background image

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT —

This Document is 

customer property

 and is to remain with this unit.  Please return to service information

pack upon completion of work.

Installer’s Guide

These instructions do not cover all variations in systems
nor provide for every possible contingency to be met in
connection with installation. All phases of this installa-
tion must comply with NATIONAL, STATE AND LOCAL
CODES. 

Should further information be desired or should

particular problems arise which are not covered sufficiently for
the purchaser’s purposes, the matter should be referred to your
installing dealer or local distributor.

A. GENERAL

WARNING

!

This information is intended for use by individuals possess-
ing adequate backgrounds of electrical and mechanical
experience. Any attempt to repair a central air conditioning
product may result in personal injury and or property dam-
age. The manufacturer or seller cannot be responsible for the
interpretation of this information, nor can it assume any
liability in connection with its use.

NOTICE:
Trane has always recommended installing Trane approved
matched indoor and outdoor systems.

The benefits of installing approved matched systems are
maximum efficiency, optimum performance and best overall
system reliability.

Check for transportation damage after unit is uncrated. Report
promptly, to the carrier, any damage found to the unit.

To determine the electrical power requirements of the unit,
refer to the nameplate of the unit. The electrical power avail-
able must agree with that listed on the nameplate.

B. LOCATION AND PREPARATION

OF THE UNIT

1. When removing unit from the pallet, notice the tabs on the

basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2 (see page 2).

2. The unit should be set on a level support pad at least as

large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin “Trane APB2001-02”.

3. The support pad must NOT be in direct contact with any

structure. Unit must be positioned a minimum of 12" from
any wall or surrounding shrubbery to insure adequate
airflow. Clearance must be provided in front of control box
(access panels) & any other side requiring service access to
meet National Electrical Code. Also, the unit location must
be far enough away from any structure to prevent excess
roof run-off water from pouring directly on the unit. Do not
locate unit(s) close to bedroom(s).

Condensing Units

2TTZ9C with ComfortLink

     

II and Charge Assist

18-AC53D1-5

4. The top discharge area must be unrestricted for at least

five (5) feet above the unit.

5. When the outdoor unit is mounted on a roof, be sure the

roof will support the unit’s weight. Properly selected
isolation is recommended to prevent sound or vibration
transmission to the building structure.

6. The maximum length of refrigerant lines from outdoor to

indoor unit should NOT exceed sixty (60) feet.

7. If outdoor unit is mounted above the air handler, maxi-

mum lift should not exceed twenty-five (25) feet (suction
line). If air handler is mounted above condensing unit,
maximum lift should not exceed twenty-five (25) feet
(liquid line).

NOTE:
Refer to “Refrigerant Piping Software” Pub. No. 32-3312-0*
(the position of the * denotes the latest revision number).

8. Locate and install indoor coil or air handler in accordance

with instruction included with that unit.

C. INSTALLING REFRIGERANT LINES

CAUTION

!

If using existing refrigerant lines make certain that all joints
are brazed, not soldered.

Condensing units have provisions for braze connections.

Pressure taps are provided on the service valves of outdoor unit
for compressor suction and liquid pressures.

The indoor end of the recommended refrigerant line sets may
be straight or with a 90 degree bend, depending upon situation
requirements. This should be thoroughly checked out before
ordering refrigerant line sets.

1

5 FT. ABOVE UNIT — UNRESTRICTED

Summary of Contents for 2TTZ9C

Page 1: ...base pan such as a concrete slab If this is not the application used please refer to application bulletin Trane APB2001 02 3 The support pad must NOT be in direct contact with any structure Unit must...

Page 2: ...ine Service Valve Turn valve stem counterclockwise only until the stem contacts the rolled edge See Figures 3 and 5 No torque is required Failure to follow this warning will result in abrupt release o...

Page 3: ...valve cap and turning the valve stem 1 4 turn counterclockwise using 1 4 Open End or Adjust able wrench See Figure 4 12 The gas valve is now open for refrigerant flow Replace valve stem cap to prevent...

Page 4: ...T C O M P R E S S O R R E F R IG E R A N T U N D E R C H A R G E R E F R IG E R A N T O V E R C H A R G E E X C E S S IV E E V A P L O A D N O N C O N D E N S A B L E S R E S T R IC T E D O D A IR F L...

Page 5: ...Assist Once the system is stabilized watch to see which LED turns on next If the system charge is correct the CHARGED LED will turn on and remain on for one 1 CHARGE ASSIST CHARGE ASSIST PORT DIRECTI...

Page 6: ...46 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 933 36 3 4 2TTZ9036C 4 1 1267 49 7 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 933 36 3 4 2TTZ9048C 4 1 1267 49 7 8...

Page 7: ...ify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain pan 8 Supply registers an...

Page 8: ...ne A business of American Standard Companies www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without n...

Reviews: