background image

PENDENT & UPRIGHT SPRINKLERS , STD. COVERAGE

MODEL F892 DESIGNER

STANDARD RESPONSE, K=16.8 , 3/4"NPT **

GENERAL DESCRIPTION

The 16.8 K-Factor Model F892 De-
signer, Standard Response, Standard
Coverage, Pendent and Upright Sprin-
klers (Ref. Figure A) are automatic
sprinklers of the frangible bulb type.
They are “standard response - spray
sprinklers” which produce a hemi-
spherical water distribution pattern be-
low the deflector.

The F892 Sprinklers are intended for
use in fire sprinkler systems designed
in accordance with the standard instal-
lation rules recognized by the applica-
ble Listing or Approval agency (e.g.,
UL Listing is based  on  the  require-
ments of the National Fire Protection
Association). Also, when acceptable
to the Authority Having  Jurisdiction,
they may be used with a “Reduced
Design Area” as indicated in Table A.

The 16.8 K-Factor F892 Sprinklers
were subjected to full scale, high-piled
storage, fire tests to qualify their use in
lieu of 8.0 or 11.2 K-Factor standard

spray sprinklers for the protection of
high-piled storage.

Higher flow rates can be achieved at
much lower pressures with the 16.8
K-Factor F892 Sprinklers — making
their use highly advantageous in high
density applications, such as the pro-
tection of high-piled storage.

The 16.8 K-Factor F892 Sprinkler also
has the advantage of having a UL and
C-UL specific application listing, which
in some cases can subsequently re-
duce the design area and the overall
water demand of the sprinkler system.
Refer to Table A for details.

Applications for the 16.8 K-Factor
Model F892   Pendent and Upright
Sprinklers are expanding beyond the
current listings/approvals. For infor-
mation regarding research  fire  tests
which may be acceptable to an Author-
ity Having Jurisdiction, please contact
the Technical Services Department.

APPROVALS AND STANDARDS

Laboratory listings and approvals for
the 16.8 K-Factor, Model F892 De-
signer, Standard Response, Standard
Coverage, Pendent and Upright Sprin-
klers are given in Table A.

WARNING

The 16.8 K-Factor, Model F892 Pen-

dent and Upright Sprinklers de-

scribed herein must be installed and

maintained in compliance with this

document, as well as with the appli-

cable standards of the National Fire

Protection Association, in addition to

the standards of any other authorities

having jurisdiction. Failure to do so

may impair the integrity of these de-

vices.

The owner is responsible for main-

taining their fire protection system

and devices in proper operating con-

dition. The installing contractor or

manufacturer should be contacted

relative to any questions.

Printed in U.S.A. 3-01

TD595J

FIGURE A

16.8 K-FACTOR MODEL F892 PENDENT (SIN G1889) AND UPRIGHT (SIN G1888) SPRINKLERS

1 - Frame
2 - Button

3 - Gasketed

Spring Plate

4 - Bulb
5 - Deflector

6 - Compression

Screw

*

Temperature rating is indicated on deflector.

**

Pipe thread connections per ISO 7/1 can be provided on special request.

TYCO FIRE PRODUCTS

, 7071 S. 13th Street, Suite 103 Oak Creek, WI 53154 — www.gemsprinkler.com

Customer Service/Sales:

Tel: (877) 436-8926 / Fax: (877) 866-9250

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500