background image

6%2)3).$5342)%3

POWER MONITORING

INSTALLATION GUIDE

 Z202366-0M 

page 1 

©2008 Veris Industries   USA 800.354.8556 or 503.598.4564  / support@veris.com   

02081

H704-42(H)(E), H704-42/1(H)(E) 

General:

   Operating Temp. Range 

0° to 60°C (32° to 140°F) (<95% RH, non-condensing)

   Storage Temp. Range 

-40° to 70°C (-40° to 158°F)

   Control (Mains) Power Source 

120 VAC L-N, 50/60 Hz (208/230 VAC for H704-42/1(E)) 

    

(+10/-25%) Input current < 75 mA

   Primary Fusing 

250 VAC/100 mA, (T) 5 x 20 mm, (if equipped) Littelfuse 218 series 

    

or equivalent 

   Altitude of Operation 

3 km max.

Measured Current Inputs:

   Number of Channels 

42

   Frequency 

50/60 Hz

   Sample Frequency 

1280 Hz

   Update Rate 

1.2 sec

   Accuracy 

±2% from 5 A to 50 A *

   Overload Capability 

Tested to 10,000 A single-cycle

   Connection to Conductor 

Solid-core toroid

   Measured Currents 

Current range 0-50 A (max. conductor size is AWG#6 THHN)

   Measured Currents, H version  Current range 0-100 A (max. conductor size is AWG#2 THHN)

Network Communications:

   Type 

Modbus RTU

   Connection 

DIP switch-selectable 2-wire or 4-wire

   Address 

DIP switch-selectable address 1 to 247

   Baud Rate 

DIP switch-selectable 2400, 4800, 9600, 19200

   Parity 

DIP switch-selectable NONE, ODD, EVEN

   Communication Format 

8-data-bits, 1-start-bit, 1-stop-bit

   Termination 

5-position depluggable connector 

 

(TX+ TX- SHIELD TX+/RX+ TX-/RX-)

Defaults:

   Warning Register 

60% of current sensor max. (configurable)

   Alarm Register 

70% of current sensor max. (configurable)

   Breaker Size Register 

20 A

*  In case of a current fault above 60A (120 for the H version), all adjacent channels will report 
higher than actual readings. To prevent this from causing over-current warnings and alarms, 
configure the warning and alarm delays for a longer time period than the response time of the 
breaker.

quick install

Installer's Specifications

NOTICE

DANGER

1.  Disconnect and lock out power.
2.  Mount current sensor strips adjacent to breaker terminations.
3.  Verify that serial numbers on CT and board match.
4.  Mount board onto electrical/fire enclosure.
5.  Connect CTs and wire the board.
6.  Reconnect power.
7.  Configure communication and addressing parameters.
Note:  Data acquisition board and CT strips are calibrated as a set. Match the serial 

numbered parts together.

MODEL #

CT SPACING

H704-42(H)(E)

3/4" on center

H704-42/1(H)(E)

1" on center

For a 400A Panel, order the H704-42Y55 

Branch Current Monitor

Shop for Veris products online at:

1.877.766.5412

www.

PowerMeterStore

.com

Summary of Contents for H704-42

Page 1: ...switch selectable 2400 4800 9600 19200 Parity DIP switch selectable NONE ODD EVEN Communication Format 8 data bits 1 start bit 1 stop bit Termination 5 position depluggable connector TX TX SHIELD TX RX TX RX Defaults Warning Register 60 of current sensor max configurable Alarm Register 70 of current sensor max configurable Breaker Size Register 20 A Incaseofacurrentfaultabove60A 120fortheHversion ...

Page 2: ...s network 2 OpticalCommunicationsIsolation Optical isolators are used to separate 120 VAC portions of the circuit from the RS485 network 3 AliveLED Flashes once per second to indicate correct operation If steadily lit or out indicates internal failure 4 50 PinRibbonCableConnectors DataAcquisitionBoard 18 inch 457 mm ribbon cables are provided standard for easy snap connection of current sensor str...

Page 3: ...ution and the possibility of condensation or high humidity Consideration must be given to the enclosure the correct use of ventilation thermal properties of the equipment and the relationship with the environment This symbol indicates an electrical shock hazard exists Documentation must be consulted where this symbol is used on the product Installation 11 375 289 mm 1 12 28 mm 5 75 146 mm Data Acq...

Page 4: ... board 4 Check that CT serial numbers and meter serial numbers match Meter and CT sold as set with accuracy calibrated as a set For208 230VACPowerConnectionversion orderH704 42E H704 42 IE 522 4 3 3 2 342 0 522 4 3 3 2 342 0 522 4 3 3 2 342 0 522 4 3 3 2 342 0 ATA CQUISITION OARD ODBUS 5P TO gS 2IBBON ABLE 4O ONTROLLER OR 0 0ANEL OARD 0ANEL OARD 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42...

Page 5: ...connected together in a daisy chain fashion and properly terminated C The Modbus cable should be shielded twisted pair wire such as Belden 1120A The cable must be voltage rated for the installation 2 Wire 4 Wire 1 Connect 2 wire or 4 wire Modbus RS485 daisy chain network wiring WARNING After wiring the Modbus cable remove all scraps of wire or foil shield from the electrical panel This could be DA...

Page 6: ...th a set of 8 dip switches for addressing See below LSB MSB VALUE Example 2 wire9600BaudNoParity DefaultOnly 1 X X X X X X 2 On Off 3 Off On Off On 4 Off Off On On 5 6 7 X X X X X X 8 X X X X X X 2400 Baud 4800 Baud 9600Baud 19200 Baud 2wire 4 wire Wiring Baud Rate Parity Wiring None Even Odd Off Off On Off On Off Parity Baud Rate DESIRED RESULT Switch Baud Rate and Parity Switch Setttings 40 2 Ad...

Page 7: ...upport veris com 02081 communications setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Shop for Veris products online at 1 877 766 5412 www PowerMeterStore com ...

Page 8: ...8 series or equivalent 5 Reconnect 120V to Data Acquisition Board 6 Reconnect power to panel 7 Check Alive LED for proper function See Product Diagram section for location service ACCESSORIES CBL008 Cable Ribbon 18 in 457 mm BCM CBL016 Cable Ribbon 48 in 1219 mm BCM CBL017 Cable Ribbon 60 in 1524 mm BCM CBL018 Cable Ribbon 72 in 1829 mm BCM CBL019 Cable Ribbon 97 in 2464 mm BCM CBL020 Cable Ribbon...