1) Introduction  

 

The D2xC1 is an ATEX, IECEx and UL certified Alarm Horn and Strobe 
which produces a loud warning signal and bright visual signal in a 
hazardous area. Sixty-Four first stage alarm sounds can be selected 
by internal switches and each one can be externally changed to a 
second, third or fourth stage alarm sound. The unit may be used for 
Gas applications in Zone 2 / Class I Zone 2 / Class I, Division 2 as well 
as for Dust applications in Zone 22 / Class II Zone 22 / Class II Divison 
2 / Class III Division 1 & 2. The beacon flashes at a set rate of 1Hz. 
The D2xC1X05DC024 is also listed as Audible & Visual Appliances for 
use in Fire Alarm Systems Private Mode in accordance with UL464 
Tenth Edition & UL1638 Fourth Edition.  

 

 

2) Warnings 

 

 

SUITABLE FOR USE IN CLASS II, DIVISION 2, GROUPS A, B, C AND D 
HAZARDOUS LOCATIONS  
SUITABLE FOR USE IN CLASS II, DIVISION 2, GROUPS E, F AND G HAZARDOUS 
LOCATIONS  
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE IS PRESENT  
WARNING 

 EXPLOSION HAZARD 

 SUBSTITUTION OF ANY COMPONENT 

MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.  
WARNING 

 EXPLOSION HAZARD 

 SUBSTITUTION OF ANY COMPONENTS 

MAY IMPAIR SUITABILITY FOR CLASS II, DIVISION 2.  
POTENTIAL ELECTROSTATIC CHARGING HAZARD 

 CLEAN ONLY WITH A 

DAMP CLOTH  
USE HEAT RESISTANT CABLES AND CABLE GLANDS (RATED 90ºC OR HIGHER)  
EXPLOSION HAZARD. DO NOT REMOVE OR REPLACE LAMPS, FUSES OR PLUG-
IN MODULES UNLESS POWER HAS BEEN DISCONNECTED OR THE AREA IS 
KNOWN TO BE FREE OF IGNITIBLE CONCENTRATIONS OF FLAMMABLE GASES 
OR VAPORS.  
EXPLOSION HAZARD. DO NOT DISCONNECT WHILE THE CIRCUIT IS LIVE OR 
UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITIBLE CONCENTRATIONS.  
DO NOT PAINT  
NE PAS PEINTURER 

 

 

 

3) Ratings and Markings 

 

 

3.1 ATEX / IECEx certification  

 
The D2xC1 Alarm Horn and Strobe complies with the 
following standards:  
 
EN60079-0:2012+A11:2013 / IEC60079-0: ed. 6.0 (2011-06)  
EN60079-15:2010 / IEC60079-15: ed. 4.0 (2010-01)  
EN60079-31:2009 / IEC60079-31: ed. 1.0 (corr. 1 2009)  
 
The EC-Type Examination Certificate DEMKO 
14ATEX4786493904X / IECEx ULD14.0004X has been issued by 
UL. This confirms compliance with the European ATEX 
Directive 94/9/EC for Group II, Category 3G/D equipment. 
The unit carries the Community Mark and subject to local 
codes of practice, may be installed in any of the EEA member 
countries. This instruction sheet describes installations which 
conform to the current issue of EN60079-14/IEC60079-14 
Electrical Installation in Hazardous Areas; EN60079-10-1 / IEC 
60079-10- 1 Explosive Atmospheres - Classification of Areas. 
Explosive Gas Atmospheres; EN60079-10-2 / IEC 60079-10-2 
Explosive Atmospheres - Classification of Areas. Explosive 
Dust Atmospheres. When designing systems for installation 
outside the UK, the local Code of Practice should be 
consulted.  
 
The D2XC1X05 is rated as follows:  
 

II 3G Ex nA IIC T2 Gc (Ta -40ºC to +50°C)  
II 3D Ex tc IIIC T90ºC Dc (Ta -40ºC to +50°C) 
 

 
CE marking: 

 

 

 

Zones, Gas/Dust Groups and Temperature Classification 
 

 

When connected to an approved system the D2X unit may be 
installed in:  
 

Zone 2   explosive gas air mixture not likely to occur 

in normal operation, and if it does, it will 
only exist for a short time. 

  
Zone 22  explosive dust air mixture not likely to 

occur in normal operation, and if it does, it 
will only exist for a short time.  

 

May be used with gases in groups: 
 

 

Group IIA propane  
Group IIB ethylene  
Group IIC hydrogen / acetylene  

 
Having a temperature classification 

 

(for Gas applications) of:  

 

T1 450ºC  

T2 300ºC 

 

 

 

 VL-D2xC1X05 Explosion Proof Horn Alarm & Strobe

 

Summary of Contents for VL-D2 C1X05 Series

Page 1: ...BE FREE OF IGNITIBLE CONCENTRATIONS DO NOT PAINT NE PAS PEINTURER 3 Ratings and Markings 3 1 ATEX IECEx certification The D2xC1 Alarm Horn and Strobe complies with the following standards EN60079 0 2...

Page 2: ...2 FG T5 Ta 40 C to 50 C Class III Div 1 2 Ta 40 C to 50 C Installation must be carried out in compliance with the National Electric Code Canadian Electric Code 3 5 Ambient Temperature Range 40 C to 70...

Page 3: ...ocks using solid or stranded wire sizes 0 5 2 5mm2 AWG 20 14 Wire insulation needs to be stripped 6 7mm Wires may be fitted securely with crimped ferrules Terminal screws need to be tightened down wit...

Page 4: ...kwise 7 Cable Routing and Tone Selection 7 1 Cable Routing Due to the compact design of the D2x units it is important that the user strips the outer sheath of and biases any cables over the size of 1m...

Page 5: ...ecting the alarm horn and strobe can be removed if the user wishes to power the strobe separately 9 4 Second Third and Fourth Stage Tone Selection For units set up for ve switching default setting Sta...

Page 6: ...cure the earth conductor to the earth stud The external earth conductor should be at least 4mm2 in size The external earth crimp ring should be located between the two M5 plain washers provided and se...

Page 7: ...www velocitydetection com Doc GLT 313 7 1 Issue 001 Date 28 10 2020 VL D2xC1X05 Explosion Proof Horn Alarm Strobe...

Page 8: ...www velocitydetection com Doc GLT 313 7 1 Issue 001 Date 28 10 2020 Tone Selection cont VL D2xC1X05 Explosion Proof Horn Alarm Strobe...

Reviews: