background image

TR-B200S-LF-WH, TR-B200S-LF-IV

Low Frequency Intelligent Sounder Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEFORE INSTALLING

Read

 

Applications  Guide  for  System  Smoke  Detectors

,

  which  provides 

detailed  information  on  sensor  spacing,  placement,  zoning,  wiring,  and 
special applications. NFPA 72 and NEMA guidelines should be observed. The 
National Fire Alarm Code, NFPA 72, requires effective January 1, 2014, that 
audible  appli-ances  installed  in  sleeping  areas  produce  a  low  frequency 
alarm signal that shall be a square wave or provide equivalent awakening 
ability with a funda-mental frequency of 520 Hz +/– 10%.

NOTE:

 Triga Series sounder bases are not compatible with remote test 

capable Triga Series detectors.

NOTICE:

 This manual should be left with the owner/user of this equipment.

IMPORTANT:

  The  detector  used  with  this  base  must  be  tested  and 

maintained regularly following NFPA 72 requirements. The detector should 
be cleaned at least once a year.

GENERAL DESCRIPTION

The  TR-B200S-LF-WH  and  TR-B200S-LF-IV  sounder  bases  are  used  with 
ad-dressable  detector  heads.  Refer  to  the  appropriate  manual  for  more 
informa-tion on sensors.
The  TR-B200S-LF-WH/TR-B200S-LF-IV  low  frequency  sounder  base 
generates a low frequency tone around 520 Hz. Studies have shown that low 
frequency audible devices that operate around 520 Hz are more effective in 
waking indi-viduals in sleeping areas.
The  sounder  base  is  capable  of  producing  a  variety  of  tone  patterns, 
includ-ing  the  distinctive  three-pulse  temporal  pattern  (ANSI  Temporal  3) 
fire alarm signal now required by NFPA 72 for commercial and residential 
applications.  The  TR-B200S-LF-WH/TR-B200S-LF-IV  offers  maximum 
flexibility  in  configu-ration  and  operation  to  meet  or  exceed  the 
requirements  of  UL268  and  UL464  for  Continuous,  Temporal  3  and  March 
time patterns. The temporal 4 pattern meets all requirements of UL268 and 
UL2075, as well as, private mode setting of UL 464.
The  TR-B200S-LF-WH/TR-B200S-LF-IV  can  be  commanded  by  the  Fire 
Alarm  Control  Panel  (FACP)  to  adopt  the  address  of  the  attached  sensor 
head, but as a unique device type on the loop. By using the address, the 
FACP  can  com-mand an  individual  sounder  base  to  activate,  or  a  group  of 
sounders  in  a  suite  or  other  multi-room  configuration.  The  command  set 
from the panel can be tailored to the specific event, allowing selection of 
volume, tone, and group. The device offers two volume levels: 75 dBA and 
85  dBA.  The  available  tones  are  Continuous,  ANSI  Temporal  3,  ANSI 
Temporal 4, and March Time. In ad-dition, some panels will offer the ability 
to command a custom tone pattern. Refer to the appropriate FACP manual 
for more information.

SPECIFICATIONS

Base Diameter: 

6.875" (17.46 cm)

Base Height (less sensor): 

2.0" (5.08 cm)

Weight: 

0.6 lb. (272 g)

Operating Temperature Range:  Refer to the applicable sensor’s operating temperature range provided in the sensor’s installation manual. 
Operating Humidity Range: 

10% to 93% relative humidity (non-condensing)

External Supply Electrical Ratings

External Supply Voltage: 

16 to 33 VDC (VFWR)

Standby Current: 

550 μA maximum VDC

Alarm Current: 

High volume setting:  70 mA maximum @ 33.0 VDC 

Low volume setting:  15 mA maximum @ 33.0 VDC

90 mA maximum @ 24.0 VDC 

20 mA maximum @ 24.0 VDC

140 mA maximum @16.0 VDC 

25 mA maximum @ 16.0 VDC

SLC Electrical Ratings

SLC Operating Voltage: 

15 to 32 VDC

SLC Standby Current: 

300 μA maximum (base only, refer to applicable sensor specification)

Sound Output

High Volume: 

Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet (3.1m), 24 Volts (in continuous tone)

Low Volume: 

Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet (3.1m), 24 Volts (in continuous tone)

In addition, the TR-B200S-LF-WH/TR-B200S-LF-IV is equipped with the cir-
cuitry to recognize the System Sensor synchronization protocol, enabling the 
sounder base to be used as a component of the general evacuation signal – 
producing an NFPA 72 compliant Temporal 3 pattern in synchronization with 
compatible listed notification devices. This requires connection to a power 
supply capable of generating the System Sensor synchronization pulses, a 
FACP NAC output configured to System Sensor synchronization protocol, or a 
separate synchronization module. 
The sounder base is intended for use with intelligent systems. In addition to 
being connected to the SLC, the sounder base requires a connection to either 
24 VDC constant power or a NAC circuit, depending on the FACP and intended 
use. The connections for 24V constant/NAC power and the communication 
loop are isolated to prevent electrical interaction between them. 
When connected to a NAC, power is supervised via the NAC circuit supervi-
sion while in standby mode (EOL resistor required for Class B operation). 
When activated, the TR-B200S-LF-WH/TR-B200S-LF-IV provides supervision 
of NAC power. (See Figure 5.) 
When using a FACP equipped with a “sounder base standby power monitor-
ing” mode and constant 24 V power, power supervision EOL devices (supervi-
sion relays and resistors) should not be used. (See Figure 4.) In this case, the 
TR-B200S-LF-WH/TR-B200S-LF-IV will provide supervision in both standby 
and alarm/active mode. Refer to FACP installation documentation to deter-
mine if this mode is available. If your FACP does not support this mode or you 
choose not to use it, power supervision relays and EOL resistors are required 
to provide supervision in standby mode.

NOTE:

 If the FACP’s “sounder base standby power monitoring” mode is en-

abled, connecting TR-B200S-LF-WH/TR-B200S-LF-IV low frequency sounder 
bases to the NAC will result in power supervision failure when in standby. 
Only connect TR-B200S-LF-WH/TR-B200S-LF-IV low frequency sounder bases 
to constant 24 V power in this case. Refer to the FACP manual for maximum 
allowable number of units per loop.

NOTE:

 For NFPA72 Installations, the Temporal 3 tone at high volume should 

be used for public mode evacuation. The use of other tone styles and low 
volume level will be at the discretion of the local Authority Having Jurisdic-
tion (AHJ).

NOTE:

 When not used as a supplementary evacuation system, the external 24 

VDC supply shall be treated as a component of the main power supply system 
and shall fall under the requirements of the main power supply system per 
NFPA 72.

I56-4

15

1TRG-00

5

This model is compatible with Models MDL, MDL3R, MDLW, MDL3W and SYNC-1

TRIGA Life Safety Systems, LLC

7600 Olde Eight Rd.

Hudson, Ohio 4426-1057

Tel: +1 330-577-5199. Email: info@trigaglobal.com 

base/sensor cross reference chart ==>

base/sensor cross reference chart ==>

Source:
For a list of compatible sensors, refer to the Sys-
tem Sensor website at www.systemsensor.com.
1/29/2021
For a complete list of compatible sensors, refer to 
the Base/Sensor Cross Reference Chart at triga-
global.com.

4/23/2021 DELETE: For a complete list of compatible 

4/23/2021 DELETE: For a complete list of compatible 
bases, refer to the Base/Sensor Cross Reference Chart at 

bases, refer to the Base/Sensor Cross Reference Chart at 
trigaglobal.com.

trigaglobal.com.

I56-4151TRG-005 

4/22/2021

Summary of Contents for TR-B200S-LF-WH

Page 1: ...setting 15 mA maximum 33 0 VDC 90 mA maximum 24 0 VDC 20 mA maximum 24 0 VDC 140 mA maximum 16 0 VDC 25 mA maximum 16 0 VDC SLC Electrical Ratings SLC Operating Voltage 15 to 32 VDC SLC Standby Current 300 μA maximum base only refer to applicable sensor specification Sound Output High Volume Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone L...

Page 2: ...6 Install a compatible smoke sensor as described in the installation manual for the sensor CAUTION Do not over tighten mounting plate screws this may cause mounting plate to flex TAMPER RESISTANT FEATURE NOTE Do not use the tamper resist feature if the removal tool is to be used This detector base includes a tamper resist feature that prevents its removal from the base without the use of a tool To...

Page 3: ...AC OPTIONAL REMOTE ANNUNCIATOR MODEL TR RA100Z E O L A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE THE SYNCHRONIZATION PULSES HORN HORN STROBE UL LISTED COMPATIBLE CONTROL PANEL UL LISTED 24V POWER SUPPLY WHEN USING 24V CONSTANT POWER AUX POWER ADDITIONAL POWER SUPERVISION RELAYS AND MODULES WILL BE REQUIRED FOR PROVIDING SUPERVISION WHEN THE SOUNDER BASES ARE INACTIVE CLASS A OPTIONAL ...

Page 4: ...90 02 NOTE Wiring shown for System Sensor MDL Series Sync Module For additional wiring configurations see your sync module manual FACP 1 EOL 1 HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF NAC 1 B B NAC 2 B B NAC 3 B B TO NEXT DEVICE OR EOL 1 TO NEXT DEVICE OR EOL 1 2 CLASS B ZONES MASTER SOUNDER BASE SOUNDER BASE OPTIONAL Triga is a trademark...

Reviews: