background image

 

TCY-MT 

PI-temperature controller 

 

Doc: 70-00-0058 V1.2, 20160322 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

www.vectorcontrols.com 

TCY-MT series PI-temperature controller 

Features 

 

Temperature PI control for HVAC systems.  

 

Up to 2 modulating outputs for DC 0–10 V with 10 mV resolution.  

 

1 internal temperature sensor and up to 2 external sensor inputs 

 

Multiple remote control functions on external input 

 

Password protected programmable user and control parameters 

 

Blue backlight 

Applications 

 

Various temperature control applications 

 

Stand alone VAV control for pressure independent actuators 

 

Water-only systems: Radiator, floor heating or chilled ceilings 

 

Individual room control for offices, residential, hotel rooms, 

meeting rooms, etc.  

General Description 

The TCY-MT is a stand-alone electronic temperature controller with one 

control loop. It may use up to 2 PI sequences. The TCY-MT features one internal NTC temperature sensor, up to two 

external sensor inputs and up to two analog outputs. The configuration has been reduced to a minimum to allow for 

simple and off-the-shelve usage. For more advanced features and current inputs and outputs the TCI product range is 

recommended. The TCY-MT can be configured using the standard operation terminal. No special tool or software is 

required.  

Name  

 

Ordering 

Item Name 

Item code 

Control Type 

Key-data 

TCY-MT2-W01 

40-10 0043-01 

Cooling only 

Compact PI controller with: 

2 TI, 1 AO 

TCY-MT2-W02 

40-10 0043-02 

Heating only 

TCY-MT2 

40-10 0043 

2-Pipe system 

TCY-MT4 

40-10 0045 

4-Pipe system 

1 TI, 2 AO 

Accessories

 

 

 

 

S-Tn10-2 

SD-Tn10-12-2 

SD-Tn10-20-2 

SDB-Tn10-12-1 

SDB-Tn10-20-1 

SOA-Tn10 

40-20 0001 
40-20 0002 

40-20 0003 

40-20 0124 

40-20 0133 

40-20 0006 

Flying lead sensor with 2 m cable 

Flying lead duct sensor 12cm immersion depth, 2m cable 

Flying lead duct sensor 20cm immersion depth, 2m cable 

Duct sensor with housing, 12cm immersion depth 

Duct sensor with housing, 20cm immersion depth 

Outdoor sensor

 

Selection of actuators and sensors 

Temperature Sensors:  

Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is SDB-Tn10-20 as Duct sensor, SRA-

Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.  

Modulating Actuators:  

Choose actuators with an input signal type of 0–10V DC or 2–10V DC.  

 

Housing:  

U  = Vertical (2x4”) housing, Standard is square housing 

Function: 

2  = 2 = 2-Pipe, 4 = 4-Pipe

 

Input: 

T  = Temperature, H = Humidity 

Output:  

M  = Modulating, B = Binary 

Series: 

TCY

 

T  C  Y 

-  M 

-  U 

(   )  

Summary of Contents for TCY-MT2-W01

Page 1: ...es and current inputs and outputs the TCI product range is recommended The TCY MT can be configured using the standard operation terminal No special tool or software is required Name Ordering Item Nam...

Page 2: ...122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non conden...

Page 3: ...rect sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers...

Page 4: ...connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY MT may display the following error condition Err1 The connection to the tempera...

Page 5: ...WN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediatel...

Page 6: ...Cooling mode YC1 1 TCY MT2 W02 Heating mode YH1 2 TCY MT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY MT4 Heating and Cooling 4 pipe system YH1 YC1 TCY MT2 0 2 TCY MT4 0 3 TCY MT2 W01 0 TCY MT2 W...

Page 7: ...MT4 heating output 0 100 0 CP 14 Max output for AO1 TCY MT4 heating output 0 100 100 CP 15 Min output for AO2 TCY MT4 cooling output 0 100 0 CP 16 Max output for AO2 TCY MT4 cooling output 0 100 100...

Page 8: ...on detectors for offices CP18 2 Switching Energy Hold OFFand Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridde...