Safety and Warning Information 

 

Connect the DIN Rail, via the Model 

2A09 End Clamp, to Protective Earth 

(PE) ground with low impedance.

 

ATEX Specific Conditions of Use 

Modules shall be installed in an enclosure which 

maintains an ingress protection rating of IP54 and 

meets the enclosure requirements of EN60079-0 and 

EN60079-15.  The EOTec modules shall be installed 

in DIN rail with DIN end clamps mounted on both 

sides of the module set.  The DIN rail must be 

connected to Protective Earth in order to provide 

modules with a Protective Earth connection.  Do not 

disconnect equipment connections or modules when 

energized. 

 

Ultra Electronics 

N

UCLEAR SENSORS & PROCESS INSTRUMENATION 

707 Jeffery Way, PO Box 300 

Round Rock, TX 78680-300 USA 
Toll Free:   800-880-9333            

Telephone:  +1 512-434-2850 

Fax:  +1 512-434-2901 
Email:  fiberop@ultra-nspi.com 

www.ultra-nspi.com 
Ultra Electronics, Nuclear sensors & Process 

Instrumentation is a business name of Weed 

Instrument Co., Inc

 

Important Notice

  -  Before utilizing the product, the user should 

determine the suitability of the product for its intended use.  The 

user assumes all risk and liability in connection with such use.  

ULTRA ELECTRONICS’ WRITTEN WARRANTY FOR THE 

PRODUCT IS MADE IN LIEU OF ALL OTHER WARRANTIES, 

EXPRESSED OR IMPLIED WARRANTIES OF 

MERCHANTABILITY AND FITNESS FOR A PARTICULAR 

PURPOSE.  The user's exclusive remedy  for breach of Ultra 

Electronics' written warranty shall be the repair or replacement of 

such quantity of product which is proven to be defective.  In no 

case shall Ultra Electronics be liable for any special, incidental, 

or consequential damages based upon breach of contract, 

negligence, strict liability or other legal theory. 

 

 

Approval Agency Controlled Document 

No changes authorized without prior agency approval

  

Publication Number: 

           RM0900207  Rev.  0 

EOTec MX Multiplexer Models 

MX420-OP2 / MX420-OP4 

2 & 4 Port 4-20mA Output Modules 

 

 

Installation Instructions 

Original Instructions 

 

 

Nuclear Sensors & 

Process Instrumentation 

 

 

POWER:

  The MX420-OP modules obtain power from 

the 10+2 interconnection bus.  Power originates from 

an MX Base Module (see specification section). 

4 to 20mA OUTPUT:

  The Port-1 I/O terminal block is 

at the top-front of the unit. Port-2 is directly below it. 

On a 4 port model, Port-3 is at the bottom-front of the 

unit with Port-4 directly below and behind it.   Screw 

terminal blocks are numbered from left-to-right as 

follows: 

 

 

NOTE:

  Internally, this module’s negative (-) input 

terminals are connected to the modules 

interconnection bus negative (-) terminal (circuit 

common). 

 

Connections 

 

MX 4-20mA Output Modules 

 

For use ONLY with the  

EOTec MX Multiplexer Line 

 