background image

Operating and installation instructions

WAREMA Mobile system
WAREMA climatronic® converter WMS UP 

Keep for future use!
Valid from 1st October 2019

2029598_a•en•2019-10-01

We reserve the right to make technical modifications

1

WARNRN

W

 

Electrical installation must be performed 
by a certified electrician in accordance 
with VDE 0100 or the legal requirements 
and standards of the country in which the 
device is being installed. The electrician 
must observe the installation instruc-
tions included with the supplied electrical 
devices.

Due to both the legal regulations for radio systems and 
structural factors, the operating range of radio remote 
controls is limited. Sufficient radio reception must be 
ensured when planning the project. This is especially the 
case where the radio signal must pass through walls and 
ceilings. The control should not be installed in the immedi-
ate vicinity of metal components (steel beams, reinforced 
concrete, fire doors). 

 

 

Therefore, check that the receiver is functioning proper-
ly before the final installation.

Strong local transmitter systems (e.g. WLAN) with trans-
mission frequencies identical to those of the control may 
interfere with reception.

Nnstallation

The device is intended for flush mounting in a building. 
Use suitable fixing materials only. 

Nmportant information on the installation loca-
tion

The device is designed for installation in a flush-mount-
ed junction box 80 x 80 mm. The space in a 60 mm 
flush-mounted switch box is usually not sufficient.

 

 

Only lines that are used for the wiring of the WAREMA 
climatronic® converter should be routed into this box.

 

 

Install the converter

 

in such a way that the bottom of 

the housing with the printed radio waves symbol   
points towards the opening of the box. This ensures 
the best possible radio reception.

 

 

Check that the converter is functioning properly before 
the final installation.

 

 

Metal-clad buildings, domestic interference sources 
(unshielded household appliances, television sets, 
computers), supply lines and metal objects such as 
sheet metal enclosures must be at least 0.5 m away 
from the converter.

 

 

When performing the installation, follow the separate 
instructions of all components being connected, e.g. 
when installing the weather station(s), follow the specifi-
cations in the corresponding instructions.

Neneral information

1

2

3

4

5

6

Fig. 1 

 WAREMA climatronic® converter WMS UP 

1  Learn button

2  Test button

 

3  Status LED 1 (red)

4   Status LED 2 (green)

5   Status LED AS485

6  

 

Encoding switch to S3 

The WAREMA climatronic® converter WMS UP (referred to 
as "converter" in the following) is a flush-mounted device 
that enables the control of one or more WMS networks. 
This allows comfort and safety functions to be set and 
managed centrally. The channel and scene commands 
can also be sent from the climatronic® system to the WMS 
networks. 
A converter is connected to the  
WAREMA climatronic® voa the RS485 interface. 
A separate converter is required for each WMS network.
Commissioning is carried out via the WMS studio pro PC 
software.
The WMS receivers, which are to react to the commands 
of the WAREMA climatronic®, are also allocated with WMS 
studio pro.

Nntended use

The WAREMA climatronic® converter WMS UP is an 
electronic device that was developed to forward control 
commands and thus to control WAREMA Mobile System 
(WMS) receivers when combined with a WAREMA clima-
tronic®. The device is designed for interior installation. Any 
use other than the purpose described in these instructions 
requires approval from the manufacturer.

Safety instructions

These instructions address persons installing, wiring or 
connecting the converter and all necessary parts. Please 
contact your specialist dealer if you need additional infor-
mation.