EN
Quick-Start Guide
FTCI-3/4D15A4P-2LUX-H1141
Other documents
Besides this document, the following material can be found on the Internet
at
www.turck.com
:
■
Data sheet
■
EU declaration of conformity (current version)
For your safety
Intended use
The devices are designed only for use in industrial areas.
The devices are used for flow measurement of water/glycol mixes up to
70 %, deionized water, HT110 and HT135.
The devices can monitor the flow rate and temperature and display these
values on a three-digit seven-segment display. The devices are intended for
inline mounting in a pipe.
The devices must only be used as described in these instructions. Any other
use is not in accordance with the intended use. Turck accepts no liability for
any resulting damage.
Obvious misuse
The devices are not safety components and must not be used for personal or
property protection.
General safety notes
■
The device must be mounted, installed, operated, parameterized and
maintained only by trained and qualified personnel.
■
The monitored medium must be free of air pockets and bubbles.
Product description
Device overview
See Fig. 1 (product image)
Functions and operating modes
The devices have two analog outputs (0…10 V). A voltage signal for the flow
rate is issued at output 1, while a voltage signal for the temperature value
is issued at output 2. The values for flow rate and temperature can also be
shown alternately on the display. The following device functions can be
configured using the three buttons on the front of the device:
■
Access code: protects the device from unauthorized programming access
■
Initial temperature value/final temperature value
■
Mean value generation: sets a time interval for generating the mean value
of the measuring signal (2…16 s). A low value results in a fast response, a
higher value results in the steady display of the measured value.
■
Media selection: sets the media to be monitored.
■
Reference function: changes the value shown in the display by ± 25 %.
Mounting
CAUTION
Shearing forces between the pipe connections of the device
Damage to equipment caused by shearing forces
➤
Mount the device in such a way that shearing forces between the pipe
connections of the device are prevented. See Fig. 2
The devices are intended for inline mounting in a pipe. When installing, the
pipe can be connected either directly via the cutting ring fitting or by using
an adapter (not included in the delivery).
➤
Pay attention to the flow direction when mounting (see type label).
Mounting the cutting ring fitting
➤
If mounting the device without using an adapter, use a precision pipe
(3/4”) in accordance with DIN 2391.
➤
Cut the pipe to length with a perpendicular cut and remove burrs.
➤
Slide the union nut onto the pipe, along with the clamp ring and cutting
ring.
➤
Insert the pipe in the fitting body as far as it will go.
➤
Tighten the union nut by hand and check the position of the pipe.
➤
Apply an AF27 wrench to the sensor connection.
➤
Tighten the union nut by 1 ¼ turns.
➤
Check that the pipe is securely seated.
Mounting the housing
The sensor is equipped with four M4 threaded bushes with a depth of 5 mm
in the bottom of the housing to facilitate mounting.
➤
Mount the device at the intended location using four M4 screws.
Alternatively:
➤
Mount the device on mounting plate FTCI-MP01AL (Ident-No. 6870040,
not included in the delivery). With the mounting plate, it is possible to
install the device from the front.
Connection
➤
Connect the device in accordance with the “Wiring Diagram.”
Commissioning
The device is operational automatically once the power supply is switched
on.
© Hans Turck GmbH & Co. KG | 100017718 2020-03 EN
FTCI-3/4D15A4P-2LUX-H1141
FTCI-3/4D15A4P-2LUX-H1141
Flow Meter
Quick-Start Guide
Doc.-No. 100017718 2003
Additional
information see
turck.com
Wiring Diagram
–
+
2 WH
4 BK
1 BN
3 BU
U
TEMP
U
FLOW
FC