(SAVE THESE INSTRUCTIONS) 

This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read 

and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, 

or operate. 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a  temperature  and  humidity  controlled  indoor  area  free  of  conductive 

contaminants.    (Please see specifications for acceptable temperature and humidity range). 

CAUTION!   

To  reduce  the  risk  of  electric  shock,  do  not  remove  the  cover  except  to  service  the  battery.  Turn  off  and  unplug  the  unit  before 

servicing the batteries. There are no user serviceable parts inside except for the battery. 

CAUTION!   

Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. 

CAUTION!   

The

 

UPS  must  be  connected to  an  AC  power  outlet  with  fuse  or  circuit  breaker  protection.  Do  not  plug into  an  outlet  that  is  not 

grounded.    If you need to de-energize this equipment, turn off and unplug the unit. 

CAUTION!   

To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer 

component. 

CAUTION!

    Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, 

ANSI/NFPA 75. 

CAUTION!

    To  reduce  the  risk  of  fire,  connect  only  to  a  circuit  provided  with  20  amperes  maximum  branch  circuit over  current  protection in 

accordance with the National Electric Code, ANSI/NFPA 70. 

CAUTION!    DO  NOT  USE  FOR  MEDICAL  OR  LIFE  SUPPORT  EQUIPMENT!   

ADI  does  not  sell  UPS  products  for  life  support  or  medical 

applications. 

DO  NOT

  use  in  any  circumstance  that  would  affect  the  operation  and  safety  of  life  support  equipment,  medical  applications,  or 

patient care. 

CAUTION!    DO NOT USE WITH OR NEAR AQUARIUMS!   

To reduce the risk of fire or electric shock, do not use with or near an aquarium.

   

Condensation from the aquarium can cause the unit to short out. 

CAUTION!    DO NOT USE THE UPS ON ANY TRANSPORTATION!   

To reduce the risk of fire or electric shock, do not use the unit on any 

transportation such as airplanes or ships.

 

The effect of shock or vibration caused during transit and the damp environment can cause the unit to 

short out. 

  WARNING!   

This product can expose you to chemicals including Styrene, and Bisphenol-A, which is known to the State of California to 

cause cancer, birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov. 
 

 

 

UNPACKING 

Inspect the UPS upon receipt. The box should contain the following: 

(a) UPS unit (b) 

User’s manual (c) USB device cable (d) Software download card 

 

AUTOMATIC VOLTAGE REGULATOR

 

The 0E-825V12VRD stabilizes inconsistent utility power to nominal levels that are safe for equipment. 

Unstable utility power can be damaging to important data and hardware. With Automatic Voltage Regulation 

(AVR), damaging voltage levels are corrected to safe levels. AVR automatically increases low utility power to 

a consistent and safe 110/120 volts. 

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT

 

1.  Ensure that the equipment plugged into the UPS does not e

xceed the UPS unit’s rated capacity. If the rated capacities of the unit are 

exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip. 

2.  There are many factors that can affect the amount of power that your electronic equipment will require. For optimal system performance keep 

the load below 80% of the unit’s rated capacity. 

HARDWARE INSTALLATION GUIDE 

1.  Your new UPS may be used immediately upon receipt. However, after receiving a new UPS, 

to ensure the battery

’s maximum charge capacity, it is recommended that you charge the 

battery for at least 8 hours. Your UPS is equipped with an auto-charge feature. When the 

UPS is plugged into an AC outlet, the battery will automatically charge whether the UPS is 

turned on or turned off. 

2.  With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals 

requiring battery backup into the battery power supplied outlets. Plug the other peripheral equipment (eg. 

printer, scanner, speakers, etc.) into the full-time surge protection outlets.   

DO NOT plug a laser printer, 

paper shredder, copier, space heater, vacuum cleaner, sump pump, or other large electrical device into 

the 

“Battery and Surge Protected Outlets”. The power demands of these devices will overload and 

possibly damage the unit. 

3.  To protect a fax, phone, or modem line, connect a telephone cable from the wall jack outlet to the IN jack of the 

UPS. Connect a telephone cable from one of the UPS OUT jacks to the modem port on the computer. The 

other UPS OUT jack can be used to protect a telephone or fax machine. 

4.  Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is 

protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air   

conditioner, refrigerator, copier, etc.). The warranty prohibits the use of extension cords, outlet strips, and 

surge strips in conjunction with the UPS unit. 

5.  Press the power switch to turn the unit on. The Power On indicator light will illuminate green 

and the unit will “beep” once.   

6.  If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at 

least one piece of equipment from the battery power supplied outlets.    Make sure the circuit breaker is depressed and then turn the UPS on. 

7.  To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 

8.  To store the UPS for an extended period of time, cover it and store with the battery fully charged. While in storage, recharge the battery every 

three months to ensure optimal battery life. 

9.  Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility. 

 

 

DESCRIPTION 

 

 

 

 

 

 

 

 

 

 

 

1. 

Battery and Surge Protected Outlets 

The UPS has six battery powered and surge protected outlets to ensure temporary uninterrupted operation of your equipment during a 

power failure. 

(DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum cleaner, sump pump, or other large 

electrical device into the 

“Battery and Surge Protected Outlets.” The power demands of these devices will overload and possibly 

damage the unit.) 

2. 

Full-Time Surge Protection Outlets 

The UPS has six surge suppression outlets.   

3. 

LCD module display 

LCD display shows all the UPS information using icons and messages. For more information please review the 

“Definitions for Illuminated 

LCD Indicators

” section. 

4. 

Power Switch 

To turn the UPS 

ON

, press the power button for approximately 2 seconds - you will hear a constant tone (1 second) - and release after a 

short beep. 

To turn the UPS 

OFF

, press the power button for approximately 2 seconds - you will hear a constant tone (1 second) - and release after two 

short beeps. 

Alarm setting: The audible alarm can be turned

 Off or On 

by quickly pressing the POWER button twice. The default setting is for the Alarm 

On. To turn the Alarm Off, quickly press the power button twice. You will hear two short beeps when the Alarm is turned Off. To turn the Alarm 

back On, quickly press the power button twice. You will hear a single short beep when the Alarm is turned On. *When the Alarm is turned Off, 

there will be no audible notification when the UPS reaches a low battery state.

 

5. 

Power On Indicator 

This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes. 

6. 

Mode Switch   

Press the Mode Switch for approximately 3 seconds to enter setup mode to select three functions: Utility High Voltage Range, Utility Low 

Voltage Range, and LCD sleep ON/OFF. When a function is selected, press Mode Switch for 3 seconds to view options. When an option is 

selected, wait for 8 seconds for the setting to be confirmed. After the setting has been confirmed the LCD screen will leave setup mode and 

go back to status display. If there is no action for 8 seconds during setup, the LCD will also leave setup mode and go back to the status 

display. 

a.  Utility High Voltage Range: Adjust the value of high voltage range. 

b.  Utility Low Voltage Range: Adjust the value of low voltage range. 

c.  LCD: L1/L0 (ON/OFF): 

* When LCD is set to L1, LCD will be always ON. When LCD is set to L0, LCD will dim if untouched for 1 minute. 

* In battery mode, LCD is always on regardless if the setting is L1 or L0. 

7.  USB Port   

The USB port allows connection and communication between the USB port on the computer and the UPS unit. 

8. 

Communication Protection Ports 

Communication protection ports will protect any standard modem, fax, or telephone line. (RJ11) 

9. 

Circuit Breaker 

Located on the side of the UPS, the circuit breaker provides overload and fault protection.   

10.  Ground Screw 

     

  The ground screw is used for any equipment that needs a chassis ground connection.

 

11.  Outlets Designed for AC Adapters 

The UPS unit has four widely-spaced outlets. AC power adapters can be plugged into the UPS without overlapping or blocking adjacent 

outlets. 
 

REPLACING THE BATTERY 

 

Replacement of batteries located in an 

OPERATOR ACCESS AREA

1. 

When replacing batteries, replace with the same number of the following battery: BB / HRC1234W or LEOCH / DJW12-9 for 

0E-825V12VRD. 

2. 

CAUTION! Risk of Energy Hazard, 12V, maximum 9 Ampere-hour battery. Before replacing batteries, remove conductive jewelry such as 

chains, wrist watches, and rings.

 

High energy through conductive materials could cause severe burns. 

3. 

CAUTION! 

  Do not dispose of batteries in a fire. The batteries may explode. 

4. 

CAUTION! 

  Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic. 

CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING 

TO LOCAL REGULATIONS. 

 

TO REPLACE THE BATTERY 

1.  Turn off and unplug all connected equipment. 

2.  Unplug it from the AC power source. 

3.  Turn the UPS upside down. 

4.  Remove the 1 retaining screw. 

5.  Slide the battery compartment cover completely off of the unit. 

6.  Remove the battery from the compartment. 

7.  Disconnect the battery wires from the battery. 

8.  Install the replacement battery by connecting the red wire and black wire to the positive (+) and negative (-) terminal of the battery. 

9.  Put the battery back into the compartment. 

10.  Slide back the battery compartment cover and tighten the retaining screw. 

11.  Charge the unit for 8 hours to fully charge the battery. 

REMINDER:   

Batteries are considered 

HAZARDOUS WASTE

 and must be disposed of properly.    Most retailers that sell lead-acid batteries 

collects used batteries for recycling, as required by local regulations. 

 

 

 

 

Problem

 

Possible Cause 

Solution

 

Full-time surge protection outlets 
stop providing power to 
equipment. Circuit breaker 
button is projecting from the side 
of the unit.

 

Circuit breaker has been tripped due 
to an overload. 

Turn the UPS off and unplug at least one piece of 
equipment.    Wait 10 seconds, reset the circuit breaker by 
pressing the button, and then turn the UPS on.

 

The UPS does not perform 
expected runtime. 

Battery not fully charged. 

Recharge the battery by leaving the UPS plugged in. 

Battery is worn out. 

Contact ADI/W Box Technologies US 1-800-233-6261; 
Canada 877-234-7378; PR 787-793-8830 

The UPS will not turn on. 

The on/off switch is designed to 
prevent damage from rapidly turning 
it off and on. 

Turn the UPS off. Wait 10 seconds and then turn the UPS 
on. 

The unit is not connected to an AC 
outlet. 

The unit must be connected to a 120V 60Hz outlet. 

The battery is worn out. 

Contact ADI/W Box Technologies US 1-800-233-6261; 
Canada 877-234-7378; PR 787-793-8830 

Mechanical problem. 

Contact ADI/W Box Technologies US 1-800-233-6261; 
Canada 877-234-7378; PR 787-793-8830 

The frequency is outside of the 
operating range of 57-63Hz. 

Turn the UPS off. Make sure the frequency range is within 
57-63Hz. Or you can turn the UPS on in battery mode. 

Downloadable power 
management software is inactive 
(all icons are gray). 
 

The USB cable is not connected. 

Connect the USB cable to the UPS unit and an open USB 
port on the back of the computer. 

The USB cable is connected to a 
bad USB port. 

Check for a different USB port and plug the cable in. 

The unit is not providing battery 
power. 

Shutdown your computer and turn the UPS off.    Wait 10 
seconds and turn the UPS back on.    This should reset the 
unit. 

 

DEFINITIONS FOR LED INDICATORS & AUDIBLE ALARMS 

 

 

Power 

 

Alarm 

CONDITION 

On 

Off 

Normal 

On 

Beeps twice   

every 30 seconds 

Utility  Failure- 

The  UPS  is  providing  power  to  battery  power-supplied  outlets  from  its 

battery. 

On 

Rapid beeping 

every 1/2 second 

Utility Failure-

 The UPS is providing battery power.    Rapid beeping indicates the unit will 

run out of power soon. 

 

 

 
 
 
 

 

 

0E-825V12VRD 

User

’s Manual 

K01-1101016-01 

BASIC OPERATION 

INSTALLING YOUR UPS SYSTEM 

TROUBLESHOOTING 

IMPORTANT SAFETY INSTRUCTIONS 

 

 