MAINS DISTRIBUTION UNIT 

MDU12-PMi 

 
 
 
 
 
 
 

 

Television Systems Limited.

 

Vanwall Road, Maidenhead, Berkshire, SL6 4UB 

Tel44 (0)1628 676200, FAX +44 (0)1628 676299 

Summary of Contents for MDU12-PMi

Page 1: ...MAINS DISTRIBUTION UNIT MDU12 PMi Television Systems Limited Vanwall Road Maidenhead Berkshire SL6 4UB Telephone 44 0 1628 676200 FAX 44 0 1628 676299...

Page 2: ...MDU12 PMi Manual 2 Issue 4 This Page is Blank...

Page 3: ...uction 4 0 Operation 4 1 The Home Screen 4 2 The Output Screen 4 3 The System Screen 4 4 The SNMP Screen 4 4 1 SNMP Alarms 4 4 2 Email Alerts 5 0 Initial Configuration 6 0 Pin outs 7 0 Response Times...

Page 4: ...MDU12 PMi Manual 4 Issue 4 This Page is Blank...

Page 5: ...mounted equipment must be earthed grounded Mounting Careful consideration of the equipment location and mounting in racks must be made In particular consideration must be given to the stability of fre...

Page 6: ...warranty If any TSL product should fail or become faulty within the warranty period first please check the PSU fuses All maintenance work must be carried out by trained and competent personnel If equi...

Page 7: ...acking Please ensure that the unit is well packed as all mechanical damage is chargeable TSL recommends that you insure your equipment for transit damage The original packaging when available should a...

Page 8: ...ty Standards Declared EN 50081 1 EN 50082 1 Manufacturer s Name Television Systems Ltd Manufacturer s Address Vanwall Road Maidenhead SL6 4UB England United Kingdom Type of Equipment Mains Distributio...

Page 9: ...it configuration and SNMP data via secure web browser interface Relay controlled outputs with delayed power up Latching relays are fitted to reduce internal heat dissipation as they draw no current on...

Page 10: ...configuration and also to set a user name and password needed to access the web pages The power must be cycled after this operation for changes to take effect Refer to section 5 p15 for initial config...

Page 11: ...11 Issue 4 Home Screen This shows the total power consumed by the MDU in Watts VA and current in amps with the power factor To navigate back to this page from any other click on the TSL Logo at the t...

Page 12: ...may be changed for this screen The Input names may be changed from the default Highlight the text type new text as in any Windows style application The input circuit polarity may be set at either Nor...

Page 13: ...6 seconds NB These delays are only effective on initial powering of the unit The SNMP Lock box if checked disables remote control access for that channel via SNMP protocol Press Update when done NB Al...

Page 14: ...y will enable the Delay set in the Outputs screen Sequential will allow circuit by circuit delay as set in the box Lower and upper voltage alarm thresholds can be set from this page If the input volta...

Page 15: ...MDU12 PMi Manual 15 Issue 4 4 3 The Status Screen This page shows the overall alarm status for the unit and refreshes every 10 seconds...

Page 16: ...reaks the upper or lower threshold values as set on the system page For details of these and other SNMP features see the supplied SNMP MIB file Press Update when done NB Allow the page to refresh befo...

Page 17: ...hen wait for the next prompt User Enter a username max 12 characters Factory default is root Then wait for the next prompt Pass Enter a password max 12 characters Factory default is telsys When these...

Page 18: ...socket RJ11 Front Panel D 9 socket D 25 socket 3 5 3 2 2 2 2 3 5 4 GND 5 7 GPI Connector D37 F GPI INPUT CONNECTOR D37 SOCKET 1 Input 1 20 Input 1 2 Input 2 21 Input 2 3 Input 3 22 Input 3 4 Input 4...

Page 19: ...agents give priority to analysing network traffic and then look at the trap queue when idle Start up delays Maximum delay is 256 seconds between each relay in Sequential Start mode and up to 50 secon...

Page 20: ...MDU12 PMi Manual 20 Issue 4 Ethernet Standard IEEE 802 3 Physical layer 10 100 Base T Data Rate 10 100 Mbps auto sensing Mode Full or half duplex auto sensing Connector RJ45...

Page 21: ...ense data As of 08 08 09 added voltage measure and trap tslMIB MODULE IDENTITY LAST UPDATED 0908080000Z ORGANIZATION Television Systems Ltd CONTACT INFO Tim Whittaker Television Systems Ltd Vanwall Ro...

Page 22: ...alarmTableIndex INTEGER alarmType INTEGER alarmIndex INTEGER alarmText DisplayString alarmState INTEGER alarmPolarity INTEGER alarmData Opaque alarmTableIndex OBJECT TYPE SYNTAX INTEGER 1 28 ACCESS r...

Page 23: ...INTEGER notApplicable 1 normallyOpen 2 normallyClosed 3 ACCESS read write STATUS mandatory DESCRIPTION Alarm active polarity notApplicable for non gpi alarms alarmEntry 6 alarmData OBJECT TYPE SYNTAX...

Page 24: ...oint degrees Centigrade alarm 6 alarmTrap TRAP TYPE ENTERPRISE tslMIB VARIABLES alarmTableIndex alarmType alarmIndex alarmText alarmState alarmPolarity alarmData DESCRIPTION An entry in the alarm tabl...

Page 25: ...ween outputs mdu12 3 mduOutputTable OBJECT TYPE SYNTAX SEQUENCE OF MduOutputEntry ACCESS not accessible STATUS mandatory DESCRIPTION Table of output controls mdu12 4 mduOutputEntry OBJECT TYPE SYNTAX...

Page 26: ...ite STATUS mandatory DESCRIPTION Output on delay from power on Delay mode only mduOutputEntry 3 mduOutputlowerCurrent OBJECT TYPE SYNTAX INTEGER ACCESS read write STATUS mandatory DESCRIPTION Lower cu...

Page 27: ...data mduOutputEntry 10 End of table mduPowerStatus OBJECT TYPE SYNTAX INTEGER totalLoss 1 input1OK 2 input2OK 3 allOk 4 note a single input MDU would report allOk if power is present ACCESS read only...

Page 28: ...BJECT TYPE SYNTAX INTEGER ACCESS read write STATUS mandatory DESCRIPTION Current total limit mdu12 11 mduPowerStatusTrap TRAP TYPE ENTERPRISE tslMIB VARIABLES mduPowerStatus DESCRIPTION The power inpu...

Page 29: ...MDU12 PMi Manual 29 Issue 4...