background image

SPECIFICATIONS
Input Signal: 

4 to 20 mA DC.

Input Impedance:

250 ±15 Ω.

Material:

Aluminum diecasting.

Air Supply:

20 to 101 psig (1.4 to 7.0

bar).

Air Supply Connection:

1/4˝ NPT.

Gage Connection:

1/8˝ NPT.

Electrical Connection:

Screw

Terminal.

Conduit Connection: 

1/2˝ NPT.

Linearity:

±0.2% of FS.

Hysteresis:

1% of FS.

Sensitivity:

±0.2% of FS.

Repeatability:

±0.5% of FS.

Air Consumption:

0.10 scfm (3 LPM)

at 20 psig (1.4 bar) supply.

Flow Capacity:

28 scfm (80 LPM) at

20 psig (1.4 bar) supply.

Stroke:

0.5 to 6˝ (10 to 150 mm).

Enclosure Rating:

IP66.

Operating Temperature:

165EL: -4 to 158°F (-20 to 70°C);
165EL-SS: -40 to 158°F (-40 to 
70°C);
165EL-FM: -4 to 140°F (-20 to 
60°C).

Weight:

165EL: 6.1 lb (2.7 kg);

165EL-SS: 12.6 lb (5.7 kg).

Agency Approvals: 

CE (165EL

only), FM (165EL only).

W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.

P.O. BOX 358 • MICHIGAN CITY, INDIANA 46360 U.S.A.

Phone: 219/879-8000

www.dwyer-inst.com

Fax: 219/872-9057

e-mail: info@dwyer-inst.com

The Series 165EL PRECISOR

®

II Electro-Pneumatic Positioner 

is used for lin-

ear operation of pneumatic linear valve actuators by means of electrical controller
or control systems with an analog output signal of 4 to 20 mA or split ranges.    

FEATURES

• There is no resonance in the range of 5 to 200 Hz.
• Perform 1/2 split control without any other substitutes.
• Easy to adjust zero and span.
• Easy to convert from reverse action to direct action or vice versa.
• Easy feedback connection.
• Fast and accurate response.
• Low air consumption.
• Designed as multi-port type for air tubing.
• Easy to install air tubing connection in any direction.
• Designed as block build structure for maintenance and repair.

STRUCTURE

Series 165EL PRECISOR

®

II Electro-Pneumatic Linear Positioner

Specifications - Installation and Operating Instructions

Bulletin F-90

TM

SPAN UNIT

TORQUE MORTOR

ZERO UNIT

BASE BODY

PILOT VALVE

FEEDBACK SHAFT

FEEDBACK LEVER

VENT UNIT

BASE COVER

JUNCTION BOX

PRINCIPLE OF OPERATION

Increase the input current signal to change lift position of valve. Force exerted by
(1) Torque Motor reduces Nozzle Back Pressure with increase in gap between (2)
Flapper and (3) Nozzle. Then (5) Spool moves upward and the (7) Seat opens
simultaneously. Air pressure of OUT1 pipe is discharged to (10) Actuator. As pres-
sure in the actuator chamber goes up, (12) Actuator Stem starts to move. The
movement of (12) Actuator Stem exerts force to the (a) Feedback Spring through
Feedback Shaft connections. Then (10) Actuator will stop at the point of force bal-
ance exerted by the input current signal and the feedback spring.

SP

AR

E

30

20

40

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

INPUT SIGNAL

4 ~ 20 mA

E

OUT1

OUT2

SUPPLY

STAINLESS STEEL VERSION

STANDARD VERSION

8-3/4

[225.30]

6-9/16

[166.69]

2X M8X1.25

4-19/32

[116.69]

1-25/32

[45.24]

1-31/32

[50.01]

4X M8X1.25

2-3/4

[69.85]

3-19/32

[91.29]

2X M8X1.25

4X M8X1.25

6-9/16

[166.69]

1-25/32

[45.24]

6-43/64

[169.47]

4-41/64

[117.87]

3-5/8

[92.08]

2-49/64

[70.25]

1-31/32

[50.01]

Summary of Contents for PRECISOR II 165EL Series

Page 1: ...rect action or vice versa Easy feedback connection Fast and accurate response Low air consumption Designed as multi port type for air tubing Easy to install air tubing connection in any direction Designed as block build structure for maintenance and repair STRUCTURE Series 165EL PRECISOR II Electro Pneumatic Linear Positioner Specifications Installation and Operating Instructions Bulletin F 90 TM ...

Page 2: ... hexagonal nut with flange first setting the actuator to the starting position and then setting the cam reference line and the bearing contact point of span adjusting arm unit to the same position Do not apply the supply pressure when attaching the cam as otherwise it is very dan gerous When the positioner is shipped out the cam is tentatively tightened to the shaft Be sure to firmly lock the cam ...

Page 3: ...t of turning varies by actuators Do not loosen the stopper screw at this time since it is set to avoid the screw coming off Ps Supply Pressure Low Pressure Balance 0 4 0 5 Ps Med Pressure Balance 0 5 Ps High Pressure Balance 0 9 1 0 Ps Normal Balanced Point Balanced Point Balanced Point Input Pressure Output Pressure Output Pressure Output Pressure MAINTENANCE If the supply air is fouled the posit...

Page 4: ...ng contact or search of Flapper Clogged fixed orifice Clogged nozzle Off positioned stabilizer spring Too low of actuator volume Clogged fixed orifice Wrong connection of OUT1 and OUT2 tube Wrong setting of feed back lever Wrong Zero Span Adjustment Supply pressure is unstable Wrong setting of Seat Adjuster Loose connection of actuator and positioner Cam Shaft is worn out What To Do Input or incre...

Reviews: