Installation and Operating Instructions

Read this instruction sheet thoroughly before installation and use of the SMD-429 PG2

Introduction

The SMD- 429 PG2 is a wireless photoelectric smoke and heat detector with a fixed tem-
perature and rate of rise heat detector, and an internal piezoelectric alarm.
Three versions are available: a 915 MHz for US version (UL) and Canadian version (ULC), a
433 MHz and 868 MHz for International version (EU) and a 433 MHz for Australian version
(AUS).

Compatible Devices

The smoke detector is compatible with Visonic Control Panels and Power G receivers.

HUSH/TEST BUTTON

Operation

Approximately every 7 to 8 seconds the unit tests for a smoke or heat alarm condition. During
this sequence the unit also performs self diagnostics, and checks for tampers and faults. During
normal operation the green LED flashes every 12 seconds and the sounder does not sound.

Smoke Alarm

The smoke detector alarms when the signal level exceeds the “alarm” threshold and auto-
matically restores when the signal level falls below the alarm “restore” threshold. During an
alarm the LED flashes once per second and the sounder sounds the evacuation temporal pat-
tern.

Alarm Silencing

This smoke alarm is provided with an automatically resettable alarm silencing feature. When the
sensor is in alarm, press the Test/Silence/Reset button to silence the local annunciation of the
alarm and transmit an alarm restore event to the control panel. The LED flashes every 8
seconds for up to 10 minutes, to indicate the alarm has been silenced.
The flashing LED stops when the unit returns to normal operation. The alarm silence feature
has a fixed time setting that desensitizes the smoke alarm for 8 minutes.
Alarm silencing does not disable the smoke alarm but rather reduces its smoke sensitivity. Fol-
lowing the silenced period the smoke alarm restores automatically to its intended operation. If
smoke around the unit is dense enough to suggest a potentially dangerous situation, it remains
in alarm, or may return to the alarm state quickly.

Detector Trouble

When the detector has a general fault, the yellow LED blinks once every four seconds and
there is a chirp every 48 seconds. After 12 hours, the panel will display a loss of supervision
message.

Status

LEDs

Sounder

(do not pulse the sounder and

LED concurrently)

Normal

Green flash every 12 seconds

Off

Heat Alarm Red flash every 1 second

ANSI S3.41 temporal 3

Heat Test

Red flash every 1 second

ANSI S3.41 temporal 3

Smoke
Alarm

Red flash every 1 second

ANSI S3.41 temporal 3
(press button to hush for 5-10 minutes)

Smoke Test Red flash every 1 second

ANSI S3.41 temporal 3
(press button to hush for 5-10 minutes)

Test Alarm

Red flash every 1 second

ANSI S3.41 temporal 3

Detector
Trouble

Yellow flash every 4 seconds

One chirp every 48 seconds

SMD-429 PG2 Series Wireless Smoke and Heat Detector

Summary of Contents for SMD-429 PG2 Series

Page 1: ...Reset button to silence the local annunciation of the alarm and transmit an alarm restore event to the control panel The LED flashes every 8 seconds for up to 10 minutes to indicate the alarm has bee...

Page 2: ...indicator the red LED blinks once per minute You can clear the alarm restore indicator only from the control panel l Tamper Tamper Restore tamper switch activated 10 second maximum delay on restore b...

Page 3: ...eyond those required for minimum protection be installed Additional areas that should be protected include the basement bedrooms especially where smokers sleep dining rooms furnace and utility rooms a...

Page 4: ...station Initiate test by pressing the test button for 5 seconds minimum Alarm activation is indicated by the flashing LED the sounder and transmission of the alarm signal to the control panel The dete...

Page 5: ...led clean and in good working order If in doubt have a professional evaluation Family Escape Planning There is often very little time between the detection of a fire and the time it becomes deadly Bec...

Page 6: ...eleased the following sequence of events occur l Red LED lights for 0 5 s off for 0 5 s l Yellow LED lights for 0 5 s off for 0 5 s This is followed by 3 loud alarm beeps and at the same time the red...

Page 7: ...ms Not Covered by Warranty In addition to the items which void the Warranty the following items shall not be covered by Warranty i freight cost to the repair centre ii customs fees taxes or VAT that m...

Page 8: ...ts the media and printed materials any upgrades and this EULA iii if you do not retain any copies of any portion of the Software iv if the recipient agrees to the terms of this EULA and v if the Softw...

Page 9: ...anual of the alarm control panel All the instructions specified within that manual must be observed FCC and IC Compliance Statement CAUTION Changes or modifications not expressly approved by Visonic c...

Reviews: