INSTALLATION 

INSTRUCTIONS 

       

TSPC240-124UPS   Uninterruptible Power Supply

 

 

Output Current 

Mode 

I

out

 Nominal             

@ 24.0 - 26.0V 

I

out 

Boost             

@ 23.4 - 23.8V 

Normal 10A* 

12A** 

Buffer 10A* 

12A** 

  *  Ambient temperature up to +60°C. Observe output current de-rating with Input Voltage. Refer to Datasheet. 

** 

Ambient temperature up to +40°C. Observe output current de-rating with Input Voltage. Refer to Datasheet. 

 

User Settings:                                                                                                  Figure 1:

 

 

Battery Test Interval:   

15 seconds or 10 minutes user selectable with switch 
 
 

 

Signal Connector:   

Remark:

 Tightening torque 0.19Nm for all contacts.

        Figure 2: 

 
Temp.Sensor:

 Connect external sensor for automatic end of charge 

battery compensation. 

Battery Remote ON/OFF:

 Enables remote disconnection of the   

battery. 

DC OK: 

Closed contact indicate that the output voltage is higher   

than 82-90% of the nominal output voltage (24V).

 

BAT OK:

 Closed contact indicates that the battery is charged and   

has low resistance (100m

 max). During battery operation, open contacts indicate   

that the battery is approaching (within approx.. 1V) the disconnection voltage level. 

AC-IN-OK:

 Closed contact when the AC supply voltage is present. Open contacts indicate loss of AC Supply Voltage or overload at low AC supply 

voltage levels.

 

              Parameter 

Condition 

Settings 

Nominal AC Input Range [VAC] 

High line 

220-240 

Input AC Voltage Range [VAC] 

High line 

187-264 

Nominal AC Input Range [VAC] 

Low line 

100-120 

Input AC Voltage Range [VAC] 

Low line 

85-132 

Input Frequency Range [Hz] 

 

47 - 63 

Output Voltage [V] 

Normal Mode 

24.0-26.0V (adjusted by POT) 

Output Voltage [V] 

Buffer Mode 

23.4-23.8V (Internally set) 

Electrical Connections   

& Wire Size 

AC Supply Input 

1 - 4 mm

2

 [AWG17-AWG11] 

Tightening Torque 0.6Nm 

DC Output 

2 - 10 mm

2

 [AWG14-AWG7] 

Tightening Torque 1.76Nm 

Battery Input 

2.5 - 10 mm

2

 [AWG13-AWG7] Nominal Power 

4 - 10 mm

2

 [AWG11-AWG7] Boost Power 

max. resistance 10m

 

Tightening Torque 1.76Nm 

Battery Charging Current [A] 

Normal Mode 

0.8…1.2 

Nominal Battery Voltage [V] 

25°C Ambient 

13.6 (Factory Set) 

Battery Adjustment Range [V] 

Normal Mode 

13.0…14.4 

Battery Test Current [A] 

Normal Mode 

2.5A for 60ms (typ) 

Battery Test Interval [s] 

Normal Mode 

15s or 8..10mins (Set by switch: Fig.1) 

Battery Warning Voltage [V] 

Buffer Mode 

10.4...11.4 

Battery Disconnection Voltage [V] 

Buffer Mode 

9.1…10.2 

Thermal Protection 

Buffer Mode 

100°C (at back of chassis) 

Automatic Battery Temperature 

Compensation Range 

Normal Mode 

-15°C…50°C (external sensor temp. Fig.2) 

Battery Remote ON/OFF 

Buffer Mode 

Switch 5V/5mA (min) to GND (Fig.2) 

Level: 0…0.5V 

Signal Relay Contact Rating 

(Resistive Load) 

Signal Monitoring 

60VDC 0.5A    (Fig.2) 