background image

IMP117-10

www.ueonline.com

GENERAL

BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR 

COMPATIBILITY BETWEEN THE PROCESS MEDIA AND THE SENSOR 

AND WETTED PARTS.

MISuSE OF THIS PRODuCT MAY CAuSE ExPLOSION AND PERSONAL 

INjuRY.  THESE INSTRuCTIONS MuST BE THOROuGHLY READ AND 

uNDERSTOOD BEFORE uNIT IS INSTALLED.

THIS  EQuIPMENT  IS  SuITABLE  FOR  CLASS  I,  DIVISION  2, 

GROuPS A,B,C,D; CLASS II, DIVISION 2, GROuPS F AND G; CLASS III; 

OR NON-HAZARDOuS LOCATIONS ONLY.

The 117 series pressure and differential pressure switch utilizes a bellows or 

diaphragm sensor to detect a pressure change. The response, at a pre-deter-

mined set point, actuates a SPDT or DPDT snap-acting switch, converting the 

pressure signal into an electrical signal. Control set point may be varied by 

turning the internal adjustment hex.  (see adjustment-Part II.)

PROOF PRESSuRE* LIMITS  STATED IN THE LITERATuRE  AND ON 

NAMEPLATES MuST NEVER BE ExCEEDED, EVEN BY SuRGES IN THE 

SYSTEM.  OCCASIONAL OPERATION OF uNIT uP TO PROOF PRES-

SuRE IS ACCEPTABLE (E.G., START-uP, TESTING). CONTINuOuS OPERATION 

SHOuLD NOT ExCEED THE DESIGNATED OVER RANGE** OR WORKING PRES-

SuRE*** RANGE.
*Proof Pressure - the maximum pressure to which a pressure sensor may be 

occasionally subjected, which causes no permanent damage (e.g., start-up, 

testing).  The unit may require re-gapping.
**Over Range Pressure - the maximum pressure to which a pressure sensor 

may be continuously subjected without causing damage and maintaining set 

point repeatability.

***Working Pressure Range - the pressure range within which two opposing 

sensors can be safely operated and still maintain set point repeatability.

WARNING:  ExPLOSION  HAZARD.  THESE  PRODuCTS  DO  NOT  HAVE 

ANY  FIELD  REPLACEABLE  PARTS.  ANY  SuBSTITuTION  OF  COMPO-

NENTS MAY IMPAIR SuITABILITY FOR CLASS I, DIVISION 2.

Please refer to product bulletin for product specifications.  Product bulletins 

may be found at www.ueonline.com.

Date code format on nameplate is “YYWW” for year and week.

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

Part I - Installation

 

Tools Needed

Adjustable Wrench

Screwdriver

Hammer (for alternate wire knockouts)

MouNTING

WARNING: ExPLOSION HAZARD - DO NOT DISCONNECT EQuIPMENT 

uNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN 

TO BE NON-HAZARDOuS.

INSTALL uNIT WHERE SHOCK, VIBRATION AND TEMPERATuRE FLuC-

TuATIONS ARE MINIMAL. MOuNT uNIT SO THAT MOISTuRE IS PRE-

VENTED  FROM  ENTERING  THE  ENCLOSuRE.    IF  uNIT  IS   BEING 

INSTALLED WHERE HEAVY CONDENSATION IS ExPECTED, VERTICAL MOuNTING 

(PRESSuRE CONNECTION DOWN) IS REQuIRED. DO NOT MOuNT IN AMBIENT 

TEMPERATuRES ExCEEDING PuBLISHED LIMITS.

ALWAYS HOLD A WRENCH ON THE PRESSuRE HOuSING HEx WHEN 

MOuNTING uNIT. DO NOT TIGHTEN BY TuRNING ENCLOSuRE. THIS 

WILL  DAMAGE  SENSOR  AND  WEAKEN  SOLDERED  OR  WELDED 

jOINTS.

Controls may be mounted and operated in any position. They may be sur-

face mounted via the two mounting ears on either side of the enclosure, or 

directly to a rigid pipe by using the pressure connection. Low pressure and 

differential pressure units, models 520-535, 540-548, are also available with 

an optional surface mounting bracket. Should the control be installed where 

condensation is expected, vertical mounting is recommended as a means of 

keeping water away from switch terminals.

WIRING

DISCONNECT  ALL  SuPPLY  CIRCuITS  BEFORE  WIRING  uNIT.  WIRE 

uNITS ACCORDING TO NATIONAL AND LOCAL ELECTRICAL CODES. 

MAxIMuM  RECOMMENDED  WIRE  SIZE  IS  14  AWG.    THE  RECOM-

MENDED TIGHTENING TORQuE FOR FIELD WIRING TERMINALS IS 7 
TO 17 IN-LBS. uSE 75

°

C RATED COPPER CONDuCTORS ONLY.

ELECTRICAL RATINGS STATED IN LITERATuRE AND ON NAMEPLATES 

MuST  NOT  BE  ExCEEDED.    OVERLOAD  ON  A  SWITCH  CAN  CAuSE 

FAILuRE ON THE FIRST CYCLE. 

Remove  the  two  screws  retaining  the cover  and  cover gasket. A 1/2” NPT 

conduit connection is provided on the left hand side of the enclosure. Two 

cast-in  7/8”  diameter  knockouts  for  electrical  conduit  are  located  on  the 

side and back of enclosure (see dimensional drawings). These can easily be 

knocked out by placing a blade of a screwdriver in groove and tapping sharp-

ly with a hammer. The terminal block terminals are clearly labeled “Common”, 

“Normally  Open”  and  “Normally  Closed”.  For  units  supplied  with  DPDT,  all 

terminals are labeled and the following color code applies.

117 Series

Type H117

(Pressure Switch)

Type H117K

(Differential Pressure Switch)

IMP117-10

U N I T E D   E L E C T R I C 

C O N T R O L S

Installation and Maintenance 

Instructions

Summary of Contents for 117 Series

Page 1: ...ustable Wrench Screwdriver Hammer for alternate wire knockouts Mounting WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS Install unit where shock vibration and temperature fluc tuations are minimal mount unit so that moisture is pre vented from entering the enclosure IF UNIT IS BEING installed where heavy condensation ...

Page 2: ...6 HEX HEAD SCREW INSTALLED IN THE 1 4 HEX PLUNGER THE LENGTH OF THIS ASSEMBLY IS ADJUSTED AT OUR FACTORY AND IS CRITICAL TO THE FUNCTION OF THE CONTROL DURING NORMAL ADJUSTMENT THESE COMPONENTS SHOULD NOT BE DISTURBED Do not adjust unless re gapping is necessary For set point adjustments and recalibration connect control to a calibrated pressure source Remove cover Loosen Phillips screw adjustment...

Page 3: ...TH COVER 101 6mm CLEARANCE FOR 1 4 6 35mm SCREW 2 MT G HOLES 895 22 7mm DIA KNOCK OUT 2 PLACES 2 75 69 9mm KNOCK OUT 2 75 ADJUSTMENT SCREW Dimension A Models Inches mm NPT Pressure 171 174 7 63 193 8 1 2 183 186 483 486 7 56 192 0 1 2 188 189 488 489 6 63 168 4 1 2 190 194 490 494 6 63 168 4 1 2 218 6 56 166 6 1 4 358 376 7 00 177 8 1 4 520 525 8 44 214 4 1 2 530 535 8 00 203 2 1 2 560 564 6 63 16...

Page 4: ...or critical appli cations where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceed ed Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recom mended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARR...

Reviews: