© 2008 Tyco Safety Products
PAGE 1 of 4
800 SERIES
17A-03-AV
2
11/08
Registered Company: Thorn Security Ltd.
Registered Office: Dunhams Lane
Letchworth Garden City
Hertfordshire
SG6 1BE
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
AV SERIES OF LOOP POWERED SOUNDERS
AND SOUNDER-BEACONS
INSTALLATION AND COMMISSIONING INSTRUCTIONS
SOUNDER
SOUNDER-BEACON
Fig. 1
PROGRAMMING
PORT
LOCKING
DEVICE
FITS
HERE
1.
TECHNICAL SPECIFICATION
System Compatibility:
Use only with ZX/MX
Fire Alarm Controllers
Environment
:
Models for indoor use only
Temperature
:
Operating:
-20°C to +70°C
Storage:
-25°C to +70°C
Humidity
:
Up to 95% (non-condensing)
Dimensions
:
Height:
36.5mm
Diameter:
115mm
Weight
:
Sounder only:
160g
Sounder/Beacon:
190g
Mounting Requirement
s
: Surface mount
The flat surface mounting flange is supplied with the
base. The DAB3-4 mounting flange must be ordered
separately.
The mounting flanges have to four drill positions for
mounting holes at 50mm, 60mm, 70mm and 80mm.
The sounder/ sounder beacon body clips onto the mounting
flange.
Electrical Characteristics:
Addressable Loop Voltage:
20 - 40Vdc
DC Loop Loading
Quiescent:
350
μ
A
Alarm:
See Tables 1 & 2
EMC
:
The base complies with the following:
Product family standard EN50130-4 in respect of
Conducted Disturbances, Radiated Immunity,
Electrostatic Discharge, Fast Transients and Slow High
Energy
EN61000-6-3 for Emissions
Low/ Mid Low
Mid High/High
Sound Output
60/70
80/90
dB
Sounder Only
2.6
4.4
mA
Sounder and Beacon
0.5Hz
5.7
7.5
mA
Sounder and Beacon
1Hz
6.8
8.6
mA
Table. 1 LPSB3000 and LPAV3000 Current Draw