background image

Technical Data Manual

5782 590 - 02  01/2015

Model Nos. and pricing: see Price List

VITOSOL 200-T 

Type SP2A

Vacuum tube collector

For the heating of DHW, supplement heating systems 

and swimming pool water via heat exchangers as well 

as for the generation of process heat.

For installation on pitched and flat roofs, as well as for 

freestanding installations and on walls.

VITOSOL

 

r

 200-T SP2A

Product may not be exactly as shown

Vacuum tube collector based on the heat pipe principle

For the utilisation of solar energy

Summary of Contents for VITOSOL 200-T SP2A

Page 1: ...ment heating systems and swimming pool water via heat exchangers as well as for the generation of process heat For installation on pitched and flat roofs as well as for freestanding installations and on walls VITOSOLr 200 T SP2A Product may not be exactly as shown Vacuum tube collector based on the heat pipe principle For the utilisation of solar energy ...

Page 2: ...r horizontally tubes parallel to the roof ridge A highly selectively coated metal absorber is incorporated inside each vacuum tube It ensures high absorption of insolation and low emissions of thermal radiation A heat pipe filled with an evaporation liquid is arranged on the absorber The heat pipe is connected to the condenser The condenser is located inside the Duotec double pipe heat exchanger m...

Page 3: ...2 2241 5 9 150 The following values apply to the absorber area as tested by TUV testing laboratories in Europe Optical efficiency Heat loss factor k1 Heat loss factor k2 k1 W m2 K k1 W m2 K2 78 5 1 42 0 005 78 5 1 42 0 005 78 5 1 42 0 005 Thermal capacity kJ m2 K 8 4 8 4 8 4 Weight lb kg 73 33 86 39 174 79 Liquid content heat transfer medium USG L 0 198 0 75 0 23 0 87 0 41 1 55 Permissible operati...

Page 4: ...ch additional collector Installation with roof brackets This method of fixing can be applied universally on all common roof covers The fixing system comprises roof brackets mounting rails clamping brackets and screws Forces are applied to the roof structure in various ways including via the roof brackets and the roof cover Roof covers can be very different Consequently damage cannot be completely ...

Page 5: ...Legend A Header casing B Mounting rail C Tube retainer D Mounting bracket E Roof bracket F Vacuum tube Legend A Vacuum tube B Clamping bracket C Tube retainer D Mounting rail E Roof bracket F Header casing G Mounting plate Refer to the Vitosol 200 T SP2A Installation Instructions for all mounting hardware dimensions and detailed installation instructions ...

Page 6: ...ports with fixed angle of inclination Angle of inclination 30 45 60 a in mm 95 2413 86 6 2200 72 4 1838 Vertical tube installation elevated Ballast and max load on the substructure Calculation in accordance with DIN 1055 4 3 2005 and DIN 1055 5 7 2005 or applicable local codes Two support slabs each both A and B are required for every collector Ballast weight requirements as well as the calculatio...

Page 7: ...t be avoided when collectors are arranged behind one another To keep the reduction in yield within acceptable parameters observe specific row clearances dimension z When the sun is at its highest on the shortest day of the year 21 12 the rows at the back should be free of shading The angle of the sun at midday on 21 12 must be used to calculate the row clearance z sin 180 h sin z 2241 mm sin 180 6...

Page 8: ...Two support slabs each both A and B are required for every collector Ballast weight requirements as well as the calculation of additional live loads due to installation of solar collectors must be evaluated by a professional structural engineer A Support slabs A B Support slabs B Installation on Walls Horizontal installation on walls For installation on balconies there is a special 10 tube 1 26 m2...

Page 9: ...ght A Collector temperature sensor Installation in several rows connection from the left or right A Collector temperature sensor Horizontal installation on a sloped roof or wall mount Single sided connection from below required U pipe fitting with integrated air vent must be used 1 collector array With this type of connection the Evacuated tube collector function at the SCU control must be enabled...

Page 10: ...gn Information Pressure Drop A 1 26 1 51 m2 B 3 03 m2 Flow Rate Pressure Drop Relative to water corresponds to Tyfocor LS at approximately 140 F 60 C Note For multiple collector arrays use the total flow for the whole array to calculate the pressure drop ...

Page 11: ... L min Medium flow mode USG min L min Low flow mode USG min L min Model 1 26 m2 10 tube collector 0 55 2 1 NR NR Model 1 51 m2 12 tube collector 0 6 2 3 0 4 1 5 NR Model 3 03 m2 24 tube collector 0 86 3 3 0 67 2 5 0 47 1 78 Individual collector flow rates Recommended collector array flow rates Flow High flow mode USG min L min Medium flow mode USG min L min Low flow mode USG min L min 10 tube coll...

Page 12: ...Vitosol 200 T SP2A Technical Data 5782 590 02 Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper ...

Reviews: