background image

www.ventsus.com

MIU_VKM_EC-01

Bodor Vents, LLC DBA: VENTS-US
11013 Kenwood Road Cincinnati, Ohio 45242
Phone: (513)348-3853 
e-mail: sales@ventsus.com

CENTRIFUGAL INLINE FAN

VKM EC 100/125/150/200/250/305

INSTALLATION GUIDE

Tools required

Pencil

Drill (Ø 8 mm))

Screwdriver

Dowel NTW 8/45 (4 pcs.)

Screws 5x45 mm (4 pcs.)

MOUNTING

The air motion in the system must be as shown with the pointer of the fan casing.
In case of the vertical installation the intake spigot must be protected with a ventilation hood. 
To attain the best performance of the fan and to minimise turbulence-induced air pressure losses while mounting connect straight air duct sections to the fan spigots.
Minimum straight air duct length:
qual to 1 air duct diameter on intake side
equal to 3 air duct diameters on outlet side

min D

min 3D

D