background image

TRACKSO INSTALLATION GUIDE FOR TRINITY NF29 METER 

 

Brand:     Trinity 
Type:      Multi-line Digital Display Panel Meter 
Models:  Trinity NF29 Meters 

CONNECTION DIAGRAM 

On the rear panel, Trinity NF29 Meters has an RS-485 communication socket as shown in the following figure.  

Figure T1 – Rear view of Trinity NF29 Meter 

 

1.

 

Please unscrew the  RS485 terminal as shown in Figure T1.  

2.

 

Connect the cables to the RS485 bus terminal blocks.  

3.

 

Please make the connections from Terminal Block chip to TrackSo IoT 
Gateway as mentioned in the Table – TT1. 

Table TT1 – Trinity NF29 Meter  RS485 chip 

connections with TrackSo IoT Gateway 

Trinity NF29 Pin No. & 

Assignment 

TrackSo Pin No. & 

Assignment 

D+ 

D- 

 

 

DEFAULT CONFIGURATION IN TRACKSO IOT GATEWAY 

 
Inverter ID: 1 (Range: 1 to 247) 
Baud Rate: 9600  
Data Bits: 8 
Stop Bit: 1 
Parity: N/A (None) 

CONFIGURATION AT THE  METER END 

Enter into programming mode to setup meter for communication 

In order to operate for all the field programmable parameters, it is easy user interface by pressing the keys such as 

keys. Once the unit displays CT PRIMARY, press key to move into the next programmable parameter, UNIT 

ADDRESS for RS485 communication. 

 

Summary of Contents for NF29

Page 1: ...to TrackSo IoT Gateway as mentioned in the Table TT1 Table TT1 Trinity NF29 Meter RS485 chip connections with TrackSo IoT Gateway Trinity NF29 Pin No Assignment TrackSo Pin No Assignment 2 A 3 D 1 B 4 D DEFAULT CONFIGURATION IN TRACKSO IOT GATEWAY Inverter ID 1 Range 1 to 247 Baud Rate 9600 Data Bits 8 Stop Bit 1 Parity N A None CONFIGURATION AT THE METER END Enter into programming mode to setup m...

Page 2: ...splay with the settable parameter unit ADDRESS such as shown below 3 Press key Immediately P starts blinking with an interval of one second which shows that the parameter is now settable Set the ADDRESS by using keys until the desired value is received and then press key to confirm the set value 4 Now the unit will reset and return into Run Mode NOTE The above details are mentioned in the Installa...

Page 3: ...he installed location LED NAME DESCRIPTION GREEN POWER Light when Power on the device RED GSM LED Status Connection State Flashing ON for 100ms and OFF for 100ms SIM Card not found Flashing ON for 500ms and OFF for 500ms Searching for GSM Network Flashing ON for 0 1s and OFF for 2 9s Once at every 3sec GSM Network Registered Flashing twice at every 3sec GPRS IP Connected Flashing 5times GPRS IP Se...

Page 4: ...ted NC not connected PIP Connected to TrackSo Server or not CONT connected NC not connected LOG no of data points stored in devices incase of no interet 6 If the GSM light starts flashing 5 times then Login to www trackso in with your Username Password 7 Click on Units from the menu bar You will be able to view your installed unit in the table as shown below 8 Check if the Status becomes Receivein...

Page 5: ...op right of the screen and click on Event Ingestion Logs in the dropdown 10 Check if there is some log generated at the time of installation of the TrackSo IoT Gateway device a If NO please restart the device and try the same flow again b If YES email us at support trackso in to consult the same ...