User manual
ALFA 52 VS 0-20

O

C

Differential Thermostat.

VDH doc. 080331

Versie: v1.2

Datum: 22-04-2010

Software;

File: Do080331.wpd

Static range (see sticker);

992903 ALFA 52/72 VS 20 -50..+50 

Typenr.: 904.000806

-50/+50,0

C

100320 ALFA 52/72 VS 20 -20..+80 

Typenr.: 904.000929

-20/+80,0

C

992901 ALFA 52/72 VS 20 0..+100

Typenr.: 904.000916

0/+100,0

C

* Installation.

On the connection diagram of the 

ALFA 52-VS

 is shown how the sensors, power supply and relays

has  to be connected. After connecting the 

ALFA 52-VS

 to the power supply, a self test function is

started.  As  this  test  is  finished,  the  measured  differential  temperature  of  sensor-1  minus  sensor-2
appears in the display. 

* Control.

The 

ALFA 52-VS

 thermostat can be controlled by four pushbuttons on the front These keys are:

SET

- view / change set point and reset the alarm

 (UP)

- increase the set point.

 (DOWN)

- decrease the set point.

MODE

- relays status key.

* Viewing the temperature from sensor-1 and sensor-2.

By pressing the 

UP

 and 

DOWN

 keys simultaneously and after that the 

UP

 key, the measured value

from  sensor-1  can  be  read-out.  If  the  down  key  is  pressed,  the  measured  value  from  sensor-2  is
shown. If no key is pressed for a few seconds, the differential temperature is shown again.

* Viewing the delta-setpoint.

By pushing the 

SET

 key, the set point of delta thermostat appears in the display.

A few seconds after releasing the keys the setpoint disappears and the differential temperature is
shown again in the display.

* Changing the delta-setpoint.

Push the 

SET

 key. The delta-setpoint appears in the display. Release the 

SET

 key. Now push the 

SET

key again together with the 

UP

 or 

DOWN

 keys to change the set point. A few seconds after releasing

the keys, the measured differential temperature is shown again in the display.

* Status of the Relays.

By pushing the 

MODE

 key the display shows the status of the relays. 

Each digit shows the status of one relay output, showing 0 = off and 1 = on. 
The code 110 means relay 1 and 2 are on and relay 3 is off.
Relays 1 and 2 are used for the differential thermostat (see function diagram).
Relay 3 is used as an alarm relay.