Quick-Start Guide

FTCI-3/4D15A4P-2LUX-H1141

Other documents

Besides this document, the following material can be found on the Internet 

at 

www.turck.com

:

 

Data sheet

 

EU declaration of conformity (current version)

For your safety

Intended use

The devices are designed only for use in industrial areas.

 

The devices are used for flow measurement of water/glycol mixes up to 

70 %, deionized water, HT110 and HT135. 

The devices can monitor the flow rate and temperature and display these 

values on a three-digit seven-segment display. The devices are intended for 

inline mounting in a pipe.

The devices must only be used as described in these instructions. Any other 

use is not in accordance with the intended use. Turck accepts no liability for 

any resulting damage.

Obvious misuse

The devices are not safety components and must not be used for personal or 

property protection.

General safety notes

 

The device must be mounted, installed, operated, parameterized and 

maintained only by trained and qualified personnel.

 

The monitored medium must be free of air pockets and bubbles. 

Product description

Device overview

See Fig. 1 (product image)

Functions and operating modes

The devices have two analog outputs (0…10 V). A voltage signal for the flow 

rate is issued at output 1, while a voltage signal for the temperature value 

is issued at output 2. The values for flow rate and temperature can also be 

shown alternately on the display. The following device functions can be 

configured using the three buttons on the front of the device:

 

Access code: protects the device from unauthorized programming access

 

Initial temperature value/final temperature value

 

Mean value generation: sets a time interval for generating the mean value 

of the measuring signal (2…16 s). A low value results in a fast response, a 

higher value results in the steady display of the measured value.

 

Media selection: sets the media to be monitored.

 

Reference function: changes the value shown in the display by ± 25 %.

Mounting

CAUTION

Shearing forces between the pipe connections of the device

Damage to equipment caused by shearing forces

Mount the device in such a way that shearing forces between the pipe 

connections of the device are prevented. See Fig. 2

The devices are intended for inline mounting in a pipe. When installing, the 

pipe can be connected either directly via the cutting ring fitting or by using 

an adapter (not included in the delivery).

 

Pay attention to the flow direction when mounting (see type label).

Mounting the cutting ring fitting

 

If mounting the device without using an adapter, use a precision pipe 

(3/4”) in accordance with DIN 2391. 

 

Cut the pipe to length with a perpendicular cut and remove burrs.

 

Slide the union nut onto the pipe, along with the clamp ring and cutting 

ring.

 

Insert the pipe in the fitting body as far as it will go.

 

Tighten the union nut by hand and check the position of the pipe.

 

Apply an AF27 wrench to the sensor connection.

 

Tighten the union nut by 1 ¼ turns.

 

Check that the pipe is securely seated.

Mounting the housing

The sensor is equipped with four M4 threaded bushes with a depth of 5 mm 

in the bottom of the housing to facilitate mounting.

 

Mount the device at the intended location using four M4 screws.

Alternatively:

 

Mount the device on mounting plate FTCI-MP01AL (Ident-No. 6870040, 

not included in the delivery). With the mounting plate, it is possible to 

install the device from the front.

Connection

 

Connect the device in accordance with the “Wiring Diagram.”

Commissioning

The device is operational automatically once the power supply is switched 

on.

© Hans Turck GmbH & Co. KG | 100017718 2020-03 EN 

FTCI-3/4D15A4P-2LUX-H1141

FTCI-3/4D15A4P-2LUX-H1141

Flow Meter

Quick-Start Guide

Doc.-No. 100017718  2003

Additional  

information see 

turck.com

Wiring Diagram

+

2 WH
4 BK

1 BN
3 BU

U

TEMP

U

FLOW