WARNING

2007-12 Prestige Control Appl. Supl.

This document is intended to be used by a factory trained and qualified heating
contractor or service technician only. Read all instructions within this document
and within the PRESTIGE Boiler Installation and Maintenance Manual, before pro-
ceeding.  It is recommended to follow the procedures in the steps given, skipping
or missing procedural steps could result in severe personal injury, death or sub-
stantial property damage.

prestige

Control Application

Supplement

Revised 1/7/2008

    

Summary of Contents for prestige

Page 1: ... Read all instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual before pro ceeding It is recommended to follow the procedures in the steps given skipping or missing procedural steps could result in severe personal injury death or sub stantial property damage prestige Control Application Supplement Revised 1 7 2008 ...

Page 2: ... of the MCBA 2 3 Revising Application Setting 3 Domestic Hot Water DHW Application Parameters General Guide 4 5 Domestic Hot Water Applications 6 12 Central Heating CH Application Parameters General Guide 13 14 Central Heating Applications 15 25 Parameter Worksheet and Recorded Settings 26 29 ...

Page 3: ... to the equipment but not related to personal injury hazards Indicates recommendations made by Triangle Tube for the installers which will help to ensure optimum operation and longevity of the equipment BEST PRACTICES NOTICE CAUTION WARNING DANGER DEFINITIONS IMPORTANT INFORMATION READ BEFORE PROCEEDING This document is intended to be used by a factory trained and qualified heating contractor or s...

Page 4: ...ing the MODE and press STEP button until STBY appears and hold both STEP and MODE buttons for 2 to 3 seconds The display should read CODE 3 Release the STEP and MODE buttons on the con trol panel 4 Press STEP once WARNING The display should read C_XX XX should be a random number from 00 to 99 5 Press the or button to change the display num ber C_XX to read C_05 Press and release the or to change t...

Page 5: ...rameter The sequence of parameters may be scrolled through as the display will roll over from parameter 42 to parameter 1 If sequential parameters are being revised and since the display will not show P_XX of the next sequen tial parameter it is recommend to press and hold the STEP button to scroll through the entire list of parameters before making any additional changes to avoid any potential co...

Page 6: ...r additional information 26 DHW differential setting for detection ON Setting is applied on storage tank with NTC sensor applications 02ºF 02ºF 54ºF See pages 7 and 8 for additional information 27 DHW differential setting for detection OFF Setting is applied on storage tank with NTC sensor applications 18ºF 16ºF 54ºF See pages 7 through 8 for additional information 29 The time period of blocking t...

Page 7: ...ge boiler WARNING Parameter Description Factory Setting Minimum Setting Maximum Setting 33 Set value addition for DHW This value is added to Parameter 1 to set the operating temperature of the Prestige during a DHW request See pages 6 through 9 for additional information 46ºF 00ºF 54ºF 35 See Warning Below Selection of the DHW application Storage tank application with NTC sensor 12 Storage tank wi...

Page 8: ...ter 1 is the set point temperature for domestic water storage in the IDWH The heat request for domes tic heating is based on this parameter setting To adjust WARNING the parameter setting press MODE until display shows PARA Press STEP once and the display should show factory setting 1140 Use the or to adjust the setting Press STORE to save the setting The display will flash when the setting is sto...

Page 9: ...thermostatic mixing valve on the hot water out let of the DHW storage tank Failure to comply could result in severe personal injury death or substantial property damage Parameter Adjustments To adjust DHW NTC sensor differential DETECTION ON value follow the steps given in the Program Access Section on page 2 until the display shows P_26 Release the STEP button and the display should show the fact...

Page 10: ...eter 1 and Parameter 33 WARNING The Detection OFF setting of Parameter 27 greatly affects the production of domestic hot water A maximum setting of Parameter 27 could result in excessive domestic storage tempera ture resulting in a potential scald hazard It is strongly recommended that the installer utilize a thermostatic mixing valve on the hot water out let of the DHW storage tank Failure to com...

Page 11: ...from a NTC sensor or DHW aquastat The DHW circulator will remain energized at all times even during a CH request for heat The Prestige will maintain all CH operation both burner and CH circulator function with no domestic priority feature ON Pump Continuous The Prestige will main tain continuous circulation on the DHW circulator and will provide burner function when a request for heat is generated...

Page 12: ...ARA mode In the STBY mode press and hold for approximately 2 seconds the button The panel display should flash a d followed by a display of dXXX with XXX indicating the current boiler temperature NOTICE Returning the unit to the ON mode using the button will restore the burner function in response to a call for heat request by the IDWH If the unit is in a continuous pump func tion the circulator w...

Page 13: ...ng the current boiler temperature NOTICE NOTICE 11 DOMESTIC HOT WATER APPLICATION PUMP SETUP At the completion of a DHW request for heat the amount of time for post pump activity can be determine The post pump feature allows the stored heat within the boil er to be absorbed in the Domestic Tank thus preventing any potential overheating of low temperature space heating applications When utilizing a...

Page 14: ...er delay in reacting to a CH space heat ing request for heat can be determined The blocking time feature in conjunction with the DHW post pump cycle may prevent any potential overheating of a low temperature CH system This blocking time period does not affect the production of domestic hot water If the parameter setting is 00 OFF setting for this func tion feature and the burner is firing at the c...

Page 15: ...ditional information 7 The maximum outdoor temperature setting when using the optional outdoor sensor 64ºF 60ºF 78ºF outdoor sensor required See page 21 for additional information 8 The minimum outdoor temperature to initiate the frost protection mode on the boiler 22ºF 22ºF 50ºF outdoor sensor required See page 22 for additional information 10 outdoor sensor required T4 Block Temperature setting ...

Page 16: ...se for heat Room thermostat Outdoor temperature external controller 00 00 05 See WARNING Below See pages 15 through 18 for additional information 38 Boiler hold temperature setting Maintains a minimum boiler temperature 32ºF 32ºF 176ºF See page 25 for additional information CENTRAL HEATING CH APPLICATION PARAMETERS GENERAL GUIDE Parameter 34 has multiple parameter settings available in addition to...

Page 17: ...e setting of the limit can only be done by entering into the access code of the control Parameter Adjustment The parameter adjustment of Parameter 5 in the CODE mode is done by following the steps given in Program Access Section on page 2 until the display shows 5_XX Use the or to adjust to the revised setting and press STORE to save the setting CH APPLICATION FUNCTION SETTING ROOM THERMOSTAT The ...

Page 18: ... allowable oper ating temperature in Parameters 4 and 5 This applica tion requires the use of a 12k NTC sensor reference Triangle Tube s Outdoor Sensor Kit connected to the appropriate 24V terminals on the Prestige The use of a room thermostat is not required typ ically in this application The room thermostat has no control over the CH burner function or the CH circulator function The room thermos...

Page 19: ...ing Temperature High Limit Parameter 4 on page 15 Boiler Operating Temperature Low Limit Parameter 5 on page 15 Boiler Operational Function Options Burner and CH Circulator Function Options Parameter 3 on page 19 through 21 CH Circulator Post Operation Parameter 20 on page 24 CH Heat Request Blocking Time Parameter 28 on page 25 Application System Options Burner Blocking Temperature Parameter 10 o...

Page 20: ...meet the load requirements An analog input of 0V will indicate the minimum system temperature of 32ºF and an analog input of 10V relates to a maximum sys tem temperature of 212ºF Because these tempera tures are outside the normal operating limits of the Prestige the minimum and maximum system tem perature must be set using Parameter 4 and 5 The actual function of the external controller will vary ...

Page 21: ...l option to OFF can be done either through the STBY mode during normal operation or by entering into the CODE mode When the unit is in normal operation and in the STBY mode press MODE once to enter PARA Press STEP three times to Parameter 3 Press or button to adjust to the following revised setting and press STORE to save the setting The unit can also be place into the OFF mode when the unit is in...

Page 22: ...ng the steps given in Program Access Section until the display shows 3_XX Use the or to adjust to the revised setting listed below and press STORE to save the setting Parameter Adjustments ON Continuous Pump Mode The parameter adjustment to set the DWH operational option to ON Continuous Pump can be done either through the STBY mode during normal operation or by entering into the CODE mode When th...

Page 23: ...er Adjustment To revise the coldest design temperature day adjustment of Parameter 6 in the CODE mode is done by following the steps given in Program Access Section on page 2 until NOTICE the display shows P_06 Use the or to adjust to the revised setting and press STORE to save the setting OUTDOOR TEMPERATURE MAXIMUM SETTING Parameter Adjustment To revise the warmest design temperature day adjust ...

Page 24: ...t in rela tion to the outdoor temperature see CH Application Function Setting Outdoor Temperature on page 16 the installer can set a desired temperature in which the request for heat has ended Once the calculated operating boiler temperature based on the outdoor temperature falls below the setting of the T4 Block Temperature the request for heat ends and the boiler will begin any post pump activit...

Page 25: ... UL UTZOT U Y KGZ 8KW KYZ OSK 6KXOUJ YZGHROYNKJ OT VGXGSKZKX GRI RGZKJ UORKX 5VKXGZOTM KSVKXGZ XK UORKX 5VKXGZOTM KSVKXGZ XK UUYZ GRR LUX KGZ 4U 8KW KYZ LUX KGZ 3G UORKX 5VKXGZOTM KSVKXGZ XK UX 6GXGSKZKX NOINK KX OY RU KX LZKX ZNK HUORKX UVKXGZOTM ZKSVKXGZ XK NGY HKKT HUUYZKJ ZNK HUUYZKJ HUORKX UVKXGZOTM ZKSVKXGZ XK ORR JKIXKGYK SOT GLZKX ZNK īIGRR LUX NKGZĬ KTJY ZU ZNK IGRI RGZKJ HUORKX UVKXGZOTM...

Page 26: ... contacts open the calculated system temperature will decrease the amount of the Parallel Shift in Parameter 12 Parameter Adjustment The parameter adjustment for Parallel Shift is Parameter 12 Follow the steps given in Program Access Section on page 2 until the display shows P_12 Release the STEP button and display should show the factory default setting Use the or button to adjust to the revised ...

Page 27: ...ler Hold Temperature feature With this setting the Boiler Hold Temperature feature is not applied SPACE HEATING APPLICATION CH REQUEST FOR HEAT SETUP At the completion of a CH request for heat the amount of time for delay in reacting to a secondary CH request for heat can be determine and set The blocking time fea ture prevents potential short cycling of the boiler During the blocking period the b...

Page 28: ...um operating temperature 186ºF 86ºF 194ºF See page 15 for additional information 5 CH boiler operating temperature set point This is the minimum allowable operating temperature during the warmest outdoor temperature when using the optional outdoor sensor 86ºF 60ºF 140ºF See page 15 for additional information 6 The minimum outdoor temperature setting when using the optional outdoor sensor 00ºF 04ºF...

Page 29: ...15 Do Not Adjust this Parameter 53 16 Do Not Adjust this Parameter 00 17 Do Not Adjust this Parameter 19 18 Do Not Adjust this Parameter 00 19 Do Not Adjust this Parameter 36 20 Post pump feature setting for the CH circulator supplied with the boiler 01 00 99 See page 24 for additional information minutes 10 seconds minutes 21 The DHW circulator post pump time period applied after the completion o...

Page 30: ...ditional information 31 Do Not Adjust this Parameter 44 32 Do Not Adjust this Parameter 01 33 Set value addition for DHW This value is added to Parameter 1 to set the operating temperature of the Prestige during a DHW request See pages 6 through 9 for additional information 46ºF 00ºF 54ºF 34 See WARNING Below Selection of CH application type based on the response for heat Room thermostat Outdoor t...

Page 31: ...arameter 01 37 Do Not Adjust this Parameter 41 38 Boiler hold temperature setting Maintains a minimum boiler temperature 32ºF 32ºF 176ºF See page 25 for additional information 39 Do Not Adjust this Parameter 122 40 Do Not Adjust this Parameter 68 41 Do Not Adjust this Parameter 10 42 Do Not Adjust this Parameter 0 ...

Page 32: ...12 Tel 856 228 8881 Fax 856 228 3584 E mail Sales triangletube com For domestic water snow melting radiant floor refrigeration Plates made of stainless steel with a 99 9 copper and brazed ensuring a high resistance to corrosion Self cleaning and self descaling Computerized sizing available from Triangle Tube Phase III Available in capacities from 25 000 BTU hr to 5 000 000 BTU hr Member of Group H...