background image

TOA Electronics Europe GmbH

1

 

(Additional) Installation Manual

SYSTEMS REMOTE MICROPHONE WITH

MONITORING OF MICROPHONE CAPSULE

RM-200MS

This  manual  contains  the  special  installation  information  for  the  RM-200MS.  The  RM-200M  instruction
manual  contains  all  instructions  of  setting  and  operation,  so  both  manuals  are  required  to  operate  the
RM-200MS.

Please follow the instructions in this manual to obtain the optimum results from this unit.

We also recommend that you keep this manual handy for future reference.

  IMPORTANT NOTE

DIFFERENT CONNECTION !

The connection of the RM-200MS differs from the RM-200M connection!

Do not connect the RM 200MS with the standard RM-200M using the RJ45 link
connectors! This will cause either no microphone capsule failure indication or
may result in an insufficient power supply to the remote microphones.

  DESCRIPTION

The  microphone  capsule  of  the  RM-200MS  is  monitored  on  failure,  and  a  failure  control  signal  is
provided  to  indicate  a  failure  on  the  microphone  capsule.  This  function  is  required  for  the  remote
microphone (for emergency purposes) to comply with the EN 60849.

In  case  of  a  microphone  capsule  failure,  the  failure  LED  on  the  VM-2000  and  RM-200M(S)  will
illuminate. It is also possible to control an extra LED for a separate failure indication.

  DIFFERENCE TO THE RM-200M

The failure control signal of the RM-200MS is sent to the VM-2000 using a pair of connectors of the
RJ45 port. On the standard remote microphone RM-200M, this pair is used for the DC power supply,
therefore the RM-200MS must not be linked with the standard RM-200M using the link connectors.

  CONNECTION OF THE RM-200MS TO THE VM-2000

The wire connected to the pins 1 and 2 of the
RJ45  connector  are  used  for  the  failure
control  signal  instead  of  power  supply.  So
these  wires  must  be  disconnected  from  the
VM-2000. Wire 1 (once connected to  pin 1  of
the RJ45 connector) must be connected to pin
15  of  the  CONTROL  I/O  connector,  and  wire
2 to pin 16.

At  the  location  of  the  VM-2000,  the  control
signal  can  be  separated  from  the  incoming
cable  by  using  the  VM-RJA  board,  and  the
RJ45 connection to the VM-2000 can be done by a ready-made cable. The separated failure control
signal will be connected to the external failure input on the I/O CONTROL connector. Please refer to
the next page.

S

8

7

6

5

4

3

2

1

to RM-200MS

LINK

CONTROL I/O

VM-2000

14

25

13

1

Reviews: