background image

Installation Manual

TS4-F, TS4-A-F, TS4-A-2F and

RSS Transmitter

Summary of Contents for RSS Transmitter

Page 1: ...Installation Manual TS4 F TS4 A F TS4 A 2F and RSS Transmitter...

Page 2: ...ed by trained professionals only Tigo does not assume liability for loss or damage resulting from improper handling installation or misuse of products Remove all metallic jewelry prior to installing t...

Page 3: ...lation Notes 10 TS4 F Installation 11 12 TS4 A F Installation 13 TS4 A 2F Installation 16 17 18 19 20 21 RSS Transmitter Commercial Installation Technical Speci cations TS4 F 22 Mechanical Speci catio...

Page 4: ...hutdown System Transmitter for rapid shutdown activation of TS4 F TS4 F TS4 A F RSS Transmitter Module Level Power Electronics Transmitter integrated in CPS 25 50 60kW Tigo RSD wire boxes or TS4 A F u...

Page 5: ...lled at the PV module factory Connected in series like regular modules No additional wiring connections to make Bracket clips to module frame without tools TS4 A F outputs are connected in series to f...

Page 6: ...r as shown and can be installed inside the inverter or external to it Method of Operation All TS4 F units start in the OFF position and measure 0 6V at the output When power is supplied to the RSS Tra...

Page 7: ...on the frame or bolted to the racking if needed TS4 A F cable glands must not be facing up Allow clearance between PV module and mounting surface for air circulation around TS4 A F For installation on...

Page 8: ...on the frame or bolted to the racking if needed TS4 A F cable glands must not be facing up Allow clearance between PV module and mounting surface for air circulation around TS4 A F For installation o...

Page 9: ...ly an external voltage source to a module or string equipped with TS4 F or TS4 A F TS4 A 2F units If parallel string connections are needed rst connect the TS4 F or TS4 A F to the PV modules then conn...

Page 10: ...x are installed and connected in series just like standard PV modules Connect modules with TS4 F in series before powering on the RSS Transmitter 10 1 2 4 123A 4 123A 4 123A 4 123A TS4 F TS4 F TS4 F T...

Page 11: ...disconnecting the TS4 A F inputs from the module junction box 11 Tigo Rapid Shutdown DO NOT DISCONNECT UNDER LOAD NEC 690 12 2017 and C22 1 2015 Rule 64 218 4 123A TS4 A F Tigo Rapid Shutdown DO NOT...

Page 12: ...sconnecting the TS4 A 2F inputs from the module junction box 12 1 Connect PV modules to TS4 A 2F inputs 2 Connect TS4 A 2F outputs in series Tigo Rapid Shutdown DO NOT DISCONNECT UNDER LOAD NEC 690 12...

Page 13: ...00VAC Power Supply 2 RSS Transmitter 3 RSS Core CT RSS Core inputs Line RSS Core inputs Ground LED Signal Neutral LED Power 12VDC VIN 12VDC GND V ADJ V G L2 L1 V Place rapid shutdown system label no m...

Page 14: ...System Transmitter N N L L V ADJ V G L2 L1 V Turn on AC power to Transmitter power supply to activate keep alive signal Note Install TS4 F before powering on RSS Transmitter Max string length 30 modu...

Page 15: ...Appendix TS4 F TS4 A F RSS Transmitter...

Page 16: ...A Output Output Power Range 0 475W Output Voltage Range 0 VOC Communication Type Power Line Communication PLC Rapid Shutdown UL Listed NEC 2014 2017 690 12 Yes Impedance Matching Capability No Output...

Page 17: ...60 Cooling Method Natural Convection Dimensions with cover 178 5mm x 134mm x 25 5mm Weight base and cover 670g Outdoor Rating IP68 NEMA 3R Cabling Type H1Z2Z2 K Output Length 1 2m standard other lengt...

Page 18: ...Voltage 16 90V Maximum Continuous Input Current IMAX 12 5A Maximum Power 500W Output Cable Length 1 2m standard other lengths available Connectors MC4 comparable standard Communication Type PLC Maxim...

Page 19: ...e per input 1 16 90V Maximum Current per input 15A Maximum Power total 1000W Output Cable Length 1 2m portrait or 2 2m landscape Connectors MC4 standard Communication Type PLC Maximum System Voltage 1...

Page 20: ...le Core 150A Dual Core 300A Maximum MPPT String Voltage 1500VDC Internal Opening for Wires 25mm Outside Dimensions 59mm Maximum Number of Strings per Core 10 Maximum String Length 30 modules Environme...

Page 21: ...30 seconds after rapid shutdown activation before disconnecting DC cables or turning off DC disconnect 21 Test your rapid shutdown system by switching off the AC power to the RSS Transmitter or invert...

Page 22: ...ww tigoenergy com P 1 408 402 0802 F 1 408 358 6279 sales tigoenergy com INSTALLATION COMPLETE Problems TS4 F Troubleshooting Guide For more details on designing and installing solutions powered by Ti...

Reviews: