background image

Type EA-1 PROTECTOSPRAY 

Directional Spray Nozzles, Automatic, 

Medium Velocity

Page 1 of 6 

AUGUST 2018 

TFP800

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Type EA-1 PROTECTO-

SPRAY Directional Spray Nozzles are 

automatic (frangible bulb) directional 

spray nozzles designed for use in water 

spray fixed systems for fire protection 

applications. They are external deflec-

tor-type nozzles that discharge a uni-

formly filled cone of medium velocity 

water droplets.
The Type EA-1 PROTECTOSPRAY 

Directional Spray Nozzles are effective 

in covering exposed vertical, horizontal, 

curved, and irregular shaped surfaces 

in a cooling spray to prevent excessive 

absorption of heat from an external 

fire and possible structural damage or 

spread of fire to the protected equip-

ment. However, use of an automatic 

nozzle requires consideration of the 

response time of the thermal element.
The Type EA-1 PROTECTOSPRAY 

Directional Spray Nozzles are also 

especially effective for area cover-

age and are sometimes used in lieu of 

standard sprinklers where directional 

spray is considered more appropri-

ate. In some applications, depending 

on water design density requirements, 

the Type EA-1 Nozzles are also used for 

fire control or extinguishment.
The Type EA-1 PROTECTOSPRAY 

Directional Spray Nozzles are available 

in three orifice sizes and a wide variety 

of spray angles (included angle of dis-

charge), as well as temperature ratings 

to provide versatility in system design.
It is recommended that the end user be 

consulted with respect to the suitabil-

ity of the materials of construction and 

finish for any given corrosive environ-

ment. The effects of ambient tempera-

ture, concentration of chemicals, and 

gas/chemical velocity should be con-

sidered, at a minimum, along with the 

corrosive nature to which the sprinklers 

may be exposed.
The Type EA-1 PROTECTOSPRAY 

Directional Spray Nozzle is a re-desig-

nation for the Gem Type EA-1.

NOTICE

The Type EA-1 PROTECTOSPRAY 

Directional Spray Nozzles described 

herein must be installed and maintained 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associa-

tion, in addition to the standards of any 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.
The design of individual water spray 

fixed systems can vary considerably, 

depending on the characteristics and 

nature of the hazard, the basic purpose 

of the spraying system, the configura-

tion of the hazard, and wind/draft con-

ditions. Because of these variations, 

as well as the wide range of available 

nozzle spray characteristics, the design 

of water spray fixed systems for fire 

protection must only be performed by 

experienced designers who thoroughly 

understand the limitations as well as 

capabilities of such systems.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Technical 

Data

Approvals

UL and C-UL Listed 

FM Approved

Maximum Working Pressure

175 psi (12,1 bar) 

(Also refer to Figure 2, Note 2)

Discharge Coefficient

Refer to Table A

Spray Angles

Refer to Table B

Temperature Rating

Refer to Table C

Finish and Material

Refer to Table D

Thread Connection

1/2 in. NPT

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Bushing (K=1.4 & K=2.8)  . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Bulb (11 mm dia.)  . . . . . . . . . . . . . . . . . . . . Glass

Bulb Seats . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Spacer . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Spring Plates . . . . . . . . . . . . . . . . . . . . . .  Inconel

Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . .  Copper

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the nozzle to acti-

vate and water to flow.

Summary of Contents for EA-1 PROTECTOSPRAY

Page 1: ...h respect to the suitabil ity of the materials of construction and finish for any given corrosive environ ment The effects of ambient tempera ture concentration of chemicals and gas chemical velocity should be con sidered at a minimum along with the corrosive nature to which the sprinklers may be exposed The Type EA 1 PROTECTOSPRAY Directional Spray Nozzle is a re desig nation for the Gem Type EA ...

Page 2: ...from the nozzle tip to the plane of protection is 2 ft 0 6 m or less the Design Spray Profile is the same as the nominal spray angles of 65 to 140 degrees Heat Sensitivity Because the Type EA 1 PROTEC TOSPRAY Directional Spray Nozzles are automatic nozzles they must be located with consideration of their ability to detect abnormal tempera ture increases due to fire Therefore it is recommended that...

Page 3: ... After wrench tightening the nozzle loosen the wrench jaws before removing the wrench After installation inspect the nozzle wrenching area and frame arms and retouch repair the wax coating wher ever the coating has been damaged and bare metal is exposed Retouch the wax coating on the wrenching area by gently applying a heated 1 8 in diameter steel rod to the areas of wax that have been damaged smo...

Page 4: ...inches Maximum Axial Distance For 95 Spray Angle In Feet and inches Maximum Axial Distance For 110 Spray Angle In Feet and inches Fixed Angle Orifice Size Fixed Angle Orifice Size Fixed Angle Orifice Size Fixed Angle Orifice Size 1 4 in 3 8 in 1 2 in 1 4 in 3 8 in 1 2 in 1 4 in 3 8 in 1 2 in 1 4 in 3 8 in 1 2 in 0 11 9 14 0 15 0 0 10 0 13 0 14 0 0 7 0 10 9 12 3 0 6 0 10 0 11 0 30 10 0 12 3 13 0 30...

Page 5: ...0 0 9 1 0 1 2 180 0 8 0 8 1 1 Maximum Axial Distance For 125 Spray Angle In Meters Maximum Axial Distance For 140 Spray Angle In Meters Maximum Axial Distance For 160 Spray Angle In Meters Maximum Axial Distance For 180 Spray Angle In Meters Fixed Angle Orifice Size Fixed Angle Orifice Size Fixed Angle Orifice Size Fixed Angle Orifice Size 1 4 in 3 8 in 1 2 in 1 4 in 3 8 in 1 2 in 1 4 in 3 8 in 1 ...

Page 6: ...part number P N Contact your local distributor for availability Type EA 1 PROTECTOSPRAY Directional Spray Nozzle Specify 1 4 2 8 or 5 6 K factor orifice temperature rating finish coating and material degree spray angle P N from Table G Sprinkler Wrench Specify W Type 11 Sprinkler Wrench P N 56 452 1 001 FINISH and MATERIAL 1 NATURAL FINISH BRONZE 6 WAX COATED BRONZE 135 F to 175 F ONLY 7 LEAD COAT...