ESFR DRY PENDENT SPRINKLER 

VK512 K25.2 (GROOVED)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: techsvcs@vikingcorp.com

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 1 of 8

Form No. F_071221    Rev 001    12.10.2021

1. DESCRIPTION

Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK512 is

a fast response fusible element type sprinkler designed for use in storage areas

subject to freezing and supplied from a wet system only, in an adjacent heated

area. With a 25.2 (363 metric) nominal K-Factor and special deflector, this sprinkler

produces large, high-momentum water droplets in a hemispheric pattern below

the deflector. This permits penetration of the fire plume and direct wetting of the

burning fuel surface while cooling the atmosphere early in the development of a

high-challenge fire.

The dry ESFR sprinkler consists of a fusible element style ESFR sprinkler

permanently secured to a special supply nipple. The sprinkler assembly features

a sealed brass inlet that’s grooved. Also included with the ESFR dry sprinkler are

two insulating boot assemblies (optional) to help seal the clearance space around

the dry sprinkler barrel. The dry sprinkler boot assembly is intended to slow the

exchange of air between the inside and outside of the freezer (or any dry sprinkler

installation) to help mitigate condensation and humidity and temperature differentials

in the area around the sprinkler. Condensation can lead to ice build-up, which could

inhibit sprinkler operation or cause premature operation.

2. LISTINGS AND APPROVALS*

FM Approved

: Class 2026

* Refer to the Approval Chart and Design Criteria for requirements that must be followed.

3.

*

TECHNICAL DATA

Specifications:

Available since 2022

Tube diameter: 1-11/16" (43.86 mm)

Minimum Operating Pressure: Refer to NFPA 13 and FM Loss Prevention Data Sheet 8-9.

Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500

psi (34.5 bar).

Connections: 1-1/2" grooved

Nominal K-Factor: 25.2 U.S. (363 metric*)

Metric K-factor measurement shown is when pressure is measured in bar. When pressure is 

measured in kPa, divide the metric K-factor shown by 10.0.

Deflector Diameter: 1-3/4" (44.5 mm)

Overall Length: Refer to Table 1.

Sprinkler Assembly Materials of Con

s

truction:

Sprinkler Frame Casting: QM Brass

Deflector: Phosphor Bronze UNS-C51000

Seat: Brass UNS-C36000

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Spring Base: Brass UNS-C31400 or UNS-C31600

Back-Up Nut: Brass UNS-C36000

Compression Screw: Stainless Steel UNS-S31603

Trigger and Support: Stainless Steel UNS-S31600

Fusible Element Assembly: Beryllium Nickel, coated with acrylic paint

Tube: Steel Tube ASTM A-513

Orifice: Brass UNS-C36000

Inlet: Brass UNS-C84400

Support (Internal): Brass UNS-C36000

Barrel: Steel Tube ASTM A-513, Electrodeposited Epoxy Base finish

Boot Assembly Materials of Con

s

truction:

Seal: ASTM D1056 2A0/1 4015-EL EPDM-Butyl-PE Foam Rubber OR ASTM D1056 2A1 Neoprene/EPDM/SBR OR ASTM D1056

 

2C1 Neoprene/EPDM

Over Seal Ring and Under Seal Ring: Cold Rolled Steel Finish: White Paint; #10 Screws: Stainless Steel

New form.

Summary of Contents for VK512

Page 1: ...re differentials in the area around the sprinkler Condensation can lead to ice build up which could inhibit sprinkler operation or cause premature operation 2 LISTINGS AND APPROVALS FM Approved Class 2026 Refer to the Approval Chart and Design Criteria for requirements that must be followed 3 TECHNICAL DATA Specifications Available since 2022 Tube diameter 1 11 16 43 86 mm Minimum Operating Pressu...

Page 2: ...g This sprinkler is to be installed into an area with a maximum ambient temperature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler TABLE 1 BASE PART NUMNBER 1 Available Part Numbers and Styles Base Part Number Nominal Length L Connection Style Connection Size 24850A 191 2 495 mm Grooved 11 2 24853A ...

Page 3: ... must be provided with adequate heat NOTICE Viking ESFR Dry Sprinklers shall be installed into the 1 1 2 grooved run of tee fittings that meet the dimensional require ments of ANSI B16 3 Class 150 The VK512 can be installed into welded outlets that meet the dimensional requirements of ANSI B16 11 WARNING Viking sprinklers are manufactured and tested to meet the rigid requirements of the approving ...

Page 4: ...5 Lubricate or seal the gaskets on the grroved coupling as necessary 6 Secure the sprinkler in place with a suitable grooved coupling 7 Clean the contact surfaces for the insulating boot NOTE When installing insulating boots pilot holes are required in metallic ceilings 8 Carefully pull apart the rubber rings A to install onto the barrel 9 Place the 2 halves of the seal casing B on either side of ...

Page 5: ...atest edition of this technical data page www vikinggroupinc com Page 5 of 8 Form No F_071221 Rev 001 12 10 2021 Fill space with one part expandable foam Fill space with one part expandable foam Figure 3 Recommended Sealing Methods Option 1 Option 3 Option 2 8 Jacket insulation maximum above deck penetration 6 Minimum Exposed Length at connection Insulated ceiling structure Minimum 31 2 clearance ...

Page 6: ...4 Maintain a minimum 12 300 mm vertical distance between the top of the area s ceiling and the overhead sprinkler piping that will feed the dry pendent sprinklers 5 5 2 NFPA Requirement for Minimum Exposed Barrel Lengths Refer to the latest edition of NFPA 13 Where dry sprinklers are connected to wet pipe sprinkler systems protecting areas subject to freezing temperatures the minimum exposed lengt...

Page 7: ...ble at the time of printing Other approvals may be in process IMPORTANT Refer to Bulletin Form No F_091699 Care and Handling of Sprinklers Also refer to Table 2 TABLE 4 COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR MODEL VK512 ESFR PENDENT SPRINKLERS Storage Type NFPA FM Sprinkler Type ESFR Storage Response Type ESFR QR System Type Wet Pipe system only Wet Pipe system only Temperature Ratin...

Page 8: ...ons may vary due to corrosive atmospheres water supplies and activity around the device B Sprinklers that have been painted or mechanically damaged must be replaced immediately Sprinklers showing signs of corrosion shall be tested and or replaced immediately as required Installation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to the i...

Page 9: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 10: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 11: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 12: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 13: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Page 14: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Page 15: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Page 16: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...