M A N U A L 

 

Thyristor - Drive 

 1 Quadranten  

Classic P3  

60 … 150 A 

      

 

Industrie Elektronik 

G   m    b    H 

 

 

Hans-Paul-Kaysser-Straße 1 

 

 

71397 Leutenbach – Nellmersbach 

 

 

 

 

Issue   / 

Revision 

Tel.: 07195 / 92 83 – 0 

Fax: 07195 / 92 83 – 129 

info@unitek-online.de

 

www.unitek-online.de 

 

01/2018 

V  01 

 

 

 

 

Summary of Contents for P3 60

Page 1: ...1 Quadranten Classic P3 60 150 A Industrie Elektronik G m b H Hans Paul Kaysser Stra e 1 71397 Leutenbach Nellmersbach Issue Revision Tel 07195 92 83 0 Fax 07195 92 83 129 info unitek online de www un...

Page 2: ...faces 6 3 Mechanical Installation 7 3 1 Dimension 7 3 2 Dimension 8 4 Electrical installation 9 4 1 Connection 9 4 2 Connection diagram 11 4 3 CE Advices 12 4 4 Motor connection 13 4 5 Actual value co...

Page 3: ...of power flow in electrical power systems Protection rating IP00 Control and power connections can voltage lead works without the drive Measured before disassembly voltage 2 2 Standards and guideline...

Page 4: ...ealth and safety guidelines Adjustments and programming should only be carried out by suitable trained personnel with knowledge in electronic drives and their software should only be carried out in ac...

Page 5: ...e control electronics The distance of air gaps and leakage paths adhere to the VDE standards 8mm Components fully insulated thyristor modules comfortably over dimensioned only components customary in...

Page 6: ...4 2 Armature chokes are necessary only for special applications Cooling self cooling fan fan Dimensions wxhxd mm 290x210x170 290x210x170 290x210x170 P3 500 550 x Power connection 500 550V Auxiliary vo...

Page 7: ...loop circuit Control precision 2 Control range 1 50 Speed control loop circuit with REG Control precision without actual value error 0 1 Control range 1 300 2 6 Interfaces Function Connector no 24Volt...

Page 8: ...Current control loop RVI LED displays Enable Current control loop enable green enabled Triggering enable Z green enabled Current command value Current control loop RVI RVI green control active The lum...

Page 9: ...Mechanical Installation Classic P3 60 150 A 01 2018 V1 8 Dimension 3 2 Dimension Manuals Zeichnungen E P3 M1352...

Page 10: ...e plate Current consumption 0 1A Fuse F1 0 8A 5x20 Manuals Zeichnungen P3 A054 Hilfssp The auxiliary voltage and the field supply are both connected across the plug in terminal X5 The phase position o...

Page 11: ...ltage steadiness isolating transformers must be used The transformer performance is determined by the permanent current and the secondary voltage Fast acting fuses must be installed between the transf...

Page 12: ...11 01 2018 V1 Classic P3 60 150 A Electrical installation Connection diagram 4 2 Connection diagram Manuals Zeichnungen E P3 A021...

Page 13: ...ound using a 10mm wire The motor housing must be connected to ground using a 10mm wire The device ground X1 8 must be connected to the mounting plate using a 2 5mm wire Device PE screw must be connect...

Page 14: ...e the fuse to fail RNB resistors brake resistors in case of power supply failure are to be connected in parallel directly to the motor armature without isolating the motor from the control unit Zeichn...

Page 15: ...est results can be achieved through the use of dc tacho generators Three phase tacho generators with rotor position evaluation or digital actual value encoders as well as ac or three phase tachos with...

Page 16: ...armature voltage can be used as actual value signal The actual value lines must be protected by two fuses of 0 1A 500V installed directly in the armature voltage For armature voltages superior to 180V...

Page 17: ...st armature circuit inductance For a higher inductance the proportional amplification can be changed via the contacts 1 and 2 and the integral time constant can be changed via the contacts 3 and 4 Osc...

Page 18: ...17 01 2018 V1 Classic P3 60 150 A Adjustment Circuit diagram 5 2 Circuit diagram Manuals Zeichnungen E P3 S074 1...

Page 19: ...s of measuring instruments which indicate mean values or by instruments which indicate actual values When measuring the dc current with these different measuring instruments there will be measuring er...

Page 20: ...tch S5 to position 6 Adjust the potentiometer Imax1 to left full scale Adjust the potentiometer Imax2 to approx 10 Potentiometer Xp to 50 Potentiometer ID 100 Potentiometer IxR left full scale Potenti...

Page 21: ...witch S5 large centrifugal mass high adjusted value small centrifugal mass low adjusted value With the command value set to 10 speed increase the amplification by turning the potentiometer Xp clockwis...

Page 22: ...e Imax1 extern Voltage V no function Current nom value Imax2 extern Voltage V Speed controll settings REGxx Switches Tacho adjustment S9 Position REG5 Schotax 1 P term S4 Position I term S5 Position D...

Page 23: ...OFF Measuring value Armature voltage max V Armature current peak A Armature current steady A Tachometer voltage max V Acceleration X4 16 V ms Integrator X4 14 V ms Motor data Identification name plate...

Page 24: ...value Tacho armature voltage Values of the tacho switch S9 too low Command value too high For armature voltage control Field current too low Fuses armature voltage feedback activated Motor runs unste...

Page 25: ...buyer or a third party non observance of the manual which is included in all consignments non observance of the electrical standards and regulations improper maintenance acts of nature All further cl...