800 SERIES

17A-03-AV

2

11/08

Registered Company: Thorn Security Ltd.

Registered Office: Dunhams Lane

Letchworth Garden City

Hertfordshire

SG6 1BE

EQUIPMENT:

PUBLICATION:

ISSUE No. & DATE:

AV SERIES OF LOOP POWERED SOUNDERS

AND SOUNDER-BEACONS

INSTALLATION AND COMMISSIONING INSTRUCTIONS

SOUNDER

SOUNDER-BEACON

Fig. 1

PROGRAMMING

PORT

LOCKING

DEVICE

FITS

HERE

1.

TECHNICAL SPECIFICATION

System Compatibility:

Use only with ZX/MX
Fire Alarm Controllers

Environment

:

Models for indoor use only

Temperature

:

Operating:

-20°C to +70°C

Storage:

-25°C to +70°C

Humidity

:

Up to 95% (non-condensing)

Dimensions

:

Height:

36.5mm

Diameter:

115mm

Weight

:

Sounder only:

160g

Sounder/Beacon:

190g

Mounting Requirement

s

: Surface mount

The flat surface mounting flange is supplied with the

base. The DAB3-4 mounting flange must be ordered
separately.

The mounting flanges have to four drill positions for

mounting holes at 50mm, 60mm, 70mm and 80mm.

The sounder/ sounder beacon body clips onto the mounting

flange.

Electrical Characteristics:

Addressable Loop Voltage:

20 - 40Vdc

DC Loop Loading

Quiescent:

350

μ

A

Alarm:

See Tables 1 & 2

EMC

:

The base complies with the following:

Product family standard EN50130-4 in respect of
Conducted Disturbances, Radiated Immunity,
Electrostatic Discharge, Fast Transients and Slow High
Energy

EN61000-6-3 for Emissions

Low/ Mid Low

Mid High/High

Sound Output

60/70

80/90

dB

Sounder Only

2.6

4.4

mA

Sounder and Beacon 
0.5Hz

5.7

7.5

mA

Sounder and Beacon 
1Hz

6.8

8.6

mA

Table. 1 LPSB3000 and LPAV3000 Current Draw

Summary of Contents for 800 Series

Page 1: ...r only 160g Sounder Beacon 190g Mounting Requirements Surface mount The flat surface mounting flange is supplied with the base The DAB3 4 mounting flange must be ordered separately The mounting flanges have to four drill positions for mounting holes at 50mm 60mm 70mm and 80mm The sounder sounder beacon body clips onto the mounting flange Electrical Characteristics Addressable Loop Voltage 20 40Vdc...

Page 2: ...sable loop wiring through the mounting flange cable entry c Secure the mounting flange to a flat surface d Feed the addressable loop wiring through the AV base cable entry then clip the sounder base to the mounting flange e Wire the AV base as shown in Fig 7 ensuring correct polarity f Fit the locking device supplied to the base pressing it in until it is fully seated See Fig 4 g Fit the address f...

Page 3: ...e missing C Tick mark on the product identification label on the underside of the tool see Fig 5 Fig 4 Fitting Locking Device LOCKING DEVICE FOR MX ADDRESSABLE DEVICES USES TYCO MX DIGITAL PROTOCOL 801AP 516 800 918 MX SERVICE TOOL Tyco Safety Products N1156 DUNHAMS LANE LETCHWORTH SG6 1BE UK S N FF FF FF FF Fig 5 C TICK MARK The AV Sounder Beacons use 2 consecutive addresses on the MX addressable...

Page 4: ...A 03 AV 2 11 08 PAGE 4 of 4 JM pl 20th November 2008 MX CONTROLLER L L1 L2 R L L1 L2 R L L1 L2 R L L1 L2 R L L1 L2 LPSB3000 LPAV3000 BASE 5BI BASE 5B BASE 5B BASE 5B BASE M M M M M Fig 7 AV Simplified Wiring Diagram ...

Reviews: