background image

The Trane Company
3600 Pammel Creek Road
La Crosse, WI 54601-7589
© 2002 American Standard Inc.

3270 3361 Rev 1

®

CO

2

 Demand-Controlled Ventilation Wall-Sensor

Ordering number: 4190 4100

The carbon-dioxide (CO

2

) sensor, shown in Figure 1, 

is designed especially for demand-controlled 
ventilation zone applications. The exceptional 
stability and reliable performance come from 
advanced silicon based Non-Dispersive InfraRed 
(NDIR) technology.

Figure 1: 

CO2 demand-controlled ventilation sensor

Specifications

Table 1 shows the specifications of the CO

2

 sensor. 

Power supply requirements

CAUTION

AVOID EQUIPMENT DAMAGE!

Make sure that you connect the power wire only to 
the 24V terminal. Connecting the power wire to the 
output terminal may result in equipment damage.

The CO2 sensor is designed to operate with a 
nominal 24 Vac supply. The power supply should 
maintain the voltage between 20 to 26 Vac. 

Use a 24 Vac power supply according to the following 
guidelines. If more than one sensor is connected to 
one 24 Vac transformer, a common loop is formed 
and the risk of a short-circuit increases. To avoid 
this, use a separate floating supply for each sensor, 
as shown in Figure 2.

Figure 2: 

Separate ac power supplies

Table 1: 

Sensor specifications

Measuring range

0–2000 parts per million (ppm) 
CO

2

Accuracy at 25°C

< ± [40 ppm CO

2

 + 3% of 

reading] (includes repeatability 
and calibration uncertainty)

Non-linearity

< 1.0% full scale (FS)

Temperature 
dependence of output

0.3% FS/°C

Long-term stability

< 5.0% FS/5-years

Recommended 
calibration interval

5 years

Response time

1 minute (0–63%)

Operating temperature 

From 59 to 95°F (15 to 35°C)

Storage temperature

From –4 to 158°F (–20 to 70°C)

Humidity range

0–85% relative humidity (RH)

Thinner section for 
cut-out

Output signals 
(jumper selectable)

4–20 mA, 0–20 mA, 0–10 Vdc

Resolution of analog 
outputs

10 ppm CO

2

Recommended external 
load

Current output: max. 500 

Voltage output: min. 1000 

Power supply

Nominal 24 Vac

Power consumption

< 5 VA

Warm-up time

< 15 minutes

Housing material

ABS plastic

Mounting holes

For standard Asian, European, 
and North American junction 
boxes

Dimensions

4

1

/

4

 in. × 3

1

/

8

 in. × 1

7

/

16

 in. 

(108 mm × 80 mm × 36 mm)

Table 1: 

Sensor specifications (Continued)

Reviews: