SAFETY INFORMATION
Before installing the VRF-1000 model, please read these
instructions and familiarize yourself with the requirements
and functions. If any questions or problems arise during the
installation, please contact Bindicator
®
Applications at
1-800-778-9242.
The VRF-1000 model must only be installed and operated
as described in this operating instruction. Please note that
other action can cause damage for which Bindicator
®
does
not take responsibility. If the model is not installed correctly
or used in approved applications, dangers may arise such
as product overflow.
Ensure that all personnel installing, wiring, and calibrating this device are
suitably qualified.
Observe all local and national electrical codes for the wiring of this device.
IMPORTANT!
Either AC or DC power is to be connected to the power input depending on
the model. Consult the nameplate of the unit. Models beginning with
VRF1A are AC powered units and accept any voltage between 85 VAC and
265 VAC. Models beginning with VRF1D are DC powered units and accept
any voltage between 9 VDC and 36 VDC.
IMPORTANT!
An electrical earth ground connection must be made to the housing input
ground screw. See Figure 1 for location. This connection is needed for both
electrical safety and proper operation of the unit. This is required for both
AC and DC units.
External ground wire must be connected to tank wall or top of tank.
VRF-1000 Series
of Variable Radio Frequency
Point Level Sensors
Integral Electronics with Opti-Sense
TM
Quick-Start Guide
150 Venture Boulevard
Spartanburg, SC 29306
Phone: (864) 574-8060, Fax: (864) 574-8063
Customer Care: (800) 778-9242
Internet: http://www.bindicator.com
email: sales@bindicator.com
© 2006 All rights reserved.
All data subject to change without notice. VRF 180400 Rev. B 12/06
Please see VRF180000 for complete installation guidelines.
Dimensional and electrical drawings of the VRF-1000 models are available in
various formats from Bindicator's website; www.Bindicator.com
From the home page, click on the link Installation Manuals/VRF180000 to obtain
the applicable drawing.
If access to the internet is not available, please contact Bindicator
®
Customer
Care Department at 1-800-778-9242 for assistance in obtaining these drawings.
Start-up & Operation
The VRF-1000 will automatically begin operation when powered up. It should be
initially powered after it is installed in the application and with material below the
probe. When initially powered up, the VRF-1000 will automatically begin a 3
second calibration operation. If the unit is powered on the bench prior to instal-
lation, or moved from one installation to another, recalibration is required.
Momentarily press the recalibration pushbutton. The green calibration indication
LED will go off, and after 3 seconds illuminate to indicate calibration is complete.
The VRF-1000 is shipped from the manufacturer with the automatic
calibration/recalibration feature enabled. If only manual pushbutton
calibration/recalibration is desired, set SW1 DIP switch position 6 to off.