Installer’s Guide

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — 

This Document is 

customer property

 and is to remain with this unit.  Please return to service information pack 

upon completion of work.

WARNING

!

WARNING (Medium/high pressure) 

Contains Refrigerant!
System contains oil and refrigerant under high pressure.  

Recover refrigerant to relieve  pressure before opening 

the system. See unit nameplate for refrigerant type. Do not 

use non-approved refrigerants, refrigerant substitutes, or 

refrigerant additives.
Failure to follow proper procedures or the use of non-

approved refrigerants, substitutes, or refrigerant additives 
could result in death, serious injury, or equipment damage.

2.  INDOOR UNIT AIRFLOW 

Indoor unit must provide the required airflow for the heat 
pump or cooling combinations approved for these coils.

IMPORTANT: Review your installation requirements.  Check 

the table on the outline drawings and note all dimensions 

for your coil before beginning the installation.

Table of Contents

General .................................................................................1

Application Information ......................................................1

Recommendation ................................................................2

Furnace in Upflow Position

 ................................................2

Furnace in Downflow Position

 ...........................................2

Maximum Airflow Setting, CFM

 ..........................................3

Installing / Brazing Refrigerant Lines ................................3

Leak Check...........................................................................4

Condensate Drain Piping ....................................................4

Cleaning the Coil .................................................................4

Outline Drawings .................................................................5

Troubleshooting Indoor TXV / Cooling Mode ...................7

Figure 1

18-AD41D1-1B-EN

Cased Aluminum Coils

"Dedicated Upflow / Downflow"  

Convertible to horizontal with separately purchased kit

Upflow models:

4PXCAU24BS3HAB

4PXCAU32BS3HAB

4PXCBU24BS3HAB

4PXCBU30BS3HAB

4PXCCU30BS3HAB

4PXCBU36BS3HAB

4PXCCU36BS3HAB

4PXCBU42BS3HAB

4PXCCU42BS3HAB

4PXCBU48BS3HAB

4PXCCU48BS3HAB

4PXCDU48BS3HAB

4PXCCU60BS3HAB

4PXCDU60BS3HAB

Downflow models:

4PXCBD30BS3HDB

4PXCBD36BS3HDB

4PXCCD36BS3HDB

4PXCBD42BS3HDB

4PXCCD42BS3HDB

4PXCCD60BS3HDB

4PXCDD60BS3HDB

NOTE: 

OPTIONAL DOWNFLOW GASKET INSTALLATION: For 

unusually humid applications that expect prolonged 

operation above 70% RH, it is recommended to use the 

BAYGSKT001A0 gasket kit to prevent water from forming 

on the bottom of the drain pan and dripping into the 

supply ductwork.

NOTE: 4PXC upflow coils may be installed in Upflow, Down

-

flow, Horizontal Right with kit, and Horizontal Left with kit.

 

4PXC downflow coils may be installed in Downflow and 

Horizontal Right with kit.

1.  FURNACE AND COIL 

The coil MUST BE installed downstream (in the outlet air) 
of the furnace.  

WARNING

!

This product can expose you to chemicals including 

lead, which are known to the State of California to case 

cancer and birth defects or other reproductive harm. 

For more information go to www. P65Warnings.ca.gov

A.  GENERAL

These coils are designed for use in combination with a heat pump 
or cooling outdoor section using 

R-410A REFRIGERANT

The 4PXC equipment has been evaluated in accordance with 
the Code of Federal Regulations, Chapter XX, Part 3280 or the 
equivalent. “Suitable for Mobile Home use” The height of the 
Furnace, Coil and discharge duct work must be 7 ft. or less.

Inspect the coil for shipping damage. Notify the transportation 
company immediately if the coil is damaged.

B.  APPLICATION INFORMATION

Summary of Contents for 4PXCAU24BS3HAB

Page 1: ... separately purchased kit Upflow models 4PXCAU24BS3HAB 4PXCAU32BS3HAB 4PXCBU24BS3HAB 4PXCBU30BS3HAB 4PXCCU30BS3HAB 4PXCBU36BS3HAB 4PXCCU36BS3HAB 4PXCBU42BS3HAB 4PXCCU42BS3HAB 4PXCBU48BS3HAB 4PXCCU48BS3HAB 4PXCDU48BS3HAB 4PXCCU60BS3HAB 4PXCDU60BS3HAB Downflow models 4PXCBD30BS3HDB 4PXCBD36BS3HDB 4PXCCD36BS3HDB 4PXCBD42BS3HDB 4PXCCD42BS3HDB 4PXCCD60BS3HDB 4PXCDD60BS3HDB NOTE OPTIONAL DOWNFLOW GASKET...

Page 2: ... coil is pressurized with 8 12 psig of dry air Do not stand directly in front of the coil connections when removing sealing plugs If no pressure is released check for leaks D FURNACE IN UPFLOW POSITION APPLICATION USES UPFLOW COIL MODELS ONLY IMPORTANT If installing the coil in the horizontal position you MUST use the horizontal kit listed below for this coil model num ber and follow the instructi...

Page 3: ...dischargeofrefrigeranttotheatmosphere 1 The following steps are to be considered when installing the refrigerant lines a Determine the most practical way to run the lines b Consider types of bends to be made and space limitations c Route the tubing making all required bends and properly secure the tubing before making final connections NOTE Refrigerant lines must be isolated from the structure and...

Page 4: ...g a strong water stream such as from a garden hose being careful to prevent fin damage Use chemical cleaners only when necessary Figure 6 Capillary tubes will come out the top of bulb when positioned correctly I CONDENSATE DRAIN PIPING Condensate drain connections are located in the drain pan at the bottom of the coil enclosure assembly The female threaded fitting protrudes outside of the enclosur...

Page 5: ...H C IN 13 5 8 13 5 8 16 5 8 16 5 8 20 1 8 16 5 8 20 1 8 23 5 8 20 1 8 23 5 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 15 3 4 19 1 4 15 3 4 19 1 4 22 3 4 19 1 4 22 3 4 GAS CONNECTION 3 4 7 8 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO ADAPTER RQUIRED 14 1 2 14 1 2 17 1 2 17 1 2 21 17 1 2 21 24 1 2 21 24 1 2 DRAIN PAN PLASTIC 4PXCCD36BS3 FIGURE A 42 17 5 8 17 1 2 16 5 8 15 3 4 3 4 17 1 2 4PXCCU30BS3 FI...

Page 6: ...6 18 AD41D1 1B EN Installer s Guide From Dwg D346711 RevB ...

Page 7: ... NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is correct NO Before starting insure the blower wheel indoor and outdoor coils are clean Is the liquid line temperature at indoor coil within 8F of outdoor liquid line temperature YES Verify line set is s...

Page 8: ...lications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2021 18 AD41D1 1B EN 27 Apr 2021 Supersedes 18 AD41D1 1A EN February 2021 ...

Reviews: