Electric Strike, Double Door Open Back Mortise or Cylindrical
Application
6225
Installation Instructions
Figure 1
5.
Install strike with two #12-24 screws. Make sure clearance
between latch bolt and strike lip is 1/32” (Figure 2). If not,
uninstall strike, adjust (Figure 3), and reinstall.
6.
Test door: With strike unlocked, door opens with latch bolt
extended. When door closes, latch bolt rides over strike lip.
89/336/EEC
Notes:
Deadbolt will not function with this strike.
Check with factory for
applications.
1.
For lock or device preparation, see their directions.
2.
Prepare door for strike (see other side).
3.
Wire strike (Figure 1).
4.
Test strike: Apply solenoid power. Fail secure (FSE)
lip unlocks. Fail safe (FS) lip locks.
DC input is
nonpolarized.
NOTE
!
J1
P1
P1 J1A
P1A
SO-12 or SO-24
12 VDC
or
24 VDC
12 VAC
SO-12 12 VDC
or
24 VAC
SO-24 24 VDC
{
{
Wiring
for DC
supply
Wiring
for AC
supply
Solenoid
Use crimp
connectors to
splice
wiring
to P1 leads
Yellow solenoid wires = 12 VDC, 0.57 A
Black solenoid wires = 24 VDC, 0.29 A
(also shown on strike label)
SOLENOID POWER REQUIREMENTS
Figure 2
Top view;
faceplate not
shown for clarity
1/32”
Latch bolt
Strike lip
Figure 3
To adjust strike,
loosen screws
A, B,
and
C
and move
backbox sideways as
necessary
A
B
C
931
238
_5
931
238
_5
931
238
_5
931
238
_5
931
238
_5
PREP
UBL
ICAT
ION
REV
IEW
COP
Y RE
V. A
NOTE:
Static Strength Rating 1500 lb.
Dynamic Strength Rating 70ft.-lb.
Endurance Rating 250,000 c.
© Allegion 2014
Printed in U.S.A.
931238-00 Rev. 01/14-b