background image

 

P/N 3101085-

EN • REV 006 • ISS 03JUL18 

 

1 / 2 

 

FX-NAC Analog NAC Module 
Installation Sheet 

Operation 

The module is an analog addressable device used to connect a 
supervised output circuit to a signal riser. The output wiring is 
monitored for open and short circuits. A short circuit causes the 
module to inhibit the activation of the audible/visual signal circuit so the 
riser is not connected to the wiring fault. Upon command from the 
control panel, the module connects the output circuit to the riser input. 
The output circuit energizes a riser to operate polarized audible and 
visual signals. The module can be used for connection of a Class A or 
Class B (with EOL) output notification appliance circuit (NAC). 

The device address is set using the two rotary switches located on the 
front of the module. One device address is required. 

The module is configured to operate as a Genesis 
Audible/Visual/Silence device type from the factory. The module can 
also be configured for other device types through front panel 
programming or the configuration utility. Refer to the applicable control 
panel technical reference manual for a list of available device types. 

Genesis Audible/Visual/Silence:

 Used with Genesis and Enhanced 

Integrity horns and strobes. Genesis and Enhanced Integrity 
appliances maintain synchronization per UL 1971. For Genesis 
devices, this configuration allows connected horns to be silenced while 
strobes on the same two-wire circuit continue to flash until the panel is 
reset. 

 

LED operation 

The module provides a bicolor LED that shows its status. 

Normal: Green LED flashes 

Active: Red LED flashes 

Installation 

Install and wire this device in accordance with applicable national and 
local codes, ordinances, and regulations. 

WARNINGS

 

• 

This module will not operate without electrical power. As fires 
frequently cause power interruption, you should discuss further 
safeguards with your local fire protection specialist. 

Note: 

The module is shipped from the factory as an assembled unit; it 

contains no user-serviceable parts and should not be disassembled. 

To install the module: 

1.  Verify that all field wiring is free of opens, shorts, and ground 

faults. 

2.  Make all wiring connections as 

shown in “Wiring” and Figure 3. 

3.  Set the module address. Refer to the panel technical reference 

manual for a list of valid addresses. 

Use a screwdriver to adjust the two rotary switches on the front of 
the module. Set the TENS rotary switch (0 through 12) for the 10s 
and 100s digit and the ONES rotary switch for the 0 through 9 
digit. For example: device address 21, set TENS rotary switch to 2 
and set the ONES rotary switch to 1 (see Figure 1). 

4.  Mount the module on the electrical box using screws provided with 

the electrical box. 

5.  Mount the wall plate on the module using #4-24 × 1/2 in. (13 mm) 

self-tapping screws. 

Figure 1: Module address 

 

Figure 2: Module installation 

 

Wiring 

Wire the device as shown in Figure 3. Be sure to observe the polarity 
of the wires. 

Insert

screwdriver

here

Screw

4-24

screws

Module

Wall plate

Compatible

electrical box