Model #: SMX1200XLHG

SmartPro Medical Grade 1kVA 230V Line interactive Tower UPS, Extended-run, full isolation, USB and Serial
ports

 

Highlights

1000VA / 1kVA line interactive, extended run tower UPS

Maintains 230V nominal output over an input range of 155 to 274V

Professional features include serial port, IEC320 plug & outlets, built-in

isolation transformer

Input: IEC C14 inlet (230V 5A) / Output: 6 IEC C13 (230V)

Description

Tripp Lite's SMX1200XLHG offers medical-grade UPS protection with built-in line-interactive voltage regulation, expandable battery runtime and

intelligent monitoring with unattended shutdown capability. Tested to CE/IEC 60601-1 standard as medical electrical equipment. Built-in isolation

transformer with Faraday shield offers full line isolation and removes common mode noise while maintaining full AC surge suppression in all modes.

Includes high quality hospital-grade plug and outlets. Resistant to electrostatic discharge. 1000VA power handling capacity supports computers,

inter-networking equipment and other critical loads during commercial power failures. External battery connector allows configuration for up to

several hours of runtime during power failures by adding one or more external battery packs (BP36V15-2U limit 1 or BP36V42-3U multi-pack

compatible). Line interactive voltage regulation corrects brownouts as low as 155V and overvoltages as high as 274V back to normal 230V levels,

saving battery reserves for use only during complete power failures. Includes diagnostic LEDs and 2 built-in communications ports (1 USB, 1 DB9)

that work with included PowerAlert Software and cabling to provide automatic unattended shutdown of connected network and PC applications.

Applications

CE/IEC 60601-1 compliant UPS provides ultimate safety and reliability for patient point of care solutions, telemedicine, nurse's stations, wireless

communications systems, electronic prescribing applications, medical imaging and mission critical equipment. Not recommended for life support

applications

Package Includes

SMX1200XLHG Medical Grade Tower UPS System 

PowerAlert Software and cabling 

Warranty information 

Instruction manual

Features

Ideal UPS protection for applications in medical patient-care areas where CE/IEC 60601-1 listed medical electrical equipment is required

Built-in isolation transformer with Faraday shield offers full isolation and removes common mode noise while maintaining full AC surge

suppression in all modes

Provides connected equipment with continuous power during short and long duration loss of commercial power

Expandable runtime is available with the addition of one or more external battery packs (BP36V15-2U limit 1 or BP36V42-3U multi-pack

Summary of Contents for SmartPro SMX1200XLHG

Page 1: ...ing one or more external battery packs BP36V15 2U limit 1 or BP36V42 3U multi pack compatible Line interactive voltage regulation corrects brownouts as low as 155V and overvoltages as high as 274V back to normal 230V levels saving battery reserves for use only during complete power failures Includes diagnostic LEDs and 2 built in communications ports 1 USB 1 DB9 that work with included PowerAlert ...

Page 2: ...t on battery voltage correction overload battery low replace Battery replacement door and back panel grounding lug Specifications OUTPUT Output Volt Amp Capacity VA 1000 Output Watt Capacity watts 750 Nominal Output Voltage s Supported 230V Frequency compatibility 50 60 Hz auto selectable Output voltage regulation line mode 18 8 Built in UPS output receptacles 6 C13 outlet s INPUT Rated input curr...

Page 3: ...3 and 199 are boosted by 10 Severe undervoltage correction Input voltages between 156 and 182 are boosted by 21 Direct pass through Input voltages between 200 and 244V AC are passed through unchanged LEDS ALARMS SWITCHES LED Indicators 5 LEDs indicate line power battery power overload voltage regulation and battery low replace status Alarms 3 function audible alarm indicates power failure conditio...

Page 4: ...e Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 252 2 Battery mode BTU hr full load 252 2 COMMUNICATIONS Communications interface USB DB9 Serial Software and cabling included PowerAlert UPS monitoring software is included on CD ROM for all common network and standalone operating systems Ships with 2 cables 1 USB to USB ...

Page 5: ...V15 2U External Battery Pack for UPS System 1 External Battery Packs BP36V42 3U BP36V42 3U External Battery Pack for UPS System 1 More information including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products model cfm txtModelID 3868 Copyright 2012 Tripp Lite All rights reserved All trademarks are the sole property of their...