Description 

The Genesis WG4 Outdoor Horn is a life safety notification 
appliance designed for indoor or outdoor use on ceilings or 
walls. See Table 1 for a list of models and Table 2 for a list of 
accessories.  

For surface mount applications, mount the WG4 onto a 
Model 449 electrical box using the gasket shipped with the 
appliance. For flush mount applications where the mounting 
surface is flush with the surface of the wall or ceiling, use the 
WG4GSKT gasket kit. 

Note that you need a Model 449 electrical box for waterproof 
applications, or a standard mount 4 in. square box for all other 
applications. 

The horn includes field-configurable jumper options that allow 
you to set the horn pattern to temporal or continuous, and the 
horn volume to low or high. 

Table 1: Models 

Number Description 

WG4WF-H  

Outdoor rated wall/ceiling horn, white with FIRE 
marking  

WG4WN-H 

Outdoor rated wall/ceiling horn, white without marking  

WG4RF-H  

Outdoor rated wall/ceiling horn, red with FIRE marking 

WG4RN-H 

Outdoor rated wall/ceiling horn, red without marking  

Table 2: Accessories 

Number Description 

WG4WTS [1] 

Outdoor-rated surface skirt, white, for Genesis WG4 
horn or horn-strobe 

WG4RTS [1] 

Outdoor-rated surface skirt, red, for Genesis WG4 
horn or horn-strobe 

WG4GSKT [2]  Appliance replacement gasket, flush mount 

[1] The trim skirt is outdoor-rated when used with the Model 449 
electrical box. 
[2] Not compatible with the trim skirts. 

To synchronize horn operation, you must install a separate 
synchronization source. See Table 3. When connecting the 
horn to a listed control panel, verify synchronization operation 
on the compatibility list for the corresponding panel. 

Table 3: Compatible synchronization source models  

Description Number 

Auto-sync output 
module 

SIGA-CC1S   SIGA-MCC1S 
GSA-CC1S   GSA-MCC1S 
SIGA-CC2A   SIGA-MCC2A 

Genesis signal master - 
remote mount 

ADTG1M-RM  

MG1M-RM 

EG1M-RM   XLSG1M-RM 
G1M-RM 

  ZG1M-RM 

Booster or auxiliary 
power supply 

APS10* 

  EBPS10* 

 

APS6* 

  EBPS6* 

BPS10* 

  MIRBPS10* 

BPS6* 

  MIRBPS6* 

EAPS10* 

  XLS-BPS10* 

EAPS6* 

  XLS-BPS 

 

* Represents any number of additional characters 

Installation 

Install this device in accordance with applicable requirements 
and in accordance with the local authorities having jurisdiction. 

WARNING: 

Electrocution hazard. To avoid personal injury or 

death from electrocution, remove all sources of power and 
allow stored energy to discharge before installing or removing 
equipment. 

 

Notes  

• 

Electrical supervision requires that you break the wire run 
at each terminal. Do not loop wires around the terminals.

 

• 

Mount the Genesis WG4 Outdoor Horn horizontally or 
vertically

 on either the wall or ceiling

; place the electrical 

box accordingly.  See Figure 1. 

Summary of Contents for Edwards Genesis WG4 Series

Page 1: ...orn or horn strobe WG4RTS 1 Outdoor rated surface skirt red for Genesis WG4 horn or horn strobe WG4GSKT 2 Appliance replacement gasket flush mount 1 The trim skirt is outdoor rated when used with the Model 449 electrical box 2 Not compatible with the trim skirts To synchronize horn operation you must install a separate synchronization source See Table 3 When connecting the horn to a listed control...

Page 2: ... Specifications on page 3 for a list of compatible boxes 4 Feed the field wiring through the wire slots on the gasket and the backplate See Figure 2 item 3 and Figure 3 item 1 5 Align the appliance and trim skirt if applicable and then secure the backplate to the electrical box with the supplied screws Check the assembly to ensure that it is securely mounted 6 Set the horn volume The default horn ...

Page 3: ...imensions W H D 5 6 8 5 1 4 in 142 216 36 mm Sound level output See Table 4 Table 5 Table 6 and Table 7 Horn tone 3 2 kHz Wire size 12 to 18 AWG 0 75 to 2 50 mm Compatible electrical box Outdoor Indoor Model 449 4 in square by 1 5 in deep box Operating environment Temperature Relative humidity 40 to 151 F 40 to 66 C 0 to 95 noncondensing Table 4 Sound pressure level dBA per UL 464 Volume Setting 1...

Page 4: ...nd ou sur un mur Voir Table 1 pour une liste des modèles et Table 2 pour une liste des accessoires Pour les applications à montage en surface monter le WG4 sur un boîtier électrique Model 449 à l aide du joint livré avec l appareil Pour les applications à montage encastré où la surface de montage est alignée avec la surface du mur ou du plafond utiliser le nécessaire de joint WG4GSKT Remarque un b...

Page 5: ...ner le joint approprié sur la platine arrière en vérifiant que la fente de guidage des câbles et les autres orifices s alignent correctement Retirer le revêtement de protection de la surface du joint et appliquer précautionneusement le joint sur le WG4 avec le côté adhésif orienté vers l appareil L appuyer fermement contre la surface arrière de l appareil pour le positionner correctement 3 Mettre ...

Page 6: ...te de guidage des câbles et des cavaliers JP3 1 2 3 JP1 1 Fente de guidage des câbles 2 Cavalier du volume de l avertisseur sonore JP3 3 Cavalier du motif de l avertisseur sonore JP1 Câblage Voir Figure 4 Raccorder tous les fils conformément aux codes de l électricité locaux et aux exigences locales pertinentes Attention risque pour le dispositif Pour éviter d endommager le dispositif vérifier que...

Page 7: ...veau de pression sonore dBA selon UL 464 Réglage du volume 16 V 24 V 33 V Continu élevé 89 7 94 7 97 4 Continu faible 85 4 89 5 92 5 Temporel élevé 84 2 90 5 93 5 Temporel faible 81 7 85 4 88 1 dBA décibels pondérés A UL 464 niveau de sortie sonore mesuré dans une salle réverbérante à 3 05 m 10 pi Tableau 5 Niveau de pression sonore dBA selon CAN ULC S525 Réglage du volume 16 V 24 V 33 V Continu é...

Page 8: ...la partie 15 des règles FCC Son fonctionnement est soumis aux deux conditions suivantes 1 ce dispositif ne doit pas causer d interférences nuisibles et 2 il doit accepter toutes les interférences reçues y compris celles qui sont susceptibles d entraîner un fonctionnement indésirable Conformité ICES Cet appareil numérique de classe B est conforme à la norme canadienne ICES 003 Classe de service Int...