background image

Input-Output Device

 FD7203

TYPE

1 input / 1 output

Instruction Manual 09-7203-09-19

1293-CPD-0282

General Description

The Input-Output device FD7203 (fig.1) is designated to produce and send an electrical signal

to various devices in case of occured events and recording external impacts, typical for a fire

condition events.The device is compatible with addressable fire control panels IFS7002,

supplementing the possibilities of the addressable systems of series IFS7000.

The device consists of a printed board with elements, 

mounted on a plastic base and closed by a cover .The 

base has an implemented terminal bus (pos.7 and pos.6, 

fig.1) through which cabels connect the addressable loop, 

the power supply and etc.

Communication between Control Panel IFS7002 and the 

input-output device is realized by means of the 

addressable loop through a specialized protocol for data

exchanging UniTALK .

Two LED indicators are built-inon the device PCB (pos.1 

fig.1), illuminated in yellow  and red (pos2.fig.1) light,

providing device status information.

1

2

3

4

5

6

7

Fig.1 - Picture of input/output module

Теchnical Data

Аddressable loop:

 

- supply voltage                   

 

 

   

 

             (15÷30)Vdc

 

- current consumption in duty mode  

 

 

             < 350µA

 

- current consuption in alarm state   

 

 

             (2±1)mA

Input:   

 

                                                        

                           1 pc.

 

- “Fault condition” - interruption 

 

 

 

              R

line

>25kΩ

 

- “Fault condition” - short circuit 

       

 

                            R

line

≤2,2kΩ

 

- “Duty mode” range   

 

 

 

                            5,7kΩ≤R

line

<15kΩ

 

- “Activated input” range (fig.3b) 

  

 

                            2,2kΩ<R

line

<5,7kΩ 

 

- “Activated input” - input does not check for short  

 

0kΩ<R

line

<5,7kΩ

 

  circuit (fig.3a)

Output: Depending on the configuration and the power supply                1 pc.

 

(Relay or monitored)

• Relay

 

- type   

 

 

                                       

             potential free,

 

 

 

 

 

 

 

                                         switching functions

 

- electrical specifications 

 

 

 

 

            30V DC /1A, 125V AC/0,5A

or

• Monitored

 

- type    

 

                                                 

 

            potential

 

- electrical specification   

     

                          

            (12÷30)Vdc

 

- peak activation current                         

           

            400mA

Degree of protection:  

 

 

 

 

 

            

IP 

30 

Operating temperature range 

 

                            

            from minus 5°С to 40°С

Relative humidity resiatance (no condensation)   

 

            (95±3) % at 40°C

Dimensions   

 

 

                                        

            (90x66x22) mm

Weight 

 

 

 

                                   

 

            0.075 kg

09/09.19

Manufacturer: UniPOS Ltd., 47 San Stefano Street, Pleven 5800, Bulgaria,

 http://www.unipos-bg.com

Summary of Contents for FD7203

Page 1: ... built inon the device PCB pos 1 fig 1 illuminated in yellow and red pos2 fig 1 light providing device status information 1 2 3 4 5 6 7 Fig 1 Picture of input output module Теchnical Data Аddressable loop supply voltage 15 30 Vdc current consumption in duty mode 350µA current consuption in alarm state 2 1 mA Input 1 pc Fault condition interruption Rline 25kΩ Fault condition short circuit Rline 2 2...

Page 2: ...cted in according to step 3A then the module will enter in Duty mode In order to learn the new configuration it is required to press and hold for 5 second the tactile button fig 3 step 5 In case that operation is successfully done the module red LED indication will be activated in the left site of the module PCB fig 3 step 5 the module enter in service system mode The module will not communicate w...

Page 3: ...Фиг 3 Manufacturer UniPOS Ltd 47 San Stefano Street Pleven 5800 Bulgaria http www unipos bg com 09 09 19 ...

Page 4: ... circuit switched OFF fig 2 and wires are connected in according to fig 3B and 3D the panel does not check monitor for fault short circuit Important note Activation of the input is done through non potential contact dry contact 3 1 3 Output and external power supply Terminals from 9 to15 depends from configurating of the type output fig 2 and fig 3A or 3B or 3C or 3D 3 1 3 1 Output configured as m...

Page 5: ...01 Out 13 5 1 4 1 16 28V does not check for short circuit of the input and managing of external device through reley with non potential contacts 3 2 2 Using as a monitored output or monitored technical common input 1 2 3 4 5 6 7 8 E E 10kΩ N NO O 10kΩ IN Address Loop 9 10 11 12 5 6kΩ 1N4001 Out 13 5 1 4 1 16 28V check for short circuit of the input and managing of external device through monitored...

Page 6: ...bserved The manufacturer does not bear warranty liabilities for damages caused through accidental mechanical damage misuse adaptation or modification after production Accessory installation of a modular box cabinet For the In Out module 7203 IO type is available accessory a modular box consisting of the module cabinet The accessory is used to bind to cover the cables to the connection terminals Un...

Reviews: