background image

 

 

Manual 

 

 

 

 

WAGO-TO-PASS® 761 

TO-PASS® Compact, 8 AI, Web, MODBUS 

761-216  

Telecontrol module for fault detection/indication, 

monitoring and remote control 

Version 2.0.0  

 

 

 

 

Summary of Contents for 761-216

Page 1: ...Manual WAGO TO PASS 761 TO PASS Compact 8 AI Web MODBUS 761 216 Telecontrol module for fault detection indication monitoring and remote control Version 2 0 0...

Page 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fu...

Page 3: ...L 12 2 4 Block Rounding for GPRS Connections 12 2 5 Safety Advice Precautions 13 3 Device Description 16 3 1 Scope of Delivery 16 3 2 Use 16 3 3 View 18 3 4 Connectors 19 3 4 1 Antenna 19 3 4 2 Operat...

Page 4: ...5 2 3 2 Voltage Measurement 42 5 2 4 Digital Outputs 43 5 2 5 Analog Outputs 44 5 2 5 1 Current Measurement 44 5 2 5 2 Voltage Measurement 45 5 2 6 MODBUS Interface 46 5 2 6 1 Serial Interface for MO...

Page 5: ...8 2 2 1 Inputs Outputs 96 8 2 2 2 Counters 97 8 3 Acknowledging Error Messages 98 8 4 Switching to Standby 99 8 5 Displaying the Data Logger DSP 100 8 6 Displaying the Event Logger ESP 102 9 Diagnost...

Page 6: ...t for LIOx Variable 122 10 3 2 2 2 Data Format for LPDx Variable 122 10 3 2 2 3 Example for Logger Script Extension 123 10 3 2 3 Logger Script FW 2 33 Counter Inputs 125 10 3 2 3 1 Data Format of an L...

Page 7: ...if applicable 1 1 Validity of this Documentation This documentation is only applicable to the telecontrol module 761 216 TO PASS Compact 8 AI Web MODBUS and its variation 761 216 000 001 1 2 Copyrigh...

Page 8: ...tes a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not avoid...

Page 9: ...otes about this Documentation 9 761 216 TO PASS Compact 8 AI Web MODBUS Manual Version 2 0 0 Additional Information Refers to additional information which is not an integral part of this documentation...

Page 10: ...ata files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item from a m...

Page 11: ...automation The specialists must be familiar with the current norms and guidelines for the devices and automated environments All changes to the controller should always be carried out by qualified per...

Page 12: ...n Source GPL The TO PASS Compact telecontrol module firmware contains Open Source software under GPL According to Section 3b of GPL we offer you the source code You can obtain the source code with lic...

Page 13: ...ation repair or maintenance work Installation only in appropriate housings cabinets or in electrical operation rooms TO PASS telecontrol modules are exposed operating equipment They may only be assemb...

Page 14: ...Only qualified staff can install and maintain the TO PASS remote module and its antenna The transmitted must be off when working on or nearer to the antenna than specified below HF Exposition The exte...

Page 15: ...an enclosure being resistant to the above mentioned materials Clean tools and materials are imperative for handling devices modules Cleaning only with permitted materials Clean soiled contacts using...

Page 16: ...of signals from plants transmission preparation of values for the operator TO PASS telecontrol modules 761 216 may be used as fault indicator remote data request system data memory event logger perma...

Page 17: ...ion Standard Extended Extended Parameterizable Time request script Not implemented Not implemented Not implemented Implemented Counter inputs Not supported Not supported Not supported Supported Delay...

Page 18: ...61 216 TO PASS Compact 8 AI Web MODBUS Manual Version 2 0 0 3 3 View Figure 1 Front view Position Description 1 SIM Card insert 2 Antenna connection 3 Statusindication 4 PC interface 5 Connecting term...

Page 19: ...tors 3 4 1 Antenna The screw connector SMA socket for the GSM antenna is located at the top of the housing Figure 2 Antenna connection Observe the maximum length of the antenna cable The total length...

Page 20: ...ce LPS requirements per DIN EN 60950 1 Table 4 Terminal assignment for operating voltage Figure 3 Terminal assignment for operating voltage Connection Short name Designation 1 2 Uv Operating voltage D...

Page 21: ...nstructively no direct conduction connection between the cabinet frame or machine parts and the carrier rail Here the earth ground must be set up via an electrical conductor accordingly valid national...

Page 22: ...achieve this connect the shield over a large surface area e g WAGO shield connecting system This is especially recommended for large scale systems where equalizing current or high impulse type current...

Page 23: ...WAGO Shield Connecting System The WAGO shield connecting system consists of shield clamping saddles busbars and various mounting carriers to enable a wide variety of setups For more information on thi...

Page 24: ...Figure 5 Terminal assignment for digital inputs Connection Short name Designation 5 DI1 Digital input 1 6 DI2 Digital input 2 7 DI3 Digital input 3 8 DI4 Digital input 4 9 DI5 Digital input 5 10 DI6...

Page 25: ...nputs Table 7 Counter input pin assignments Figure 6 Counter input pin assignments Connection Short name Explanation 5 DI1 Counter input 1 configurable 6 DI2 Counter input 2 configurable 7 DI3 Counter...

Page 26: ...Figure 7 Terminal assignment for analog inputs Connection Short name Designation 13 AI1 Analog input 1 14 AI1 Analog input 1 15 AI2 Analog input 2 16 AI2 Analog input 2 17 AI3 Analog input 3 18 AI3 A...

Page 27: ...0 Analog inputs are single ended The analog inputs are single ended and the Aix connections are connected internally to the GND connections Connect shielding Shielded cables are required for analog in...

Page 28: ...voltages Only SELV PELV voltages shall be connected to the device terminals Table 9 Terminal assignment for digital outputs Figure 8 Terminal assignment for digital outputs Connection Short name Desig...

Page 29: ...als Table 10 Terminal assignment for analog outputs Figure 9 Terminal assignment for analog outputs Connection Short name Designation 29 AO1 Analog output 1 30 AO1 Analog output 1 31 AO2 Analog output...

Page 30: ...6 Not assigned 7 MODBUS RX 8 MODBUS TX 9 Not assigned Table 12 PC interface cable assignment TO PASS Telecontrol Module PC D Sub 9 Pin Description Pin Description 2 TXD 2 RXD 3 RXD 3 TXD 5 GND 5 GND C...

Page 31: ...is activated Initialization takes approx 40 s after system start up if everything is OK SMS GPRS processing Antenna is not connected the modem is searching for a network Poor GSM network the modem is...

Page 32: ...14 sol Stripped length 9 mm 10 mm 3 6 2 Supply Table 16 Technical Data Supply Operating voltage 10 V 30 VDC Nominal voltage operation with mains power 24 VDC Nominal voltage operation using battery 12...

Page 33: ...9 Technical Data MODBUS Communication MODBUS interface RS 232 MODBUS Protocol RTU MODBUS register query Input Holding Interface speed 9600 Baud 19200 Baud Interface parameters 8N2 8E1 8O1 8N1 3 6 6 Di...

Page 34: ...utput type Semiconductor outputs Output current 0 5 A 30 V DC short circuit protected Type of load Resistive inductive lamps Energy dissipation Wmax unique switching off 125 mJ Lmax 2 Wmax I2 3 6 10 A...

Page 35: ...granted for the standard version of the telecontrol module 761 216 Approval Canada Approval Croatia Approval Mexico Approval Turkey The following approvals have beeen granted for versions 761 216 000...

Page 36: ...ambient temperature of 20 C to 70 C In the event of higher or lower temperatures proper cooling or heating arrangements must be provided Please contact WAGO Kontakttechnik GmbH Co K G for assistance...

Page 37: ...ng the TO PASS telecontrol module from the DIN rail Figure 13 Removing the TO PASS telecontrol module from the DIN rail 1 Press the undersurface against the lower DIN rail edge until the TO PASS telec...

Page 38: ...connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals Terminate both solid and ferruled conductors without actuation by simply pushing them...

Page 39: ...ail The shield connection of the TO PASS telecontrol module shield terminal 38 must be connected to the DIN rail The DIN rail must have a low impedance ground see section Connections Ground 5 2 1 Digi...

Page 40: ...PELV voltages Only SELV PELV voltages shall be connected to the device terminals Connect shielding Shielded cables are recommended for the counter inputs When using shielded cables the shield must be...

Page 41: ...rminals Analog inputs are single ended The analog inputs are single ended and the Aix connections are connected internally to the GND connections Connect shielding Shielded cables are required for ana...

Page 42: ...Voltage measurement cannot be performed via multiplier at the analog inputs since the internal resistance of the TO PASS telecontrol module depends on the input current WAGO 857 Series JUMPFLEX Isolat...

Page 43: ...761 216 TO PASS Compact 8 AI Web MODBUS Manual Version 2 0 0 5 2 4 Digital Outputs Only connect SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Figure 18 Connecti...

Page 44: ...V PELV voltages Only SELV PELV voltages shall be connected to the device terminals Connect shielding Shielded cables are required for analog outputs The cable shield must be connected to the grounded...

Page 45: ...es 45 761 216 TO PASS Compact 8 AI Web MODBUS Manual Version 2 0 0 5 2 5 2 Voltage Measurement RL Load resistance RM Internal resistance of measuring device RL RM must be less than 600 With RM RL the...

Page 46: ...ces WAGO TO PASS 761 761 216 TO PASS Compact 8 AI Web MODBUS Manual Version 2 0 0 5 2 6 MODBUS Interface 5 2 6 1 Serial Interface for MODBUS and PC Figure 20 Connection example for serial interface fo...

Page 47: ...WAGO TO PASS 761 Connect Devices 47 761 216 TO PASS Compact 8 AI Web MODBUS Manual Version 2 0 0 5 2 6 2 MODBUS RS 485 Network Figure 21 Connection example for MODBUS RS 485 Network Fullduplex...

Page 48: ...r using a double click 5 Select the CD drive in which you have placed the CD with the operating software 6 Start the WAGO TO PASS_SETUP 2 17 EXE program or a newer version in the main directory on the...

Page 49: ...O PASS telecontrol module it must first be configured with the telephone number 1 Every TO PASS telecontrol module requires an SIM card for proper operation You can obtain an SIM card from any mobile...

Page 50: ...PIN button so that the TO PASS telecontrol module does not use the PIN code Also deactivate the PIN on the SIM card To do this insert the SIM card into a cell phone and under menu item Security select...

Page 51: ...g ISDN Select the type of connection for communicating with the TO PASS telecontrol module RS 232 Direct connection via RS 232 cable GSM Dial up using GSM modem on the PC Analog Dial up using analog m...

Page 52: ...COM1 COMx Here select the serial interface where the communication cable is connected with a RS 232 connection Language English German French Select the langauge for the TO PASS operator interface her...

Page 53: ...have set the type of connection for communicating with the TO PASS telecontrol module you are then able to read out the parameters of the connected module Select the menu option Edit Read Parameters...

Page 54: ...o be configured from the project tree under it select the Identity option On the right side you will find the selection field for the function the display field for the name the input field for the te...

Page 55: ...and enter the PIN number in the field provided Roaming Roaming is always activated in TO PASS telecontrol modules To select a favorite carrier click the Allow button and enter the 5 digit carrier ID i...

Page 56: ...es are sent by the TO PASS telecontrol module as SMS however they can also be sent as an e mail fax or voice mail as defined in configuration The TO PASS telecontrol module can also transmit messages...

Page 57: ...l address e g for a T Mobile SIM card 8000 receiver provider net Transmission as fax Follow the instructions from the provider for transmissions as fax messages For T Mobile or Vodafone for example en...

Page 58: ...or transmitting the data of the logger APN access In this field enter the APN access point Access Point Name for the SIM card provider e g T Mobile internet t mobile Vodafone web vodafone de The speci...

Page 59: ...Inputs Digital inputs 1 4 can be configured as counter inputs starting from Firmware Version FW 2 33 The counters count up or down from the given starting and end value With upward counting exceeding...

Page 60: ...a the visualization system This function is available starting with Firmware Version FW 2 33 Starting value In this field enter the starting value for the counter This field is only active when the in...

Page 61: ...pplications with GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the message when the digital input has been set or when the coun...

Page 62: ...ith GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the deactivation message when the digital input has been reset or when the co...

Page 63: ...llowing applies in this case DI1 20 1 DI2 21 2 DI3 22 4 and DI4 23 8 Thus for example if DI1 and DI3 are set then the binary number is 5 If only DI4 is set then the binary number is 8 In the multiplex...

Page 64: ...Enable Addresses Multiplex operation Click the button Use to enable disable multiplex operation for digital inputs DI1 DI4 If a status combination of digital inputs DI1 DI4 is fulfilled in multiplex o...

Page 65: ...Multiplex Input entry The input fields for the alarm texts pertaining to the 16 statuses are provided on the right side Figure 28 Configuring multiplex operation alarm texts Table 31 Configuring multi...

Page 66: ...alog inputs Table 32 Configuring the analog inputs Standardization Input signal Use these buttons to select the input signal for the sensor connected to the TO PASS telecontrol module Min value In thi...

Page 67: ...lue Use these buttons to select up to four analog values which can also be transmitted with the message when the analog value has violated the first upper lower limit Second value In this field enter...

Page 68: ...nects the DC voltage available at terminal 37 to the corresponding output Deactivation text In this field enter the deactivation text for the output When the TO PASS telecontrol module receives this t...

Page 69: ...output signal for the actuator connected to the TO PASS telecontrol module Min value In this field enter the starting value from which the output value is normalized This value corresponds to the min...

Page 70: ...ter the decimal point are also taken into account for switching of the analog outputs A period decimal point must be used as the separator Up to four digits are evaluated With a minimum value of 0 and...

Page 71: ...digital inputs are to be sent as error messages select the desired recipient for the respective input statuses using buttons 1 4 Click the Internet button to also transmit the message to a Web portal...

Page 72: ...216 TO PASS Compact 8 AI Web MODBUS Manual Version 2 0 0 4 Click the Internet button to also transmit the message to a Web portal In addition you can also specify the analog values that are to be tra...

Page 73: ...telecontrol module waits for an acknowledgement after transmitting an alarm SMS Acknowledgement is in the form of an SMS containing the configured response text or a simple call by the recipient to th...

Page 74: ...t the TO PASS telecontrol module from the project tree using the identifier Select the entry Repeat times under the option Special Functions The input fields for the Web interval the Web outputs and t...

Page 75: ...function is available starting with Firmware Version FW 2 33 Switching input In this field select a digital input to be used for switching of the transmission interval between Web interval Off status...

Page 76: ...times of day Time adjustment must be performed for limited SMS transmission to check the day of the week and the active time The first SMS is transmitted when the starting value for the active time on...

Page 77: ...nt Table 37 Setting the time adjustment Settings Time adjustment The TO PASS telecontrol module sends an SMS to itself and receives the current time from the provider transmitted by this SMS when the...

Page 78: ...0 7 9 MODBUS The MODBUS functionality facilitates connectivity for MODBUS interface equipped devices The devices must be configured as slave devices and are connected via PC interface As a result the...

Page 79: ...used The following formats are possible Not used no MODBUS connection 9600 8N2 RTU Input 0x04 9600 8E1 RTU Input 0x04 9600 8O1 RTU Input 0x04 9600 8N1 RTU Input 0x04 9600 8N2 RTU Holding 0x03 9600 8E1...

Page 80: ...larm under the MODBUS entry The input fields and buttons for the alarms are provided on the right side Figure 36 Configuring the MODBUS alarm Table 39 Configuring the MODBUS alarm Alarm Setting Discre...

Page 81: ...try The input fields for the addresses of the registers to be polled are provided on the right side The input fields are identical for all register groups Figure 37 Configuring the MODBUS registers Ta...

Page 82: ...the cycle time in minutes at which the process image is to be saved The process image is specific to devices and firmware used and is described in the Section Operation Data Logger DSP The data logge...

Page 83: ...u have adapted all parameters for the TO PASS telecontrol module to your requirements you have to write the parameters to the connected module Select the menu option Edit Write Parameters The software...

Page 84: ...Compact 8 AI Web MODBUS Manual Version 2 0 0 8 Operation 8 1 Remote Query of Process Values The TO PASS telecontrol module offers two options for remote inquiry of the process values available Query v...

Page 85: ...ot set 1 set 00 00mA Analog output 1 00 00mA Analog output 2 Normal Status Status text or prepaid information optional AC 99 Alarm counter displays the alarms that are still possible per hour The alar...

Page 86: ...le 44 Counter status Status Explanation 0 Digital input not configured as a counter e ZW Counter is active Counter value d ZW Counter is not active Counter value o ZW Counter overflow Counter vlaue r...

Page 87: ...lues with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mode used to dial up...

Page 88: ...line display is green Figure 39 Visualization of the process values Process values pertaining to inputs are displayed in the upper portion of the window and those pertaining to digital and analog out...

Page 89: ...The process values displayed are valid if the on line display is green Figure 40 MODBUS process values MODBUS Alarm In this line the variable for the MODBUS alarm Module Register Text is displayed wit...

Page 90: ...k the Counter button possible only when inputs have been configured as counters The process values displayed are valid when the on line indicator is highlighted in green Figure 41 Counter process valu...

Page 91: ...US Manual Version 2 0 0 8 2 Telecontrol TO PASS telecontrol modules offer the option of influencing a process remotely with the help of their analog and digital outputs There are two methods available...

Page 92: ...containing the identifier and the transmitted text Example Table 45 Example of parameters for Set DO Parameter Setting Activation text DOUT1 1 Deactivation text DOUT1 0 Turn off time 00 00 00 Send an...

Page 93: ...arameter Setting Output Signal 0 20 mA Min value 0 Max value 100 Unit Text AOUT1 Send an SMS with the text AOUT1 75 to set analog output 1 to a value of 15 mA 75 The TO PASS telecontrol module acknowl...

Page 94: ...nds for counters Control command Function Cx x 1 4 Select counter 1 4 E Activate counter D Deactivate counter R Reset counter n e g 500 Set counter value Control commands must be concluded with a semi...

Page 95: ...s with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mode used to dial up th...

Page 96: ...are displayed in the upper portion of the window and those pertaining to digital and analog outputs are displayed in the lower portion of the window Digital inputs configured as counter inputs are hi...

Page 97: ...in green Figure 43 Counter process values The counter statuses are shown at the top of the window while the counter values the starting and end values and the limits are shown at the bottom To start a...

Page 98: ...dgement SMS containing the identifier the response text and the alarm text Acknowledgement by phone call is based on the card being used Some data cards do not allow voice links meaning that acknowled...

Page 99: ...to the respective ready state This takes place with simple changeover via SMS To do this just send an SMS with the text Standby1 to the TO PASS telecontrol modules The TO PASS telecontrol module then...

Page 100: ...of the data logger using the menu item Visualization Data logger Either select all inputs or only specific inputs with the help of the selection field in the upper portion of the window All entries ar...

Page 101: ...MODBUS Manual Version 2 0 0 As an alternative you can also display all data records saved via Edit Display all data records or all new data records for the selected telecontrol module via Edit Display...

Page 102: ...o read the contents of the event logger select the menu option Edit Read all data records It is possible to display all values of the event logger with the help of the menu option Visualization Event...

Page 103: ...utputs are displayed in the lower area By pressing the buttons Output 1 Output 4 in the upper area switch digital inputs on and off A value range of 0 mA 20 mA and 4 mA 20 mA is defined for the analog...

Page 104: ...end values and the limits are shown at the bottom To start a counter click the button Activate To stop a counter click the button Deactivate To restore the counter to its starting value click the butt...

Page 105: ...direct serial link to the TO PASS telecontrol module To test the connection select the menu option Edit Test SMS GPRS The following window is displayed Figure 46 Testing the connection Select the add...

Page 106: ...k required The modem test may only be performed with a direct serial link to the TO PASS telecontrol module To test the mode select the menu item Modem Test The following window is displayed Figure 47...

Page 107: ...provider for APN access user name and password see also Section Parameter setting Addresses Under Special Functions select Repetition Time and set the WEB Interval for the cyclic transmission to the...

Page 108: ...the character 10 2 1 Example HTTP Request The HTTP request consists of both header and data string which are separated by an empty line CR LF Carriage Return Line Feed To improve readability line brea...

Page 109: ...tensions In the data set descriptions the maximum number of characters is indicated in square brackets Starting from Firmware Version 02 33 08 you can select the script version to be applied to data t...

Page 110: ...Analog input 1 Value 6 Unit 5 Alarm 1 12 A2 Analog input 2 Value 6 Unit 5 Alarm 1 13 A3 Analog input 3 Value 6 Unit 5 Alarm 1 14 A4 Analog input 4 Value 6 Unit 5 Alarm 1 15 A5 Analog input 5 Value 6...

Page 111: ...improve readability line breaks have been inserted ID TO PASS 12345 PA 0000 home 99 TI 11 05 05 14 34 21 D1 1 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA...

Page 112: ...larm 1 11 D8 Digital input 8 Value 1 Alarm 1 12 A1 Analog input 1 Value 6 Unit 5 Alarm 1 13 A2 Analog input 2 Value 6 Unit 5 Alarm 1 14 A3 Analog input 3 Value 6 Unit 5 Alarm 1 15 A4 Analog input 4 Va...

Page 113: ...n is not enabled 1 Position deviation is enabled Flag 3 0 GPS receiver is turned off 1 GPS receiver is turned on Flag 4 0 No valid position available 1 Valid position available Flag 5 0 Static mean va...

Page 114: ...n inserted ID TO PASS Ext 12345 SV 01 01 PA 0000 home 99 TI 11 05 05 12 19 51 D1 0 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA 0 A4 00 00 mA 0 A5 00 00 m...

Page 115: ...0 AO 000 0 04 00 mA C1 0 0 0 C2 r 20F5800 0 C3 r 0 0 C4 0 0 0 SQ 21 US Hello MA 00 00 0 MV 0026 0000 002E 0064 0026 0000 0054 0064 HT 1 value always 1 the device time has not been set TI entry is oper...

Page 116: ...t value reached transgressed 2 Second value reached transgressed If both values are reached simultaneously only status 2 is transmitted SQ Signal quality or modem connection without formatting Table 5...

Page 117: ...ome 99 TI 11 05 05 12 19 51 D1 0 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA 0 A4 00 00 mA 0 A5 00 00 mA 0 A6 00 00 mA 0 A7 00 00 mA 0 A8 00 00 mA 0 VS 2...

Page 118: ...mpact 8 AI Web MODBUS Manual Version 2 0 0 10 3 2 Logger Script Data transmission to the logger script is activated via cyclical transmission repetitions Web interval Data packet information contains...

Page 119: ...t Byte 0 1 2 3 4 5 6 Bit 76543210765432107654321076543210765432107654321076543210 Cont PNNNNNNNSJJJJJMMMMDDDDDhhhhhmmmmmmssssssDIN AIN1 Byte 7 8 9 10 11 12 13 Bit 7654321076543210765432107654321076543...

Page 120: ...breaks have been inserted ID TO PASS 12345 PA 0005 home 99 TI 11 05 05 14 36 11 LO 092D4AD100000000000000000000 562D4AD123000000000000000000 3F2D4AD12A000000000000000000 562D4AD137000000000000000000 5...

Page 121: ...2 GPS message 81 see LPDx variable data format table 8 LIO3 3 I O message 74 see LIOx variable data format table 9 LPD3 3 GPS message 81 see LPDx variable data format table 10 LIO4 4 I O message 74 s...

Page 122: ...Value 3 10 7 analog input Value 3 11 8 analog input Value 3 12 Supply voltage Value 3 13 Digital output image Image 1 14 1 analog output Value 3 15 2 analog output Value 3 10 3 2 2 2 Data Format for L...

Page 123: ...000 000 000 000 B89 0 000 000 LPD3 C0 11 05 05 06 34 25 276 C41 2600 N 216 1621 E 0C 4D34 3 26A F 21 11 7 0 LIO4 001C 56 11 05 05 08 34 36 00 000 000 000 000 000 000 000 000 B83 0 000 000 LPD4 C0 11...

Page 124: ...C 2C Altitude in m 51 5 51 5 10 515 0x203 203 Position accuracy 2 2 Direction 309 35 309 x 60 35 18575 0x488F 488F Speed in km h 3 7 3 7 10 37 0x25 25 Speed in knots 2 0 2 0 10 20 0x14 14 Number of sa...

Page 125: ...input hexadecimal Value 8 4 Counter status 3rd input Status 1 5 Counter value 3rd input hexadecimal Value 8 6 Counter status 4th input Status 1 7 Counter value 4th input hexadecimal Value 8 The count...

Page 126: ...00 003 32E 7D5 7D9 7DA 7D8 7D6 7D5 AD0 0 000 32D LCD1 0 0 r 54600 r 0 0 0 LIO2 0001 11 00 01 01 00 09 52 00 CE3 32E 7D5 7D8 7DA 7D7 7D6 7D4 ACE 0 D04 32D LCD2 0 0 e 54600 d 0 0 0 LIO3 0002 78 00 01 0...

Page 127: ...ion 2 0 0 10 3 2 4 Time Request Script FW 2 33 If time adjustment is to take place via the Internet a time request script is transmitted on system start in order to adjust the time when a reply is rec...

Page 128: ...08 setpoint settings for digital and analog outputs and for changing the counters can be transmitted as replies Table 62 Setpoint settings Variable Contents Format AO1 1 analog output Normalized value...

Page 129: ...ache CR LF Content length 31 CR LF Keep alive timeout 15 max 100 CR LF Connection Keep Alive CR LF Content type text html CR LF CR LF Values stored 08 09 19 13 22 23 The header depends on both install...

Page 130: ...Connection example for a display device at AO1 output 44 Figure 20 Connection example for serial interface for MODBUS and PC 46 Figure 21 Connection example for MODBUS RS 485 Network Fullduplex 47 Fi...

Page 131: ...WAGO TO PASS 761 List of Figures 131 761 216 TO PASS Compact 8 AI Web MODBUS Manual Version 2 0 0...

Page 132: ...ical Data Counter Inputs 33 Table 22 Technical Data Analog Inputs 34 Table 23 Technical Data Digital Outputs 34 Table 24 Technical Data Analog Outputs 34 Table 25 Technical Data Data and event logger...

Page 133: ...us 116 Table 54 Signal quality from AT Reference Guide by Telit 116 Table 55 Data format for logger script FW 2 20 standard 119 Table 56 Data format for logger script FW 2 31 extended 121 Table 57 Dat...

Page 134: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet http www wago com...