background image

Unitary Products Group

ACCESSORY KIT INSTALLATION INSTRUCTIONS

HIGH ALTITUDE APPLICATION CONVERSION 

MID-EFFICIENCY SINGLE-STAGE INDUCED COMBUSTION FURNACES

MODELS: P*HU/G8T-UH/L8T-UH/FL8 UPFLOW / HORIZONTAL

P*DN/G8T-DN/L8T-DN DOWNFLOW

035-14446-000 Rev. B  (1002)

GENERAL

This instruction is intended for the conversion of new equip-
ment only, for operation at altitudes greater than 4,500 ft.
above sea level. Follow the basic unit installation instruction
for all other aspects of the installation.

All units are equipped to operate up to 4,500 feet above sea
level without a high altitude kit. Installations above 2,000 ft.
must be field derated as required by the National Fuel Gas
Code, ANSI Z223.1 (latest edition), or in Canada, CAN/CGA
B149.1 or .2 and all other applicable local codes and utility
requirements.

This instruction provides the necessary information to select
and install both the proper pressure switch and orifice for
your specific application. Data is provided for both natural
and propane (LP) gases. This high altitude pressure switch
and accessory includes a special switch and other items as
detailed below.

 

.

* May be any numeral 0-9.

PRESSURE SWITCH

For installations below 4500 ft., refer to furnace installation
instructions to properly derate applications which do not
require a pressure switch change. For  applications above
4,500 feet, a pressure switch change is required to provide
safe and reliable operation. Table 1 indicates the correct
pressure switch accessory for each unit model applied.

This conversion kit is to be installed by a qualified service agency in accordance with the manufacturer’s instructions
and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is
not followed exactly, a fire, an explosion or production of carbon monoxide may result causing property damage, per-
sonal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installa-
tion is not proper and complete until the operation of the converted appliance is checked as specified in the
manufacturer’s instructions supplied with the kit. 

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

Installation must be made in accordance with American National Standard National Fuel Gas Code, ANSI Z223.1-lat-
est edition, unless superseded by local codes. For Canadian installations, the conversion shall be carried out in accor-
dance with the requirements of the Provincial authorities having jurisdiction and in accordance with the CAN1-B149.1
and .2 installation codes.

The manufacturer accepts no responsibility for malfunctions due to improper conversions.

Improper installation, adjustment service, or mainte-
nance can cause injury or property damage; there-
fore, only a qualified installer or qualified service
personnel should perform this conversion.

COMMON PARTS

Description

Part Number

Quantity

Conversion Label

035-11635-000

1

Install. Instruction.

035-14446-000

1

PRESSURE SWITCH

Accessory Kit

Switch Part Number

Pressure Setting

1PS0301

024-27669-00*

.35 IWG

1PS0302

024-27627-00*

.42 IWG

1PS0311

024-27626-00*

.40 IWG

1PS0312

024-27628-00*

.45 IWG

Do not adjust the original pressure switch to allow
operation at high altitude. Unsafe operation will
result.

Table 1: 

HIGH ALTITUDE PRESSURE SWITCH USAGE

INPUT
(MBH)

OUTPUT

(MBH)

ACCESSORY 

PART NUMBER

Upflow / Horizontal & Downflow Models

40

32

1PS0301

57

46

1PS0301

80

64

1PS0301

100

80

1PS0311

115

92

1PS0311

130

104

1PS0311

160

130

1PS0301