background image

Rev03 29-10-2019

 

 

Victron Energy B.V. / De Paal 35 / 1351 JG ALMERE / Nederland 

Telefoon: (+31) (0)36 535 97 00 / 

www.victronenergy.com

 / e-mail: sales@victronenergy.com 

 

BatteryProtect 48|100 

ENGLISH 

Installation 

1. The BatteryProtect (BP) must be installed in a well-ventilated area and preferably close (max 50 

cm) to the battery (but, due to possible corrosive gasses, not above the battery!). Voltage drop 

over a long or undersized cable between the battery plus and the BP may result in unexpected 

shutdown of the BP. 

2. A properly sized fuse must be inserted according to local regulations in the cable between the 

battery and the BP. 

3. The BP is designed to allow current to flow from IN (battery) to 

OUT (load) terminals only.  

Reverse currents from OUT to IN terminals are strictly forbidden, 

and will damage the device. If you wish to use the BP as a 

disconnection for a charge source, you must orient the unit in the 

system so that the current is flowing in the intended direction, IN 

to OUT. 

4. The short circuit protection of the BP will be activated if you try 

to directly connect loads with capacitors on their input (eg 

inverters). For that use case, please use the BP to control the 

remote on/off switch on the inverter, instead of disconnecting the 

higher power DC line. 

5. Use a 1,5mm² wire (included) for the minus connection, which should be connected directly to 

the battery minus. No other equipment should be connected to this wire. 

6. The BP will automatically detect the system voltage after connection of plus and minus to the 

battery. During voltage detection the 7 segment display shows a series of flashes between the top 

and lower part. 

7. Do not connect the load output until the BP has been fully programmed. 

8. A remote on-off switch can be connected to the two pole connector (see figure 1) or between 

pin 2-1 of the two pole connector and the battery plus. 

9. A buzzer, LED or relay can be connected between the alarm output and the battery plus (see 

figure 1). Maximum load on the alarm output: 50 mA (short circuit proof). 

 

Load disconnect events and alarm output options 

Buzzer or LED mode (buzzer or LED connected to the alarm output): 

  In case of under voltage, a continuous alarm will start after 12 seconds. The BP will 

disconnect the load after 90 seconds and the alarm will stop. 

  In case of over voltage, the load will be disconnected immediately and an intermittent alarm 

will remain on until the overvoltage problem has been corrected. 

Relay mode (relay connected to the alarm output): 

  In case of under voltage, the relay will engage after 12 seconds. The BP will disconnect the 

load after 90 seconds and the relay will disengage. 

  In case of over voltage, the load will be disconnected immediately and the alarm output will 

remain inactive. 

Li-ion mode: 

  Connect the load disconnect output of the VE.Bus BMS to pin 2-1. 

The load is disconnected immediately when the load disconnect output of the VE.Bus BMS 

switches from ‘high’ to ‘free floating’ (due to battery cell under voltage, over voltage or over 

temperature). The under voltage thresholds and alarm output of the BP are inactive in this 

mode. 

 

Programming 

When switched off (remote open), the BP can be programmed for the desired voltages and modes 

by connecting the PROG pin to the ground. Please see the programming table. 

The display will first step through the shutdown and restart voltages. Disconnect the PROG pin 

when the desired voltage is displayed. 

The display will confirm the chosen voltage and default mode (

) twice. 

Reconnect the PROG to ground if another mode is (

 or 

) is required. Disconnect when the 

required mode is displayed. 

The display will confirm the chosen voltage and mode twice. 

 

Operation 

There are 4 possible error modes, indicated by the 7 segment display: 

 

 

  Short circuit detected 

 

 

  Over load or over temperature 

 

 

  Under voltage 

 

 

  Over voltage 

After 5 minutes the error is no longer displayed to reduce current consumption. 

The decimal point of the 7 segment display is used for status indication: 

  On solid: the BP attempts to activate the output 

  Flash every 5s: output is active 

  Flashing every 2s in Li-ion mode: output ‘connecting’ 

Remote control and short circuit 

  The BP will connect the load 1 second after closing the remote contact. 

  The BP will disconnect the load immediately when the remote contact is opened. 

  When in Li-ion mode the BP will connect the load 30 seconds after the remote input of the BP 

has been pulled high by the VE.Bus BMS. This delay increases to 3 minutes in case of 

frequent switching. 

  In case of a short circuit, the BP will attempt to connect the load every 5 seconds. After two 

attempts the display will show 

 

 (short circuit detected). 

 

Programming table 

 

7 segment display 

Under voltage shut down 

48V system 

Under voltage restart 

48V system 

 

42V 

48V 

 

40V 

46V 

 

38V 

46V 

 

45V 

53V 

 

46V 

55,2V 

 

42V 

51,2V 

 

46V 

51,2V 

 

47,2V 

51,2V 

 

48V 

52V 

 

40V 

52,8V 

 

Buzzer or LED mode 

 

Relay mode 

 

Li-ion mode 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specifications 

 

BatteryProtect 

BP48|100 

Maximum cont. load current 

100A 

Peak current 

250  

Operating voltage range 

32–60  

Current consumption 

When on: 2mA   When off or low voltage shutdown: 1,5mA 

Alarm output delay 

12 seconds 

Max. load on alarm output 

50mA (short circuit proof) 

Load disconnect delay 

90 seconds 

(immediate if triggered by the VE.Bus BMS)

 

Default thresholds 

Disengage: 42V   Engage: 48V 

Operating temperature range 

Full load: -40°C to +40°C 

(up to 60% of nominal load at 50°C)

 

Weight 

0 , 2 kg     0 .5   l bs 

0,5kg   0.6 lbs 

0 , 8 kg     1 .8   l bs 

Dimensions (hxwxd) 

4 0   x   4 8   x   1 0 6 m m 

1.6 x 1.9 x 4.2 inch 

59 x 42 x 115mm 

2.4 x 1.7 x 4.6 inch  

62 x 123 x 120mm 

2.5 x 4.9 x 4.8 inch 

 

Example Wiring Diagrams 

 

 

 

 

 

 

 

 

 

OUT 

OUT 

IN 

IN 

OUT 

IN 

IN 

OUT 

Summary of Contents for BP48|100

Page 1: ...diately and the alarm output will remain inactive Li ion mode Connect the load disconnect output of the VE Bus BMS to pin 2 1 The load is disconnected immediately when the load disconnect output of the VE Bus BMS switches from high to free floating due to battery cell under voltage over voltage or over temperature The under voltage thresholds and alarm output of the BP are inactive in this mode Pr...

Page 2: ...ederland Telefoon 31 0 36 535 97 00 www victronenergy com e mail sales victronenergy com Connection diagram of the BP 48 100 Connector pin numbering Figure 1 Connection diagrams and pin numbering Figure 2 System with 48V Li ion battery set with 10kΩ series resistor ...

Page 3: ...tkoppelingsuitgang van de VE Bus BMS aan op pin 2 1 De belasting wordt onmiddellijk ontkoppeld wanneer de belastingontkoppelingsuitgang van de VE Bus BMS overschakelt van hoog naar potentiaalvrij als gevolg van de onderspanning overspanning of overtemperatuur in de accucel De onderspanningsdrempels en de alarmuitgang van de BP zijn in deze modus inactief Programmeren Wanneer uitgeschakeld afstands...

Page 4: ...MERE Pays Bas Téléphone 31 0 36 535 97 00 www victronenergy com e mail sales victronenergy com Aansluitschema van de BP 48 100 Connectorpinnummering Afbeelding 1 Verbindingsdiagrammen en pinnummering Figuur 2 Systeem met 48V Li ion accuset met 10kΩ serie weerstand ...

Page 5: ...ctée et la sortie de l alarme restera inactive Mode Lithium ion Connectez la sortie de déconnexion de la charge du BMS du VE Bus à la broche 2 1 La charge est immédiatement déconnectée lorsque la sortie de déconnexion de la charge du BMS du VE Bus passe de élevée à flottante car la cellule de la batterie est en sous tension surtension ou surchauffe Les seuils de sous tension et la sortie de l alar...

Page 6: ...6 535 97 00 www victronenergy com E Mail sales victronenergy com Schéma de connexion du BP 48 100 Numérotation des broches du connecteur Illustration 1 Schémas de connexion et numérotation des broches Illustration 2 Système avec batterie Li ion de 48 V avec résistance de la série 10 kΩ ...

Page 7: ... BMS S utgång för belastningsfrånkoppling till stift 2 1 Belastningen kopplas bort omedelbart när utgången för belastningsfrånkoppling på VE Bus BMS växlar från hög till fritt flytande på grund av underspänning överspänning eller övertemperatur i battericellerna Batteriskyddets underspänningströskel och larmutgång är inaktiva i detta läge Programmering När enheten är avstängd fjärr öppen kan önska...

Page 8: ...MERE Niederlande Tel 31 0 36 535 97 00 www victronenergy com E Mail sales victronenergy com Kopplingsschema för BP 48 100 Numrering av anslutningsstift Bild 1 Kopplingsscheman och stiftnumrering Bild 2 System med 48 V litiumjonbatteriset med10kΩ serieresistor ...

Page 9: ...ng wird die Last sofort abgeschaltet und der Alarmausgang bleibt nicht aktiv Lithium Ionen Modus Verbinden Sie den Ausgang für die Lastabschaltung am VE Bus BMS mit Pol 2 1 Die Last wird sofort abgeschaltet wenn der Lastabschaltausgang des VE Bus BMS von hoch auf freischwebend wechselt aufgrund von Batteriezellen unter Spannung Überspannung oder Übertemperatur Die Schwellwerte für die Unterspannun...

Page 10: ...ses Baixos Telefone 31 0 36 535 97 00 www victronenergy com e mail sales victronenergy com Anschlussplan des BP 48 100 Nummerierung der Anschlusspins Abbildung 1 Anschlusspläne und Pin Nummerierung Abbildung 2 System mit 48V Li Ionen Batteriesatz mit 10kΩ Widerstand ...

Page 11: ...rga é desligada automaticamente imediatamente e a saída do alarme continua inativa Modo Li ion Ligue a saída de corte da carga do VE BUS BMS ao pino 2 1 A carga é desligada automaticamente quando a saída de corte da carga do VE Bus BMS muda de Alto para Lenta devido a subtensão sobretensão ou sobreaquecimento da bateria O limiar de subtensão e a saída de alarme do BP estão desativados neste modo P...

Page 12: ...n 31 0 36 535 97 00 www victronenergy com e posta sales victronenergy com Esquema de ligações de BP 48 100 Numeração de pinos e conectores Figura 1 Esquema de ligações e numeração de pinos Figura 2 Sistema com conjunto de bateria de Li ion de 48 V com resistência de série 10 kΩ ...

Page 13: ... permanecerá inactiva Modo Li Ion Conectar la salida de carga por baja tensión del BMS del VE Bus al pin 2 1 La carga se desconecta inmediatamente cuando la salida de desconexión de carga por baja tensión del BMS del VE Bus conmuta de high alto a free floating flotante debido a la subtensión sobretensión o exceso de temperatura de las celdas de la batería Los umbrales de subtensión y de salida de ...

Page 14: ... 31 0 36 535 97 00 www victronenergy com e posta sales victronenergy com Diagrama de conexión del SBP 48 100 Numeración de conectores pin Figura 1 Diagramas de conexión y numeración de pines Figura 2 Sistema con juego de baterías de Li ion de 48V Con resistencia de serie de 10kΩ ...

Page 15: ...diatamente e l emissione dell allarme rimarrà inattiva Modalità Li ion Collegare l emissione di disconnessione del carico del VE Bus BMS al pin 2 1 Il carico è scollegato immediatamente quando l emissione di disconnessione del carico del VE Bus BMS passa da high a free floating a causa della sottotensione sovratensione o sovratemperatura della cella della batteria Le soglie di sottotensione e l em...

Page 16: ...fon 31 0 36 535 97 00 www victronenergy com e posta sales victronenergy com Schema di connessione del BP 48 100 Numerazione dei pin del connettore Figura 1 Schemi di connessione e numerazione dei pin Figura 2 Sistema con batteria agli ioni di litio da 48V con resistore da 10kΩ ...

Page 17: ...ıkışı devre dışı kalmaya devam eder Li ion modu VE Bus BMS in yük kesme çıkışını pim 2 1 e bağlayın VE Bus BMS in yük kesme çıkışı yüksek durumundan serbest yüzdürme durumuna geçtiğinde yük derhal kesilir akü hücresi düşük voltajı aşırı voltajı veya aşırı sıcaklığı nedeniyle BP nin düşük voltaj eşiği ve alarm çıkışı bu modda devre dışı kalır Programlama Kapalıyken uzaktan açık BP istenen voltajlar...

Page 18: ...ERE The Netherlands Phone 31 0 36 535 97 00 www victronenergy com e mail sales victronenergy com BP 48 100 Bağlantı şeması Konnektör pimi numaraları Şekil 1 Bağlantı şemaları ve pim numaraları Şekil 2 48V Li ion akü seti içeren sistem 10 kΩ serisi resistör ile ...

Reviews: