background image

Steam Humidifier

EHUMD800ASM00BA / EHUMD800BSMLCBA

TABLE OF CONTENTS

Safety Cautions

 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2

Materials List

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3

Principles & Sequence of Operation

 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3

Specifications & Dimensions

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4

Installation Instructions

 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7

 

Choosing a Location   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7

    - Dispersion Tube Location   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7
  - 

Elevation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8

    - Distance from Humidifier to Dispersion Tube  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9
    - Humidifier Location .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10
  Prepare Humidifier for Mounting   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
  Install Steam Dispersion Tube   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11

  Mount Humidifier   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
  Install Steam Hose   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
  Supply Water .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11
  Drain Line .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 12
  Electrical Power Wiring & Shut-off Switch   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 12
  Control Wiring  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 17

Start-up Procedure

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

Operating Modes

  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 19

Shut Down Procedure

 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 20

Display Panel

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 20

Maintenance

 .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 21

Troubleshooting Guide

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 23

Steam Humidifier

Installation & Maintenance Instructions

Trane  

6200 Troup Highway • Tyler, TX 75711-9010

READ AND SAVE THESE INSTRUCTIONS

18-CH87D1-1D  

10016618 B2210106A 10 .22

Summary of Contents for EHUMD800ASM00BA

Page 1: ...ier Location 10 Prepare Humidifier for Mounting 11 Install Steam Dispersion Tube 11 Mount Humidifier 11 Install Steam Hose 11 Supply Water 11 Drain Line 12 Electrical Power Wiring Shut off Switch 12 Control Wiring 17 Start up Procedure 19 Operating Modes 19 Shut Down Procedure 20 Display Panel 20 Maintenance 21 Troubleshooting Guide 23 Steam Humidifier Installation Maintenance Instructions Trane 6...

Page 2: ...ce procedures on any part of the system DISCONNECT ELECTRICAL POWER Disconnect electrical power before installing supply wiring or performing service or maintenance procedures on any part of the humidification system Failure to disconnect electrical power could result in fire electrical shock and other hazardous conditions These hazardous conditions could cause property damage personal injury or d...

Page 3: ...and canister To control the Steam Humidifier as part of the HVAC system a Connected Thermostat Control with an integral humidistat is installed to detect the RH level in the duct When the humidistat detects RH below the set point and the humidifier and HVAC system blower are operating the humidifier energizes the electrodes to provide steam Steam is delivered into the duct work via the steam hose ...

Page 4: ...E 1 Humidifier Capacities and Recommended Home Sizes Amperage Voltage Maximum steam capacity gal day Maximum recommended home size in ft2 Tight Average Loose 11 5 120V 11 5 2 500 sq ft 1 500 sq ft 1 000 sq ft 208V 20 5 4 500 sq ft 2 500 sq ft 1 500 sq ft 240V 23 3 16 0 120V 16 0 3 500 sq ft 2 000 sq ft 1 500 sq ft 208V 30 0 6 000 sq ft 4 000 sq ft 2 500 sq ft 240V 34 6 Assumes 8 ft ceiling height ...

Page 5: ... 1 3 4 8 1 4 1 dia 10 1 8 20 7 8 FRONT VIEW FIGURE 2 Humidifier Dimensions inches 90 1518 SPECIFICATIONS DIMENSIONS CONTINUED 3 3 8 7 7 8 8 7 8 3 3 8 1 5 8 4 1 4 5 3 4 Dispersion Outlet Electrical Knockouts Fill Cup TOP VIEW 7 1 8 SIDE VIEW 1 4 4 12 BACK VIEW Mounting Holes 3 3 8 3 3 8 7 7 8 2 6 5 8 9 1 8 1 7 8 Water Fill Line Connection Drain BOTTOM VIEW Electrical Knockouts 3 sq 2 sq 1 3 4 8 1 4...

Page 6: ...e the drain frequency As water in the canister boils and turns into steam minerals are left behind Minerals remaining in solution increase the conductivity of the water Minerals also deposit onto the submerged portions of the electrodes rendering those areas ineffective As this occurs the level of water in the canister rises to expose uncoated electrode surface There are benefits and trade offs to...

Page 7: ...e controls to lock out the humidifier during AC calls and use the blower activation feature to allow the humidifier to run with the blower only The dispersion tube must be mounted with the plate on a vertical surface with the tube angled up as shown in Figure 3 The steam tubelets must face up regardless of the airflow direction in the duct The plate is labeled UP to indicate proper orientation On ...

Page 8: ...9 1800 fpm 3 4 5 16 25 0 35 0 300 fpm 24 31 36 60 600 fpm 17 22 26 48 1200 fpm 12 15 18 25 1800 fpm 10 13 15 20 Velocity in feet per minute Duct airflow volume in cubic feet per minute duct area in square feet Example 1 200 cfm through 16 x 12 duct 1 200 12 x 16 144 sq in sq ft 1 200 1 333 900 fpm INSTALLATION INSTRUCTIONS CONTINUED ELEVATION The preferred location for the dispersion tube is highe...

Page 9: ... Hose 1 I D Steam Hose 1 I D Downward Slope to Tee Drain Hose 7 8 I D Steam Humidifier FIGURE 6 90 1844 If the dispersion tube must be mounted below the humidifier or if the steam hose needs to run up and over an obstruction a drip tee with drain trap Part 5628RP must be installed as shown in Figure 4 NOTICE CONTROL CONDENSATE FLOW AND COLLECTION Failure to follow steam hose recommendations in thi...

Page 10: ...lows access for servicing and clearance to remove front panel for replacing the canister and side panel for access to the electrical components during installation See Figure 7 for minimum clearances around humidifier The humidifier should be mounted as close to the dispersion tube as possible Table 4 shows how capacity is reduced as the distance between the humidifier and dispersion tube increase...

Page 11: ... humidifier is mounted plumb INSTALL STEAM DISPERSION TUBE Make sure steam dispersion tube is mounted higher than the humidifier so that condensation that forms in the steam hose runs back into the canister If the dispersion tube cannot be mounted higher than the humidifier or if the steam hose must extend up from the humidifier then down to the dispersion tube due to an obstruction a drip tee and...

Page 12: ...ze as the power wiring With factory settings the Steam Humidifier draws 11 5 amps 10 Use a minimum 20 amp dedicated circuit when installing to operate at 11 5 amps The Steam Humidifier can be set to draw 16 0 amps 10 by repositioning dip switch 1 on the control circuit board see Figure 8 When set to 16 amps use a minimum 25 amp dedicated circuit For both applications size wire according to local c...

Page 13: ...LATION INSTRUCTIONS CONTINUED Factory setting for 11 5 AMP nominal operation Slide Dip Switch 1 to ON position for 16 0 AMP nominal operation LED D8 90 1959 FIGURE 8 Control Circuit Board with Dip Switches 13 ...

Page 14: ...G YEL BLUE MAIN POWER BREAKER NOT PROVIDED TRANSFORMER J11 120 VAC J13 208 VAC J14 240 VAC LOW VOLTAGE FIELD WIRING SLOW BLOW FUSE 5X20mm 5A ELECTRODE WATER LEVEL PROBE ELECTRODE STEAM CANISTER P7 HUMIDISTAT 1 2 FAN PACK CON1 RESIDENTIAL STEAM HUMIDIFIER IS SHIPPED FROM THE FACTORY WIRED FOR 240 VOLTS HUMIDITY CONTROL PROVIDED FAN PACK OPTIONAL DOOR SWITCH ORANGE DRY CONTACT POWER TERMINAL BLOCK F...

Page 15: ... VAC J14 240 VAC ELECTRODE WATER LEVEL PROBE ELECTRODE STEAM CANISTER LOW VOLTAGE FIELD WIRING P7 P3 WHT RED BLK ORG FAN PACK HUMIDISTAT 1 2 RESIDENTIAL STEAM HUMIDIFIER IS SHIPPED FROM THE FACTORY WIRED FOR 240 VOLTS MOVE THE JUMPER WIRE TO TERMINAL J13 TO OPERATE AT 208VAC MAIN POWER BREAKER NOT PROVIDED L2 N L1 GND DRAIN VALVE FILL VALVE DISPLAY PANEL RIBBON CABLE BLK YEL SLOW BLOW FUSE 5X20mm ...

Page 16: ...HT YEL BLUE TRANSFORMER LOW VOLTAGE FIELD WIRING DRY CONTACT P7 P3 WHT RED BLK ORG FAN PACK HUMIDISTAT 1 2 RESIDENTIAL STEAM HUMIDIFIER IS SHIPPED FROM THE FACTORY WIRED FOR 240 VOLTS MOVE THE JUMPER WIRE TO TERMINAL J11 TO OPERATE AT 120VAC MAIN POWER BREAKER NOT PROVIDED L2 N L1 GND DRAIN VALVE FILL VALVE DISPLAY PANEL RIBBON CABLE BLK YEL SLOW BLOW FUSE 5X20mm 5A CON1 ELECTRODE WATER LEVEL PROB...

Page 17: ... 12 If protection from over humidification is desired install optional high humidity limit switch at least 4 feet downstream of the dispersion tube MANUAL HUMIDIFIER CONTROL TYPICAL 24 VAC TERMINAL STRIP IN FURNACE THERMOSTAT BLOWER ACTIVATION RELAY REMOVE WIRE G TO G HIGH HUMIDITY LIMIT SWITCH STEAM HUMIDIFIER OPTIONAL NOTES 1 18AWG WIRE IS ACCEPTABLE FOR 24V INSTALLATIONS 2 FAN PACK TERMINALS PR...

Page 18: ...y per local codes 110V ISOLATION RELAY P N RLY00636 AUX 2 AUX 1 AUX 2 AUX 1 G 1 2 1 1 W2 Bk W3 W1 RS1 ODT RS1 ODT B C RH RC O HUMIDISTAT STEAM HUMIDIFIER 824 624 CONTROL CIRCUIT BOARD FIGURE 13 Steam Humidifier using 850 or 950 Control Wired to 24 Volt Relay Panel BAY24VRPAC52D FIGURE 15 Steam Humidifier Wiring for Communicating Furnaces using 110 Volt HUM Output from Furnace FIGURE 14 Steam Humid...

Page 19: ...range that allows the humidifier to generate steam at the rated capacity If the conductivity of the water is low it may take a week or more for the humidifier to generate steam at the rated capacity The rated capacity is achieved when the humidifier is detecting a nominal current of either 11 5 or 16 0 amps between the electrodes If the humidifier has not reached capacity after 168 hours of operat...

Page 20: ...r stops operating Occurs after fill valve has been energized for 40 minutes and high water probe does not detect water Off Humidifier is not producing steam Solid Green Humidifier is turned on and receiving a call for humidity from the control Solid Yellow Humidifier is producing steam but at less than the rated capacity Occurs if humidifier has operated for 168 hours and has not reached nominal c...

Page 21: ... at the circuit breaker 4 Allow the unit to cool 5 Shut off water supply to unit CANISTER REPLACEMENT AND DRAIN VALVE SERVICE 1 Remove front panel see FIGURE 16 2 Pull three wires off posts on top of canister two electrode wires and one water level probe wire shown in FIGURE 17A and FIGURE 17B 3 Inspect the two electrode wires see ELECTRODE WIRE REPLACEMENT section for detailed instructions Replac...

Page 22: ...ctrode wires Part 5614RP have O shape connectors see FIGURE 18B Do not use replacement wires with D shape connectors see FIGURE 18A 5 Attach the new electrode wires see FIGURE 17A and FIGURE 17B a For units with one circuit board Use a pair of needle nose pliers to attach the spade connectors to the spade terminals J8 and J10 on the circuit board Electrode wires are interchangeable and can be plac...

Page 23: ...ace with 5 amp slow burn fuse if necessary With humidifier energized check that LED light D8 is energized on the circuit board If the LED is lit replace the membrane switch if not replace the circuit board Steam light does not turn on Call for humidity not being received Check humidistat wiring and setting Do not leave ADHC in TEST mode Check wiring and settings of high RH limit switch and airflow...

Page 24: ...d to low conductivity water and systems that operate for short cycles Plumb humidifier to softened water Use blower activation feature on ADHC or run constant HVAC fan Operate humidifier on 208 240 volts To determine operating current attach clamp on ammeter to one of the electrode wires on top of canister Unless the unit is operating on softened water switch to the Model 8043LCRP canister if curr...

Page 25: ...on 7 Choisir un emplacement 7 Emplacement du tube de dispersion 7 Élévation 8 Distance de l humidificateur au tube de dispersion 9 Emplacement de l humidificateur 10 Préparation de l humidificateur pour le montage 11 Installation du tube de dispersion de vapeur 11 Montage de l humidificateur 11 Installation du boyau à vapeur 11 Eau d alimentation 11 Conduite d évacuation 12 Câblage de l alimentati...

Page 26: ...CTRIQUE Débranchez l alimentation électrique avant d installer le câblage d alimentation ou d effectuer toute procédure de service ou d entretien sur toute pièce du système d humidification Le non respect de cette directive peut causer un incendie un choc électrique et d autres situations dangereuses Ces situations dangereuses pourraient causer des dommages matériels des blessures ou la mort Tout ...

Page 27: ...u d évacuation Reportez vous à la Figure 1 pour une représentation du système de remplissage et d évacuation et de la cartouche Pour contrôler l humidificateur à vapeur au sein du système de CVC une commande de thermostat reliée avec un humidostat intégré est installée pour déceler le niveau d HR dans le conduit Lorsque l humidostat détecte une HR inférieure au point de réglage et que l humidifica...

Page 28: ...AU 1 Capacités de l humidificateur et tailles de résidence recommandées Intensité Tension Capacité maximale de vapeur litres jour Taille de résidence maximale recommandée en m2 Élevée Moyenne Faible 11 5 120 volts 43 5 230 m 138 m 92 m 208 volts 77 6 414 m 230 m 138 m 240 volts 88 2 16 0 120 volts 60 6 322 m 184 m 138 m 208 volts 113 6 552 m 368 m 230 m 240 volts 131 0 Assume des plafonds de 2 4 m...

Page 29: ...éfonçables électriques 7 6 cm 5 1 cm 4 4 21 0 2 5 dia 25 7 53 0 VUE AVANT FIGURE 2 Dimensions de l humidificateur cm 90 1518 8 6 20 0 22 5 8 6 4 1 10 8 14 6 Sortie de dispersion Alvéoles défonçables électriques Godet de remplissage VUE DE DESSUS 18 1 VUE LATÉRALE 2 5 10 2 10 2 30 5 VUE ARRIÈRE Trous de montage 8 6 8 6 20 0 5 1 16 8 23 2 4 8 Connexion de la conduite de remplissage d eau Drain VUE D...

Page 30: ...fréquence des évacuations Tandis que l eau dans la cartouche bout et se transforme en vapeur les minéraux sont laissés derrière Les minéraux qui restent dans la solution augmentent la conductivité de l eau Les minéraux se déposent aussi sur les parties submergées des électrodes ce qui rend ces zones inefficaces Dans ce cas le niveau d eau dans la cartouche augmente pour exposer la surface non enro...

Page 31: ...els de climatisation et utilisez la fonction d activation du ventilateur pour permettre à l humidificateur de fonctionner avec le ventilateur seulement Le tube de dispersion doit être monté avec la plaque sur une surface verticale avec le tube incliné vers le haut comme dans la Figure 3 Les petits tubes de vapeur doivent être orientés vers le haut quelle que soit la direction du débit d air dans l...

Page 32: ... 546 m min 7 6 cm 10 2 cm 12 7 cm 40 6 cm 94 6 132 5 91 m min 61 0 cm 78 7 cm 91 4 cm 152 4 cm 182 m min 43 2 cm 55 9 cm 66 0 cm 121 9 cm 364 m min 30 5 cm 38 1 cm 45 7 cm 63 5 cm 546 m min 25 4 cm 33 0 cm 38 1 cm 50 8 cm Vélocité en mètres par minute volume du débit d air dans le conduit en centimètres cubes par minute zone de conduit en mètres carrés Exemple 34 m dans un conduit de 40 6 x 30 5 c...

Page 33: ...ers le bas jusqu au T Boyau d évacuation diamètre intérieur de 2 2 cm Boyau à vapeur diamètre intérieur de 2 5 cm pente vers le bas de l humidificateur jusqu au T Bride de serrage Humidificateur à vapeur FIGURE 6 DIRECTIVES D INSTALLATION SUITE Si le tube de dispersion doit être monté sous l humidificateur ou si le boyau à vapeur doit être acheminé vers le haut et par dessus une obstruction un té ...

Page 34: ...our le service et de l espace pour retirer le panneau avant pour remplacer la cartouche et le panneau latéral pour accéder aux composants électriques pendant l installation Reportez vous à la Figure 7 pour connaître les dégagements minimums requis autour de l humidificateur L humidificateur doit être monté aussi près du tube de dispersion que possible Le Tableau 4 indique la mesure dans laquelle l...

Page 35: ...iveau INSTALLATION DU TUBE DE DISPERSION DE VAPEUR Assurez vous que le tube de dispersion de vapeur est monté plus haut que l humidificateur afin que la condensation qui se forme dans le boyau à vapeur s écoule dans la cartouche Si le tube de dispersion ne peut pas être installé plus haut que l humidificateur ou si le boyau à vapeur doit se prolonger au dessus de l humidificateur puis vers le bas ...

Page 36: ...humidificateur à vapeur tire 11 5 ampères 10 Utilisez un circuit spécialisé d au moins 20 ampères lorsque vous effectuez une installation qui utilisera 11 5 ampères L humidificateur à vapeur peut être réglé pour tirer 16 0 ampères 10 en repositionnant le commutateur DIP n 1 sur la carte de circuits imprimés reportez vous à la Figure 8 Lorsqu il est réglé à 16 ampères utilisez un circuit spécialisé...

Page 37: ...de l usine pour le fonctionne ment nominal à 11 5 ampères Glissez le commu tateur DIP n 1 à la position ON pour le fonctionne ment nominal à 16 0 ampères DEL D8 90 1959 FIGURE 8 Carte de circuits imprimés de contrôle avec commutateurs DIP 13 ...

Page 38: ...IE BLOC VENTILATEUR EN OPTION INTERRUPTEUR DE PORTE CONTACT SEC JAU BLEU TRANSFORMATEUR J11 120 VCA J13 208 VCA J14 240 VCA ÉLECTRODE CAPTEUR DU NIVEAU D EAU ÉLECTRODE CARTOUCHE DE VAPEUR CÂBLAGE SUR LE TERRAIN À FAIBLE TENSION BLA ROU NOI ORG BLOC VENTILATEUR HUMIDOSTAT 1 2 DISJONCTEUR PRINCIPAL NON FOURNI TERRE ROBINET DE PURGE ROBINET DE REMPLISSAGE PANNEAU D AFFICHAGE CÂBLE RUBAN NOI JAU FUSIB...

Page 39: ...TEUR DU NIVEAU D EAU ÉLECTRODE CARTOUCHE DE VAPEUR CÂBLAGE SUR LE TERRAIN À FAIBLE TENSION P7 P3 BLA ROU NOI ORG BLOC VENTILATEUR HUMIDOSTAT 1 2 L HUMIDIFICATEUR À VAPEUR RÉSIDENTIEL EST EXPÉDIÉ DE L USINE CÂBLÉ POUR 240 VOLTS DÉPLACEZ LE FIL DE LIAISON À LA BORNE J13 POUR L UTILISER SUR 208 VOLTS CA DISJONCTEUR PRINCIPAL NON FOURNI L2 N L1 TERRE ROBINET DE PURGE ROBINET DE REMPLISSAGE PANNEAU D A...

Page 40: ...APEUR RÉSIDENTIEL EST EXPÉDIÉ DE L USINE CÂBLÉ POUR 240 VOLTS DÉPLACEZ LE FIL DE LIAISON À LA BORNE J11 POUR L UTILISER SUR 120 VOLTS CA DISJONCTEUR PRINCIPAL NON FOURNI L2 N L1 TERRE ROBINET DE PURGE ROBINET DE REMPLISSAGE PANNEAU D AFFICHAGE CÂBLE RUBAN NOI JAU FUSIBLE À FUSION LENTE 5X20mm 5A CON1 ÉLECTRODE CAPTEUR DU NIVEAU D EAU ÉLECTRODE CARTOUCHE DE VAPEUR CÂBLAGE DU CIRCUIT DE COMMANDE CÂB...

Page 41: ...fication installez un interrupteur de limite supérieure d humidité offert en option à une distance d au moins 1 2 mètre en amont du tube de dispersion REMARQUES 1 UN FIL DE CALIBRE 18 AWG EST ACCEPTABLE POUR LES INSTALLATIONS DE 24 VOLTS 2 LES BORNES DU BLOC VENTILATEUR FOURNISSENT 24 VOLTS CA SUR DEMANDE D HUMIDITÉ ET DEMEURENT SOUS TENSION PENDANT DEUX MINUTES UNE FOIS LA DEMANDE SATISFAITE COMM...

Page 42: ...ISOLATION 110 VOLTS N P RLY00636 AUX 2 AUX 1 AUX 2 AUX 1 G 1 2 1 1 W2 Bk W3 W1 RS1 ODT RS1 ODT B C RH RC O HUMIDOSTAT HUMIDIFICATEUR À VAPEUR COMMANDE 924 624 CARTE DE CIRCUITS IMPRIMÉS FIGURE 13 Humidificateur à vapeur utilisant les commandes 850 ou 950 reliées au panneau de relais de 24 volts BAY24VRPAC52D FIGURE 15 Câblage de l humidificateur à vapeur pour les appareils de chauffage de communic...

Page 43: ...e en marche initiale avec une nouvelle cartouche l humidificateur peut passer à travers une série de cycles de remplissage de purge jusqu à ce que la conductivité de l eau se trouve dans l étendue qui permet à l humidificateur de générer de la vapeur à la capacité nominale Si la conductivité de l eau est faible il pourra s écouler une semaine ou plus avant que l humidificateur ne génère de la vape...

Page 44: ...provisionnant la cartouche avec de l eau Pendant le cycle de purge lorsque le robinet de remplissage est ouvert laissant de l eau froide entrer dans la cartouche pour tempérer l eau d évacuation le voyant Fill remplissage ne s allume pas Vert clignotant Les robinets de remplissage et de purge vibrent pour déloger les dépôts de minéraux du drain Clignote 10 fois dans quatre secondes Se produit si l...

Page 45: ...n électrique principale de l humidifier au niveau du disjoncteur 4 Laissez l unité se refroidir 5 Coupez l alimentation en eau vers l unité REMPLACEMENT DE LA CARTOUCHE ET SERVICE DU ROBINET DE VIDANGE 1 Retirez le panneau avant reportez vous à la FIGURE 16 2 Tirez les trois fils hors des poteaux se trouvant sur le dessus de la cartouche deux fils d électrode et un fil de sonde du niveau d eau ill...

Page 46: ... forme de O reportez vous à la FIGURE 18B N utilisez pas des fils de rechange avec des cosses en forme de D reportez vous à la FIGURE 18A 5 Fixez les nouveaux fils d électrode reportez vous à la FIGURE 17A et la FIGURE 17B a Pour les unités avec une carte de circuits imprimés Utilisez des pinces à bec effilé pour fixer les cosses rectangulaires sur les bornes embrochables J8 et J10 sur la carte de...

Page 47: ...ne fois l humidificateur alimenté vérifiez que le voyant à DEL D8 est allumé sur la carte de circuits imprimés Si la DEL est allumée remplacez l interrupteur de membrane sinon remplacez la carte de circuits imprimés Le voyant Steam vapeur se s allume pas L appel d humidité n est pas reçu Vérifiez le câblage et le réglage de l humidostat Ne laissez pas le CANH en mode TEST Vérifiez le câblage et le...

Page 48: ...ionnent pendant des cycles courts Reliez l humidificateur à de l eau adoucie Utilisez la fonction d activation du ventilateur du CANH ou faites fonctionner le ventilateur CVC en continu Faites fonctionner l humidificateur sur 208 240 volts Pour déterminer le courant de fonctionnement reliez un ampèremètre à pince sur l un des fils d électrode sur la partie supérieure de la cartouche À moins que l ...

Reviews: