Installation Guide
Temperature
Z204455-0E
Page 1 of 4
©2014 Veris Industries
02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Product Identification
Product Overview
The TWS analog series measures the temperature of the air inside a room. Devices are designed for use in hospital
rooms, laboratories, and other spaces that require precise environmental control. The keypad allows control of
setpoint values. The slide switch position determines the output type (amp or volt). To maintain accuracy, keep
vents clear of dust, debris, etc. The TWS is warranted for period of five years.
TWS Series
Wall Mount with Analog Setpoints, LCD and
Thermostat Control
Setpoint
= Analog
TWS
Temp Cal
Certificate
0 = None
1 = 1 point Cal
Validation
2 = 2 point Cal
Validation
Option
S
= CE
A
Specifications
Input Power
15-30VDC/24VAC, 100mA max.
Outputs
Switch-selectable amp or volt
If volt is selected, the configuration menu allows selection between
0-5V or 0-10V
Physical
UL 94-V-O fire retardant ABS
Temperature Accuracy
±0.5°C (±1°F)
Operating Humidity Range
0-100% RH (non-condensing)
Operating Temperature Range
10° to 35°C (50° to 95°F)
Analog Output Scaling
10° to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F), menu
selectable*
Calibration Offset
Adjustable ±9.9° (C or F) in 0.1° increments
Setpoint Range
Minimum to Full Scale in 1° (C or F) increments
* If the 0° to 50°C (32° to 122°F) scaling range is selected, the device’s operating temperature range still applies.
One side of the transformer secondary is connected to the signal common, so an isolation transformer or
dedicated power supply may be required.
RTD/Thermistors in wall packages are not compensated for internal heating of the product.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper
surge protection (EN 61000-6-1:2007 specification requirements).
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
I = 1k Balco (nickel-iron) RTD
J = 10k Dale, Thermistor
K = 10k w/11k shunt,Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
Q = 1uA/C, Linitemp
R = 10k US, Thermistor
S = 10k 3A 221, Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor
CC= 15k, Thermistor