown for the following parameter ECG ...

Page 37: ... a lamp are sent via this object The internal counter can be set to 0 Reset or another value via this object Please remember The Write flag is switched off in the presetting 528 ECG 1 Life Time Exceeded Yes No 1 Bit 1 002 CRT This object is used to send a status message when the configured lifetime of a lamp is exceeded 8 6 Objects for scene control The scene objects are collected in the scene cha...

Page 38: ...t is used for the relative dimming of scene 1 Bit 3 is set to dim up and deleted to dim down Bits 1 to 3 refer to the increment size Bit 0 2 deleted is interpreted as a stop telegram Attention The Min Max Setting already defined in the group configuration are taken into account ...

Page 39: ...e following description this prefix will be omitted 9 1 General Three parameter pages are available under the heading General The parameters are described below 9 1 1 Parameter page behaviour Parameter Settings Behaviour on KNX Failure No Action Switch to On Value Switch to Off Value Switch to Emergency Value Use this parameter to set the behaviour of the connected ECGs lamps on KNX failure Behavi...

Page 40: ... switch status and value status of the connected ECGs and groups Send Status Value During Dimming If Change 2 If Change 5 If Change 10 If Change 20 inactive Use this parameter to set whether and when you would like a value status to be sent via a 4 bit dim telegram during dimming relative dimming If you use the setting inactive the value is only sent after the dimming process is complete Behaviour...

Page 41: ...use the central failure object for ECG and lamp faults object number 22 Function of Failure Object Total number of Failures Failure Rate 0 100 Use this parameter to select whether you want to use the failure analysis objects objects number 15 17 and 19 to report the total amount of errors or the error rate in Threshold for Total Failures 1 2 3 100 Configures a threshold value for the general failu...

Page 42: ...tem can be used Broadcast for Colour ECGs DT 8 None Colour Temperature RGB Colour RGBW Colour XY Colour Determines which type of colour control is to be used for the broadcast commands Please note The status information is only updated if the selected type of colour control matches the type defined in the group If RGB colour is selected Selection of Object Type RGB 3 Byte combined Object RGB separ...

Page 43: ... off Delay for Switching On the ECGs 0 1 Seconds 0 2 Seconds 0 3 Seconds 1 Second 2 Seconds Delay until the ECGs are switched on During this time the actuator controlling the power supply must have switched safely Disable manual Operation No Yes Use this parameter to disable the manual mode directly on the device reference to 5 Manual Mode Dim To Cold Colour Temperature at Value 0 1000 10000 3000 ...

Page 44: ...low 9 2 1 General Parameter Settings Group description Use this parameter to define a group description To simplify the overview this description will be displayed for all communication objects For example Test group Operation Mode Normal Mode Permanent Mode Normal Night Mode Staircase Sets the operating mode of the group If Permanent Mode is selected ...

Page 45: ...50 of the previous value After a further minute the switch off value is set Delayed dimming After the set time the switch off value is dimmed within one minute Automatic Switch OFF After min 1 Minute 2 Minutes 3 Minutes 4 Minutes 5 Minutes 10 Minutes 15 Minutes 90 Minutes Use this parameter to set the time after which a group in night mode automatically switches off This parameter is only visible ...

Page 46: ...ect an object appears which enables control of the group when the value is 1 If you select Staircase function Disable Object an object appears which only disables the staircase function when the value is 1 This can be used to deactivate the staircase function for a certain time period for example during cleaning Behaviour on release No change Change to switch on value Change to switch off value Th...

Page 47: ...elay see next parameter when all ECGs in a group are switched off When the group is switched back on the object is reset to 1 to reactivate the supply After reactivating the first DALI telegram is sent delayed When the device is switched on this object is always set to 1 by default Delay for Switching OFF the ECG Power 10 Seconds 30 Seconds 1 Minute 2 Minutes 5 Minutes 10 Minutes Sets the time del...

Page 48: ...e in 2 Minutes Dim to Value in 5 Minutes Dim to Value in 10 Minutes Sets the switch on behaviour Switch Off Value 0 5 10 45 50 95 99 Sets the switch off value Switch Off Behaviour Set Value immediately Dim to Value in 3 Seconds Dim to Value in 6 Seconds Dim to Value in 10 Seconds Dim to Value in 20 Seconds Dim to Value in 30 Seconds Dim to Value in 1 Minute Dim to Value in 2 Minutes Dim to Value i...

Page 49: ...ime always refers to the complete value range A time of 30 s therefore means a value change of 100 within 30 s If the value within a scene only changes by 50 the change will only take 15 s Time for Dimming 3 Seconds 4 Seconds 5 Seconds 6 Seconds 10 Seconds 20 Seconds 30 Seconds 60 Seconds Sets the dim time for relative dimming in relation to a value range from 0 to 100 Max Value for Dimming 50 55 ...

Page 50: ...and dimming time the dimming time is ignored in the ETS 9 2 3 Analysis and service Parameter Settings Type of Failure Status Object 1 Bit 1 Byte Determines whether the error object of the group is to be sent as a 1 Bit object without differentiating the type of error status or as an 8 Bit object with error type differentiation Additional Failure Objects No Yes Use this parameter to select whether ...

Page 51: ...is sent 9 2 4 Colour control Parameter Settings Colour Control Type none Colour Temperature RGB Colour RGBW Colour XY Colour Use this parameter to select the type of colour control you would like to use for the group Please make sure that the ECGs in the group support this type of control If colour temperature is selected Colour Temperature when Switching On 1000 K 10000 K 3000 K Sets the colour t...

Page 52: ...st 10 Seconds standard 20 Seconds slow 40 Seconds Use this parameter to select how quickly you want to change the colour temperature during dimming If RGB colour is selected Selection of Object Type RGB 3 Byte combined Object RGB separated Objects HSV separated Objects Selects the objects that will be used for the colour control Colour Value when Switching On Colour selection Use this parameter to...

Page 53: ...to select how quickly you want the colour temperature to change Colour changing Fading Time via Dimming fast 10 Seconds standard 20 Seconds slow 40 Seconds Use this parameter to select how quickly you want the colour temperature to fade during dimming If RGBW colour is selected Colour Control Type RGBW 6 Byte combined Object 251 600 RGBW separated Objects HSVW separated Objects Selects the objects...

Page 54: ...Seconds 60 Seconds 90 Seconds Use this parameter to select how quickly you want the colour temperature to change Colour changing Fading Time via Dimming fast 10 Seconds standard 20 Seconds slow 40 Seconds Use this parameter to select how quickly you want the colour temperature to fade during dimming If XY colour is selected Selection of object type XY separated objects XY combined object 242 600 s...

Page 55: ...last object value please remember that the colour set in the ETS will be used if the object value is invalid Colour changing Fading Time immediately 1 Second 5 Seconds 10 Seconds 20 Seconds 30 Seconds 60 Seconds 90 Seconds Use this parameter to select how quickly you want the colour temperature to change 9 3 ECGs The settings for the ECGs are made on two parameter pages provided that this ECG is d...

Page 56: ... set the operating mode in which the ECG shall be operated Night operation is controlled via a central object no 12 Function of Additional Objectt No Obejct Disable Object Release Object This parameter can be used to define the function of an additional object If the Disable object is selected an object is displayed which blocks operation of the ECG if the value is 1 If the Enable object is select...

Page 57: ...is dimmed within one minute Activate Permanent Mode and Ignore Telegrams Automatic Switch Off after minutes 1 minute 2 minutes 3 minutes 4 minutes 5 minutes 10 minutes 15 minutes 90 minutes This parameter is used to decide after how many minutes the ECG shall be switched off Function of Additional Object No Object Disable Object Release Object Staircase function Disable Object Use this parameter t...

Page 58: ...ine via Object None Energy Saving Object 1 16 Here you define the object with which the power supply is to be switched off This parameter is only visible if this function was previously set on the General Special Functions parameter page see 9 1 General Operating hours Calculation Yes No This parameter can be used to set whether an individual operating hour count for the ECG is desired Operating h...

Page 59: ...ng value prior to the lamp being switched off Switch ON Behaviour Set Value Immediately Dim to Value in 3s Dim to Value in 6s Dim to Value in 10s Dim to Value in 20s Dim to Value in 30s Dim to Value in 1 Minute Dim to Value in 2 Minutes Dim to Value in 5 Minutes Dim to Value in 10 Minutes Use this parameter to set the switch on behaviour Switch OFF Value 0 5 10 45 50 95 99 Use this parameter to se...

Page 60: ...o Value in 5 Minutes Dim to Value in 10 Minutes Use this parameter to configure the behaviour on receipt of a new dimming value via value setting Please remember that the dim time always refers to the full value range Accordingly a dimming time of 30 s means a value change of 100 within 30 s If the value within a scene is only changed by 50 the change is performed within 15 s Time for Dimming 3 Se...

Page 61: ...his parameter to select the object that minimum and maximum values are valid for It is possible to set for example 60 via dimming and 100 via value setting Switch ON via Dimming No Switch ON with Dimming Object Switch ON with Value Object Switch ON with Dimming Value Object Use this parameter to select whether a switched off group should be switched on when receiving a relative 4 Bit dimming objec...

Page 62: ...sioning is carried out individually for each channel When calling the DCA channel 1 is preselected The selection buttons can be used to select between channel 1 and channel 2 only in case of using a 2 channel device The following description refers to the commissioning of one channel DALI Gateway KNX ...

Page 63: ...g the planning phase the list is empty as the ETS is not yet connected to the system To start with you should plan and name the ECGs Use the description field to enter a name light number room number etc Double click to display an editing window which will allow you to enter a maximum of 30 characters opened Now assign the individual ECGs to their corresponding groups Use drag and drop to pull the...

Page 64: ...tive you need to program the physical address of the gateway The communication between the plug in and the gateway is based on the physical address Use the commissioning page and the new installation button to start the teach in process of the connected DALI segment During the teach in process all ECGs are automatically recognised and each ECG is assigned a short address from 0 63 Depending on the...

Page 65: ... process it might be useful to switch certain groups or all connected lamps on or off You can also send broadcast commands via the context menu in order to for example switch all lights on or off Once an ECG has been identified you can drag and drop it onto the previously planned element in the ECG configuration table Once an ECG has been dragged into the ECG configuration table it disappears from...

Page 66: ...settings onto the gateway and the ECGs you must press the Download button The download can take up to 1 minute The progress bar informs about the current status Once the download is complete all previously planned ECGs are programmed in the system with the DALI configuration The respective devices are marked with an OK flag in the ECG configuration table If no group has been assigned yet the flag ...

Page 67: ... Discharge lamp ECG Type 3 Low voltage lamp ECG Type 4 Incandescent lamp ECG Type 5 0 10V Converter ECG Type 6 LED ECG Type 7 Relais module ECG Type 8 Colour module RGB ECG Type 8 Colour module tunable white During the commissioning lamps ECGs are identified visually ON OFF flashing It is therefore crucial that all lamps and ECGS operate correctly If the gateway identifies a lamp or ECG fault duri...

Page 68: ... ECG fault already exists during the search process of the initial installation the device is usually not detected This means that the number of ECGs found does not correspond to the number that was expected ECG faults are only displayed in the manner described above if the ECG concerned has been previously programmed and is known to the gateway 11 2 ECG and group detail info In addition to the EC...

Page 69: ...ight hand side tree Additional information for the ECGs is displayed via tooltip in the tree on the right hand side To activate the tooltip hover over the position with the mouse 11 2 2 ECG info in the ECG table Double click to open another window with further details 11 2 3 Group info in the group tree Additional information for the group is displayed via tooltip in the group tree ...

Page 70: ...CGs can be individually controlled Emergency Converter The emergency converter can be set into inhibit mode If the power supply for the connected emergency lights is turned off within 15 minutes after activating the converter inhibit mode the lights are turned off instead of changing into emergency mode This operating mode may be necessary during the commissioning and installation process to preve...

Page 71: ...oning Manual DALI gateway S64 KNX S128 KNX 71 Group menu in the left hand side tree Context menu in the ECG table ECG menu in the right hand side tree The following commands are available On Off Blink Initialize ECG ...

Page 72: ...ible to get ECGs with an external programmed short address even if their long address is not defined and still 0xFFFFFF In order to delete those short address the checkbox can be ticked Delete externally programmed Short Address Please ensure that all ECGs are powered at the time of post installation to avoid that those ECGs are deleted from the gateway memory In case of the special parameter sett...

Page 73: ... ECGs have to be identified and you must use the post installation function Please remember that the quick exchange is only possible for devices of the same type You cannot for example replace an ECG for self contained battery emergency lamps with a device for LEDs If a quick exchange is not possible because of any of the conditions above the gateway terminates the process with an error code The d...

Page 74: ...rs to the complete value range A time of 30s therefore means a value change of 100 within 30 s If the value within a scene only changes by 50 the change will only take 15 s To assign a flexible KNX scene to a DALI scene the parameter KNX Scene is used Hereby a flexible assignment can be defined to activate this scene with another KNX scene via KNX communication object The KNX scene numbers 1 to 64...

Page 75: ...colour Keep value In this case the current value remains unchanged when the scene is invoked The entry field for the value is disabled Any entry in the value field is ignored Keep colour In this case the current colour remains unchanged when the scene is invoked The entry field for the colour is disabled Any entry in the colour field is ignored To delete an entry select a group and use drag and dr...

Page 76: ...NX S128 KNX 76 12 2 Colour entries Each group can only support one type of colour control The following window is shown for colour temperature For RGB RGBW or HSV the window is as follows For the XY option the following window appears ...

Page 77: ...ed The command setting the value and colour of the group is executed This means you can check the correct properties before programming the whole scene If Keep Value or Keep colour have been selected the current values are kept and the new values are not activated 12 5 Testing the whole scene After a scene has been programmed the button becomes active Press the button to activate and execute the s...

Page 78: ...odule can also be used for general time based colour changes For example a building could be lit up in red for the first half of the night and in blue for the second half 13 1 Configuration To create a sequence of different colour settings up to 16 different templates can be created A template combines different actions which perform a value or colour control event at a configurable time Select th...

Page 79: ...late The middle part of the page is used to create an action list All groups that have been selected automatically perform an action at the configured time Altogether a maximum of 300 actions can be stored on a DALI gateway if all templates are used A context menu is available to control and create action lists To open the context menu move the mouse pointer onto an action and press the right mous...

Page 80: ...the value field However if this value exceeds the possible value range it is automatically limited to the maximum value For example if you enter 200 for the function Set value the maximum value 100 is automatically entered The following functions are possible for an action Set value This function sets the brightness level of a group The permitted value range is between 0 and 100 Value This functio...

Page 81: ...r spectrum can be set Colour RGBW This function sets the colour values of DT 8 devices that support the primary colours RGB or RGBW On the ECG the colour is also changed if the light is turned off at the time of the action The values for each primary colour can be entered separately The permitted value range for RGB and W is between 0 and 100 The final colour is a mixture of the different primary ...

Page 82: ...actions This also applies to the selected method A DT 8 device with XY control for example will ignore an RGBW action and vice versa If the DT 8 devices within a group or template use different methods but you want them all to perform a colour change at the same time you need to set up two actions with different functions for the same point in time Once an action table within a template is complet...

Page 83: ...ted 13 5 Timer To ensure the safe operation of the colour control mode the exact time and date are required on the device This has to be provided by the KNX in form of 3 Byte communication objects The precision of the DALI gateway s internal time calculation is limited It is therefore essential to update the time at least once a day When the application is started the device automatically sends a ...

Page 84: ...Time control Manual DALI gateway S64 KNX S128 KNX 84 The template is saved as an xml file in the desired target directory ...

Page 85: ...from the DALI gateway is exported and transferred to the ETS DCA configuration It should be noted that all DCA data in the ETS is overwritten with this data In order to subsequently load this configuration into the DALI gateway the Restore function MUST be executed under Commissioning Restore see chapter 11 6 Data restore Edit Descriptions The description texts of the ECGs the groups and input dev...

Page 86: ...ex 4 description Raum 4 text index 5 description text index 6 description text index 7 description text index 8 description text index 9 description text index 10 description text index 11 description text index 12 description text index 13 description text index 14 description text index 15 description text index 16 description GRP_TEXT xml If you do not want to overwrite all texts you can simply...

Page 87: ...nts used within the product are listed below including their copyright holders and the license conditions ______________________________________________________________________ _______ 1 Package Name ColorMine Version 1 1 3 https www nuget org packages ColorMine Copyright c 2013 ColorMine org MIT License License MIT The MIT License MIT Copyright c 2013 ColorMine org MIT License Permission is hereb...

Page 88: ...tact Manual DALI gateway S64 KNX S128 KNX 88 16 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Tel 49 7474 692 0 Fax 49 7474 692 150 Hotline Tel 49 7474 692 369 hotline theben de www theben de ...

Reviews: