background image

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service 

information pack upon completion of work.

Installer’s Guide

These instructions do not cover all variations in 

systems nor provide for every possible contingency 

to be met in connection with installation.  All phases 

of this installation must comply with NATIONAL, 

STATE AND LOCAL CODES.  Should further information 

be desired or should particular problems arise which are 

not covered sufficiently for the purchaser’s purposes, the 

matter should be referred to your installing dealer or local 

 distributor.

 A.  GenerAl

WArnInG

!

This information is intended for use by individuals pos ses­
s ing adequate backgrounds of electrical and mechanical 
 experience. Any attempt to repair a central air condition ing 
product may result in personal injury and or  property damage. 
The manufacturer or seller cannot be respon sible for the 
interpretation of this information, nor can it  assume any liability 
in connection with its use.

NOTICE: 

Trane has always recommended installing Trane 

approved matched indoor and outdoor systems.
The benefits of installing approved matched systems 

are maximum efficiency, optimum performance and 

best overall system reliability. 

WArnInG

!

These units use r­410A refrigerant which operates at 50 to 70% 
higher pressures than r­22. Use only r­410A approved service 
equipment. refrigerant cylinders are painted a “rose” color to 
indicate the type of refrigerant and may contain a “dip” tube to 
allow for charging of liquid refrigerant into the system. All r­410A 
systems use a POe oil that readily absorbs moisture from the 
atmosphere. To limit this “hygroscopic” action, the system should 
remain sealed whenever possible. If a system has been open to 
the atmosphere for more than 4 hours, the compressor oil must 
be replaced. never break a vacuum with air and always change 
the driers when opening the system for component replacement.  
For specific handling concerns with r­410A and POe oil, 
reference retrofit Bulletin  
SSC­APG011­en.

Check for transportation damage after unit is uncrated.  

Report promptly, to the carrier, any damage found to the 

unit.
To determine the electrical power requirements of the unit, 

refer to the nameplate of the unit.  The electrical power 

available must agree with that listed on the nameplate.

Condensing Units

4TTB3­D

18­AC80D1­2

 B.  lOCATIOn AnD PrePArATIOn  

OF The UnIT

  1.  When removing unit from the pallet, notice the tabs on 

the basepan. Remove tabs by cutting with a sharp tool 

as shown in Figure 2 (see page 2).

  2. The unit should be set on a level support pad at least 

as large as the unit base pan, such as a concrete 

slab. If this is not the application used please refer to 

application bulletin SSC-APG002-EN.

  3.  The support pad must NOT be in direct contact with 

any structure.  Unit must be positioned a minimum 

of 12" from any wall or surrounding shrubbery to 

insure adequate airflow.  Clearance must be provided 

1

5 FT. ABOVe UnIT — UnreSTrICTeD

CAUTIOn

!

UnIT COnTAInS r­410A reFrIGerAnT!

R-410A OPERATING PRESSURE EXCEEDS THE 
LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS 
REQUIRED. FAILURE TO USE PROPER SERVICE 
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR 
PERSONAL INJURY.

SerVICe

USE ONLY R-410A REFRIGERANT AND

APPROVED POE COMPRESSOR OIL.

Summary of Contents for 4TTB3-D

Page 1: ...dip tube to allow for charging of liquid refrigerant into the system All R 410A systems use a POE oil that readily absorbs moisture from the atmosphere To limit this hygroscopic action the system should remain sealed whenever possible If a system has been open to the atmosphere for more than 4 hours the compressor oil must be replaced Never break a vacuum with air and always change the driers when...

Page 2: ... most practical way to run the lines 2 Consider types of bends to be made and space limitations NOTE Large diameter tubing will be very difficult to rebend once it has been shaped 3 Determine the best starting point for routing the refrigerant tubing INSIDE OR OUTSIDE THE STRUCTURE 4 Provide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficien...

Page 3: ...e to vacuum pump and observe the micron gauge If gauge pressure rises above 500 microns in one 1 minute then evacuation is incomplete or system has a leak 6 If vacuum gauge does not rise above 500 microns in one 1 minute the evacuation should be complete 7 Blank off vacuum pump and micron gauge close valves on manifold gauge set NOTE DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE NOTE A 3 16 Allen wr...

Page 4: ...orm a final unit inspection to be sure that factory tubing has not shifted during shipment Adjust tubing if necessary so tubes do not rub against each other when the unit runs Also be sure that wiring connections are tight and wire routing is secure H Seacoast Shield If installed within one mile of salt water including seacoasts and inland waterways models without factory supplied Seacoast Salt Sh...

Page 5: ...ounding of equipment must comply with local codes 3 Low voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to W2 and W3 leGenD FACTORY WIRING FIELD WIRING PRINTED FROM B152901 P02 PRINTED FROM B152903 P02 NOTE W2 present only on 2 stage thermostat and furnace ...

Page 6: ...15 435 441 446 452 458 464 470 120 464 470 476 482 488 495 501 125 495 501 507 514 520 527 533 r 410A reFrIGerAnT ChArGInG ChArT Refer to Service Facts or Installer s Guide for charging method LIQUID TEMP F DESIGN SUBCOOLING F LIQUID GAGE PRESSURE PSI From Dwg D154557P01 Rev 2 subcool value column Add refrigerant to raise the pressure to match the table or remove refrigerant to lower the pressure ...

Page 7: ...5 8 210 8 1 4 79 3 1 8 508 20 4TTB3030D 3 1 730 28 3 4 829 32 5 8 756 29 3 4 3 4 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 4TTB3036D 3 1 832 32 3 4 829 32 5 8 756 29 3 4 3 4 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 4TTB3042D 4 1 741 29 1 8 946 37 1 4 870 34 1 4 3 4 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TTB3048D 4 1 741 29 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 ...

Page 8: ...efrigerant Lines been secured and isolated properly 4 Have passages through masonry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain pan 8 Supply registers and return grille...

Reviews: