Liebert®

EXM™ MBC™ 

User Manual—10-200kVA, 208/120V and 220/127V, 60Hz

Summary of Contents for Liebert EXM MBC

Page 1: ...Liebert EXM MBC User Manual 10 200kVA 208 120V and 220 127V 60Hz...

Page 2: ...r damages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the correct methods tools and materials to be used in...

Page 3: ...net6 Figure 2 One line diagram single input Liebert EXM 10 40kVA UPS with three breaker Lieb ert EXM MBC and input output transformer cabinet 10 Figure 3 One line diagram single input Liebert EXM 10 2...

Page 4: ...23 Terminal details 800mm Liebert EXM MBC three breakers 160 200kVA system29 Figure 24 Terminal details 800mm Liebert EXM MBC four breakers 160 200kVA system 30 Figure 25 Control wiring diagram Lieber...

Page 5: ...UPS with internal batteries 36 Table 15 Liebert EXM MBC input currents single input main 37 Table 16 Liebert EXM MBC input currents dual input rectifier 38 Table 17 Liebert EXM MBC input currents dual...

Page 6: ...Vertiv Liebert EXM MBC Installation Manual iv...

Page 7: ...ware that the system contains high DC as well as AC voltages Check for voltage with both AC and DC voltmeters prior to making contact AVERTISSEMENT Le centre de gravit lev des appareils pr sente un ri...

Page 8: ...y test equipment designed for troubleshooting should be used This is particularly true for oscilloscopes Always check with an AC and DC voltmeter to ensure safety before making contact or using tools...

Page 9: ...t tre utilis s Cette mise en garde couvre notamment les oscilloscopes Utilisez toujours un voltm tre c a et c c pour v rifier les tensions avant d tablir un contact ou d utiliser des appareils Des ten...

Page 10: ...ately Verify that the correct equipment is being installed The equipment supplied has an identification tag on the back of the main door reporting the type size and main calibration parameters of the...

Page 11: ...ons bars auxiliary terminal blocks and power isolators 1 4 1 Moving the Cabinets The route to be travelled between the point of arrival and the unit s position must be planned to make sure that all pa...

Page 12: ...ed to the cabinets they are connected to The cable design must comply with the voltages and currents provided in Tables 15 through 17 follow local wiring practices and take into consideration the envi...

Page 13: ...for heavy currents as a way of easing installation WARNING Risk of electric shock Can cause equipment damage injury and death Before cabling up the cabinet ensure that you are aware of the location an...

Page 14: ...ship attached to the UPS The 600mm and 800mm maintenance bypass cabinets ship separately from the UPS Liebert EXM UPS Liebert EXM UPS Maintenance Bypass Cabinet Matching Battery Cabinet Matching Liebe...

Page 15: ...m me la mort Le non respect des proc dures de mise la terre peut entra ner des risques d lectrocution du personnel ou des risques d incendie en cas de d fectuosit de la mise la terre WARNING Risk of...

Page 16: ...a single input type connect the AC input supply cables between the Liebert EXM MBC and the UPS bypass input supply busbars A B C or A B C N terminals and connect AC jumper connectors between UPS bypas...

Page 17: ...he UPS to the main ground system must follow the most direct route possible Consideration should be given to the use of smaller paralleled cables for heavy currents as a way to ease installation In mo...

Page 18: ...TERY NOTES 1 Install in accordance with national and local electrical codes 2 Input and bypass must share the same single source 3 Bypass and rectifier inputs and output cables must be run in separate...

Page 19: ...single source 3 A neutral is required from the system AC input source Vertiv recommends a full capacity neutral conductor and grounding conductors 4 Bypass and rectifier inputs and output cables must...

Page 20: ...s must share the same single source 3 A neutral is required from the system AC input source Vertiv recommends a full capacity neutral conductor and grounding conductors 4 Bypass and rectifier inputs a...

Page 21: ...al codes 2 Vertiv recommends a full capacity neutral conductor and grounding conductors 3 Bypass and rectifier inputs and output cables must be run in separate conduits 4 Control wiring must be run in...

Page 22: ...single source 3 A neutral is required from the system AC input source Vertiv recommends a full capacity neutral conductor and grounding conductors 4 Bypass and rectifier inputs and output cables must...

Page 23: ...AC input source Vertiv recommends a full capacity neutral conductor and grounding conductors 4 Bypass and rectifier inputs and output cables must be run in separate conduits 5 Control wiring must be...

Page 24: ...ker Configuration Configured Breaker 2 MBB MIB 3 BIB MBB MIB 4 RIB BIB MBB MIB Table 3 Terminal block details 200mm Liebert EXM MBC two to four breakers 10 40kVA system Terminal Block Single Input Sys...

Page 25: ...ration Configured Breaker 2 MBB MIB 3 BIB MBB MIB 4 RIB BIB MBB MIB Table 5 Terminal block details 300mm Liebert EXM MBC two to four breakers 60 100kVA system Terminal Block Single Input System Dual I...

Page 26: ...2 Main components 600mm Liebert EXM MBC three to four breakers 120 160kVA system RIGHT SIDE VIEW Panel Removed LEFT SIDE VIEW Panel Removed FRONT VIEW Door Removed Neutral Busbar MBB MIB EXM15104 RIGH...

Page 27: ...0mm Liebert EXM MBC three or four breakers 160 200kVA system RIGHT SIDE VIEW Panel Removed LEFT SIDE VIEW with Panel Removed 160 180kVA Models LEFT SIDE VIEW Panel Removed 200kVA Model Only FRONT VIEW...

Page 28: ...for forklift handling 5 Control wiring and power wring must be run in separate conduits 6 All wiring must be in accordance with national and local electrical codes 7 Liebert EXM MBC will always be att...

Page 29: ...s of vertical 4 Top and bottom cable entry available through removable access plates Remove punch to suit conduit size and replace 5 Unit bottom is structurally adequate for forklift handling 6 Contro...

Page 30: ...r forklift handling 5 Control wiring must be run in separate conduits 6 All wiring is to be in accordance with national and local electrical codes 7 The maintenance bypass cabinet will always be attac...

Page 31: ...ly adequate for forklift handling 5 Control wiring must be run in separate conduits 6 All wiring is to be in accordance with national and local electrical codes 7 The maintenance bypass cabinet will a...

Page 32: ...FRONT Door Not Shown RIGHT SIDE Panel Not Shown MIB BIB RIB Output TB3 See Detail A MBB NOTES 1 Control wiring and power wiring must be run in separate conduits 2 All wiring must be in accordance wit...

Page 33: ...MBB MIB Neutral Busbar Input TB2 See Detail A Rectifier Input TB4 See Detail A Ground Busbar LEFT SIDE Panel Not Shown FRONT Door Not Shown RIGHT SIDE Panel Not Shown MIB BIB RIB Output TB3 See Detail...

Page 34: ...nel Not Shown MIB See Detail B MBB Input See Detail A Ground Busbar See Detail A Neutral Busbar MBB See Detail B NOTES 1 Control wiring and power wiring must be run in separate conduits 2 All wiring m...

Page 35: ...r See Detail A Neutral Busbar MBB See Detail B NOTES 1 Control wiring and power wiring must be run in separate conduits 2 All wiring must be in accordance with national and local electrical codes 3 If...

Page 36: ...Ground Busbar See Detail A Neutral Busbar MBB See Detail B NOTES 1 Control wiring and power wiring must be run in separate conduits 2 All wiring must be in accordance with national and local electric...

Page 37: ...e Detail A Ground Busbar See Detail A Neutral Busbar MBB See Detail B NOTES 1 Control wiring and power wiring must be run in separate conduits 2 All wiring must be in accordance with national and loca...

Page 38: ...tail A Ground Busbar See Detail A Main Input Busbar See Detail A Neutral Busbar MBB See Detail B NOTES 1 Control wiring and power wiring must be run in separate conduits 2 All wiring must be in accord...

Page 39: ...Customer furnished electrode conductor must be installed in accordance with national and local electrical codes 2 Overcurrent protection is based on 80 rated devices 3 MBB auxiliary switch connections...

Page 40: ...tiv Liebert EXM MBC Installation Manual 34 Figure 26 Solenoid key release unit 200mm Liebert EXM MBC K0 K1 K2 TB1 Fuseblock for SKRU Solenoid key release unit is mounted between the BIB and MBB breake...

Page 41: ...tiv Liebert EXM MBC Installation Manual 35 Figure 27 Solenoid key release unit 300mm Liebert EXM MBC K0 K1 K2 Solenoid key release unit is mounted between the BIB and MBB breakers TB1 Fuseblock for SK...

Page 42: ...t EXM MBC Installation Manual 36 Figure 28 Solenoid key release unit 600mm Liebert EXM MBC Figure 29 Solenoid key release unit 800mm Liebert EXM MBC K0 K1 TB1 Fuseblock for SKRU K2 TB1 Fuseblock for S...

Page 43: ...n mm 78 74 2000 Weight lb kg 198 90 288 131 535 243 700 318 Color Black ZP 7021 Degree of Protection for UPS Enclosure IP 20 with and without front door open Standards and Conformities UL1778 5th Edit...

Page 44: ...0 100kVA and 300mm Liebert EXM MBC UPS Rating kVA UPS Weight lb kg Liebert EXM MBC 300mm Weight lb kg Combined Weight UPS and Liebert EXM MBC lb kg 60kVA 844 383 288 131 1132 514 80kVA 918 416 288 131...

Page 45: ...uminu m Wire Bolt Size 208 120 220 127 10 34 3W N G 45 65 1 6 1 4 M10 208 120 220 127 15 51 3W N G 70 85 1 4 1 2 M10 208 120 220 127 20 68 3W N G 90 115 1 2 1 1 0 M10 208 120 220 127 30 102 3W N G 150...

Page 46: ...220 127 20 68 90 3W N G 115 1 2 1 1 0 M10 208 120 220 127 30 102 150 3W N G 175 1 2 0 1 4 0 M10 208 120 220 127 40 136 175 3W N G 230 1 4 0 2 1 0 M10 208 120 220 127 60 205 300 3W N G 400 2 3 0 2 4 0...

Page 47: ...220 127 20 56 70 3W N G 115 1 2 1 2 M10 208 120 220 127 30 83 110 3W N G 130 1 1 0 1 2 0 M10 208 120 220 127 40 111 150 3W N G 175 1 3 0 1 4 0 M10 208 120 220 127 60 167 225 3W N G 285 2 300 2 2 0 M10...

Page 48: ...27 60 167 3W N G 225 285 2 300kcmil 2 2 0 M10 208 120 220 127 80 222 3W N G 300 400 2 3 0 2 4 0 M10 208 120 220 127 100 278 3W N G 350 460 2 4 0 2 300kcmil M10 208 120 220 127 120 333 3W N G 450 620 2...

Page 49: ...256 030695 868 4AWG 256 030695 733 2 3AWG 54811BE 1AWG 54857BE 1 0AWG 256 30695 593 2 0AWG 54862BE 60238 3 0AWG 54864BE 60244 4 0AWG 54866BE 60250 250kcmil 54868BE 60256 300kcmil 54870BE 60262 350kcm...

Page 50: ...Vertiv Liebert EXM MBC Installation Manual 44 NOTE Refer to the manufacturer s data for proper torque for circuit breaker power connections...

Page 51: ...Vertiv Liebert EXM MBC Installation Manual 45 NOTES...

Page 52: ...Vertiv Liebert EXM MBC Installation Manual 46...