TREVENT EL-6-380L

TREVENT EL-9-380L
TREVENT EL-9-380

TREVENT EL-10,5-380

OPERATION

MANUAL

FOR ELECTRIC FAN HEATERS

TREVENT EL-12-380

TREVENT EL-22,5-380
TREVENT EL-30-380

TREVENT EL-36-380

SAFETY MEASURES
DESIGN AND DIMENSIONS

SERVICE

TECHNICAL PARAMETERS
FAN HEATER INSTALLATION

Summary of Contents for EL-10,5-380

Page 1: ...VENT EL 9 380 TREVENT EL 10 5 380 OPERATION MANUAL FOR ELECTRIC FAN HEATERS TREVENT EL 12 380 TREVENT EL 22 5 380 TREVENT EL 30 380 TREVENT EL 36 380 SAFETY MEASURES DESIGN AND DIMENSIONS SERVICE TECHNICAL PARAMETERS FAN HEATER INSTALLATION ...

Page 2: ...CTION OF FAN HEATERS MAIN DIMENSIONS TECHNICAL DETAILS AUTOMATICS POSSIBLE MOUNTING METHODS CONNECTION OF FAN HEATERS TREVENT EL L 6 9 KW ELECTRIC FAN HEATERS OPERATION MANUAL REFERENCE INFORMATION WIRES SECTION CALCULATION TABLE POTENTIAL PROBLEMS AND TROUBLESHOOTING METHODS PASSPORT WARRANTY TREVENT EL 9 12 KW TREVENT EL 22 5 36 KW ...

Page 3: ... are intended Any other use that is not in accordance with this manual may result in property damage personal injury or death Every effort should be made to avoid the possibility of improper use of the fan heater It is necessary to restrict access to the fan heater by unauthorized persons as well as to train the maintenance personnel The manufacturer is not liable for damage caused by the actions ...

Page 4: ... protected from the phase loss Install the fan heater on a solid base that can sustain the weight of the fan heater Check for grounding Do not use the fan heater without grounding as this may result in property damage personal injury or death It is not allowed to use the fan heater with fully closed blinds The electrical network that powers the fan heater and automatics must be short circuit proof...

Page 5: ...r with a rated thermal power of 9kW and line supply of 380V Fan heaters have three stages of heating and a control panel with a TREVENT 6 9 L digital thermostat After stopping the heating the fan continues to run for several minutes to cool the EHTs The control panel is powered by a fan heater and is protected against short circuits by the automatic circuit breaker in the heater body The fan heate...

Page 6: ...ries for the TREVENT EL fan heaters with the power of 9 12kW and the TREVENT EL fan heaters with the power of 22 5 36kW as well as EL series panels for the TREVENT EL fan heaters with the power of 22 5 30kW and the PROG series panels for the TREVENT EL fan heaters Fan heaters are protected from overheating by two self healing thermal fuses that temporarily turn off the EHTs when the body overheats...

Page 7: ... made of galvanized steel Temperature sensors for protection of EHTs from overheating are mounted in the upper and lower parts of groups of EHTs BODY consists of metal elements coated with highly resistant polymer paint galvanized fastening and structural elements FAN is located in a special diffuser in the rear part of the fan heater so that the air flow is evenly distributed over the entire surf...

Page 8: ...MAIN DIMENSIONS 07 MAIN DIMENSIONS TREVENT EL 6 380L EL 9 380L TREVENT EL 9 380 EL 10 5 380 EL 12 380 480 475 380 478 475 333 458 Ø 10 2 ports 100 Ø 11 ...

Page 9: ... BRACKET MOUNTING DISTANCE For ease and safety of installation the ring bolt must be screwed into the bracket of the fan heater and used for lifting and securing during installation Permissible load on the ring bolt according to GOST 4751 73 When lifting the fan heater do not deviate from the lifting plane by more than 45 ...

Page 10: ... ІІ ІІІ TECHNICAL DETAILS TREVENT EL Model range Power supply voltage Power line frequency Capacity at heating stages Rated air capacity Current Increase in air temperature at rated power Connection wires section Weight Main dimensions LxWxH V Hz kW m h А С mm kg mm EL 9 380 380 50 4 5 9 0 1600 3 13 5 18 5 2 5 19 EL 10 5 380 380 50 4 5 6 10 5 1600 3 16 20 5 4 0 19 І ІІ ІІІ EL 12 380 380 50 6 12 25...

Page 11: ...ENT EL 10 5 380 Model Р kW Т1 C 12 22 5 30 36 0 5 10 15 20 0 5 10 15 20 0 5 10 15 20 0 5 10 15 20 Т2 C 14 19 24 29 34 15 20 25 30 35 18 23 28 33 38 21 26 31 36 41 TREVENT EL 12 380 TREVENT EL 22 5 380 TREVENT EL 30 380 TREVENT EL 36 380 double overheating protection EHTs continue to be aired for some time after switching off two or three stages of heating capability of operation in the fan mode de...

Page 12: ...ble to set the required temperature and operating mode during working and non working hours according to the weekly schedule in the scheme of programmable thermostat during connection Control panel controls the operation of two groups of EHTs which allows to provide three stages of heating power Power supply 230V 50Hz Environmental parameters 5 25 C CONTROL PANEL WITH MECHANICAL THERMOSTAT FOR TRE...

Page 13: ...t temperature indoors It is possible to set the required temperature and operating mode during working and non working hours according to the weekly schedule in the scheme of programmable thermostat during connection Control panel controls the operation of two groups of EHTs which allows to provide three stages of heating power Power supply 230V 50Hz Environmental parameters 5 25 C ...

Page 14: ...ss than Mounting height Range of air stream from 0 25 m 2 5 5 m to 15 m For model with the power of 12kW Directional louvers are installed horizontally Recommended distances from the wall and placement of several fan heaters min 0 25m min 0 5m 2 5 5 m RECOMMENDED DISTANCE FROM WALLS AND CEILING LACEMENT OF SEVERAL DEVICES 5 m 15 m ...

Page 15: ...eam from 0 25 m 3 8 m to 25 m Directional louvers are installed horizontally Failure to observe the minimum distance of 0 25 m from the wall or ceiling will lead to improper operation of the fan heater which will reduce the service life of the fan heater min 0 25m min 0 5m 3 8 m RECOMMENDED DISTANCE FROM WALLS AND CEILING LACEMENT OF SEVERAL DEVICES 3 8 m 25 m ...

Page 16: ...CONNECTION OF FAN HEATERS 15 CONNECTION OF FAN HEATERS TREVENT EL 6 9 380L 1 EHTS OF FAN HEATER 2 CONTROL PANEL 3 FAN MOTOR 4 THERMOSTAT ...

Page 17: ...16 CONNECTION OF FAN HEATERS CONNECTION OF FAN HEATERS TREVENT EL L 9 12 KW 1 EHTS OF FAN HEATER 2 CONTROL PANEL 3 FAN MOTOR 4 THERMOSTAT ...

Page 18: ...CONNECTION OF FAN HEATERS 17 CONNECTION OF FAN HEATERS TREVENT EL L 22 5 36 KW 1 EHTS OF FAN HEATER 2 CONTROL PANEL 3 FAN MOTOR 4 THERMOSTAT ...

Page 19: ... 33 0 49 5 59 4 75 9 95 7 118 8 145 2 171 6 Current A Power kW Voltage 220V Voltage 380V Conductor material copper Section of power core mm Current A Power kW 2 5 4 6 10 16 25 35 50 70 95 120 20 28 36 50 60 85 100 135 165 200 230 4 4 6 1 7 9 11 0 13 2 18 7 22 0 29 7 36 3 44 0 50 6 19 23 30 39 55 70 85 110 140 170 200 11 6 15 1 19 8 25 7 36 3 46 2 56 1 72 6 92 4 112 2 132 0 Current A Power kW Volta...

Page 20: ...t in a heater went off Contact a specialized installation company No power is supplied to the control panel Contact a specialized installation company A foreign object fell into the fan blading The automatic circuit breaker built in the heater went off Restore the automatic circuit breaker and find out the cause of its activation During operation the fan heater makes unwanted sounds Conduct a visu...

Page 21: ...or low temperature and so on independent performed by the user or an unauthorized person repair change of equipment design connection of additional equipment that is not recommended by the manufacturer wrong mains voltage с pieces of equipment prone to wear including change in color of the body and materials Any changes to the provisions of the Warranty Terms traces of changes or attempts to chang...

Page 22: ... serial number Address and place of installation Purchase date Company that issues a complaint Company that installed the equipment Date and circumstances of defect detectio Date of issuing a complain Name and surname of contact person Telephone number email Defect description 21 WARRANTY ...

Page 23: ...TREVENT UKRAINE LLC Ukraine 79066 Lviv Hruntova 1 str tel 098 86 900 25 website Trevent ua email trevent ua gmail com ...