POWER MONITORING
INSTALLATION GUIDE
Z202366-0M
page 1
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com
02081
H704-42(H)(E), H704-42/1(H)(E)
General:
Operating Temp. Range
0° to 60°C (32° to 140°F) (<95% RH, non-condensing)
Storage Temp. Range
-40° to 70°C (-40° to 158°F)
Control (Mains) Power Source
120 VAC L-N, 50/60 Hz (208/230 VAC for H704-42/1(E))
(+10/-25%) Input current < 75 mA
Primary Fusing
250 VAC/100 mA, (T) 5 x 20 mm, (if equipped) Littelfuse 218 series
or equivalent
Altitude of Operation
3 km max.
Measured Current Inputs:
Number of Channels
42
Frequency
50/60 Hz
Sample Frequency
1280 Hz
Update Rate
1.2 sec
Accuracy
±2% from 5 A to 50 A *
Overload Capability
Tested to 10,000 A single-cycle
Connection to Conductor
Solid-core toroid
Measured Currents
Current range 0-50 A (max. conductor size is AWG#6 THHN)
Measured Currents, H version Current range 0-100 A (max. conductor size is AWG#2 THHN)
Network Communications:
Type
Modbus RTU
Connection
DIP switch-selectable 2-wire or 4-wire
Address
DIP switch-selectable address 1 to 247
Baud Rate
DIP switch-selectable 2400, 4800, 9600, 19200
Parity
DIP switch-selectable NONE, ODD, EVEN
Communication Format
8-data-bits, 1-start-bit, 1-stop-bit
Termination
5-position depluggable connector
(TX+ TX- SHIELD TX+/RX+ TX-/RX-)
Defaults:
Warning Register
60% of current sensor max. (configurable)
Alarm Register
70% of current sensor max. (configurable)
Breaker Size Register
20 A
* In case of a current fault above 60A (120 for the H version), all adjacent channels will report
higher than actual readings. To prevent this from causing over-current warnings and alarms,
configure the warning and alarm delays for a longer time period than the response time of the
breaker.
quick install
Installer's Specifications
NOTICE
DANGER
1. Disconnect and lock out power.
2. Mount current sensor strips adjacent to breaker terminations.
3. Verify that serial numbers on CT and board match.
4. Mount board onto electrical/fire enclosure.
5. Connect CTs and wire the board.
6. Reconnect power.
7. Configure communication and addressing parameters.
Note: Data acquisition board and CT strips are calibrated as a set. Match the serial
numbered parts together.
MODEL #
CT SPACING
H704-42(H)(E)
3/4" on center
H704-42/1(H)(E)
1" on center
For a 400A Panel, order the H704-42Y55
Branch Current Monitor