background image

 

 

 

Fieldbus Independent 
I/O Modules 

4 AO DC 0-10 V 
750-559(/xxx-xxx) 

Manual 

 

 
Version 1.0.6 

Summary of Contents for 750-559

Page 1: ...Fieldbus Independent I O Modules 4 AO DC 0 10 V 750 559 xxx xxx Manual Version 1 0 6 ...

Page 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be fully ex cluded we would appreciate any information or ideas at any time E Mail documentation wago com We wish to point out that the software and hardware terms as well as the trademarks of companie...

Page 3: ...ntended Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Analog Output Modules 7 2 1 1 750 559 xxx xxx 4 AO DC 0 10 V 7 2 1 1 1 Variations 7 2 1 1 2 View 7 2 1 1 3 Description 8 2 1 1 4 Display Elements 9 2 1 1 5 Schematic Diagram 9 2 1 1 6 Technical Data 10 2 1 1 7 Process Image 11 2 1 1 7 1 Standard Format 11 ...

Page 4: ...nufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual is exclusively geared to specialists having qualifications in PLC programming electrical specialists or persons instructed by electrical specialists who are also familiar with the valid standards WAG...

Page 5: ...SD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use of the device and software optimization More information References on additional literature manuals data sheets and internet pages 1 3 Number Notation Number Code Example Note Decimal 100 normal notati...

Page 6: ...D information is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in housings cabinets or in electrical operation rooms Access must only be given via a key or tool to authorized qualified personnel The relevant valid and applicable standards and guidelines con...

Page 7: ...Description 750 559 4 AO DC 0 10 V 4 Channel Analog Output Module 0 10 V 750 559 025 000 4 AO DC 0 10 V T 4 Channel Analog Output Module 0 10 V extended temperature range from 20 C to 60 C 2 1 1 2 View A1 A2 13 14 C D B A 750 559 M M A3 A4 M M B AO 2 Power jumper contacts Datacontacts Common ground Function AO 1 Common ground Common ground AO 4 AO 3 Common ground Error Fig 2 1 1 1 4 Channel Analog...

Page 8: ...ill show if there are any overload or a short circuit to ground in either channel Any configuration of the output modules is possible when designing the fieldbus node Grouping of module types is not necessary The system supply is used for the power supply of the module The field side supply voltage of 0 V and 24 V to downstream I O modules is derived from adjacent I O modules or from a supply modu...

Page 9: ...on Operational readiness and trouble free internal data bus communication off No Error 13 14 C D B A A B Fig 2 1 1 2 Display elements g055702x B red Error on Overload or short circuit to ground in one of the output channels 2 1 1 5 Schematic Diagram 750 559 1 2 3 4 5 6 7 8 AO 1 AO 2 Common ground 24V AO 3 0V Common ground AO 4 AO Logic Function 270 pF 10 nF Common ground Error Fig 2 1 1 3 4 Channe...

Page 10: ...ns W x H x L from upper edge of 35 DIN rail 12 mm x 64 mm x 100 mm Weight ca 55 g Standards and Regulations cf Chapter 2 2 of the Coupler Controller Manual EMC Immunity to interference CE acc to EN 50082 2 96 EMC Emission of interference CE acc to EN 50081 1 93 EMC Immunity to interference Ship building acc to Germanischer Lloyd 01 EMC Emission of interference Ship building acc to Germanischer Llo...

Page 11: ...B14 The three least significant bits B0 B2 are not parsed Some fieldbus systems can process the status information using by means of a status byte As the returned status byte of this output module is always zero it will not be parsed 2 1 1 7 1 Standard Format For the standard module 750 559 the numerical values ranging from 0x0000 to 0x7FFF are scaled on the output current ranging from 0 V to 10 V...

Page 12: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastraße 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com ...