background image

USER MANUAL

BEACON 

SOUNDER

we watch gas where you can't

DocuSign Envelope ID: AD1219C0-C292-4C55-B2EE-1190F300B975

Summary of Contents for BEACON SOUNDER

Page 1: ...USER MANUAL BEACON SOUNDER we watch gas where you can t DocuSign Envelope ID AD1219C0 C292 4C55 B2EE 1190F300B975...

Page 2: ...L 3 1 PRODUCT OVERVIEW 4 1 1 PCB Layout 4 1 2 Drilling Template 4 2 DIP SWITCH SETTINGS 5 3 MOUNTING INSTRUCTIONS 7 4 GENERAL SPECIFICATION 8 5 SERIAL PROTOCOL SPECIFICATION 8 6 LIMITED WARRANTY 13 Do...

Page 3: ...le internal electronical components whilst wiring up Environmental ex posure during installation should be under dry circumstances avoid heavy moist and wet conditions The Beacon Sounder is only weath...

Page 4: ...m2 Stranded core 1 1 PCB LAYOUT 1 Sounder 2 10 pin DIP switch 3 6 pin DIP switch J2 Communication input J4 Terminal block 7 pins Supply Ground BU Blue light GN Green light YL Yellow light RD Red light...

Page 5: ...3 4 3 4 looping 3 4 flashing 10 Hz 50 duty cycle 3 4 DIP SWITCH 5 6 YELLOW LIGHT continuous fancy loop 5 6 5 6 looping 5 6 flashing 10 Hz 50 duty cycle 5 6 DIP SWITCH 7 8 GREEN LIGHT continuous fancy...

Page 6: ...r OFF Falling trigger DIP SWITCH 3 FN Function ON J2 TTL Communication protocol OFF J4 terminal block input DIP SWITCH 4 VOL Volume ON High OFF Low DIP SWITCH 5 BL WH Swap blue to white ON Active OFF...

Page 7: ...ight Ensure all rubber gaskets are placed correctly Insert Supply signal cable through the 5 5mm hole see drilling template Connect supply signal cable to the terminal block Transparent lens O ring le...

Page 8: ...Sounder PN Air Be ac 010 over a serial interface This serial interface can be used to select colour display effect and sound effect If the serial input is used the digital I O inputs are no longer en...

Page 9: ...PTACLE 22 01 2045 Molex CRIMP CONTACT GOLD PLATED 08 55 0111 Molex DIPSWITCH SETTING Set DIP switch FN 3 to ON to configure the Beacon Sounder to use a serial input DIP SWITCH 3 FN Function ON J2 TTL...

Page 10: ...II Hex Green 4 ASCII Hex Blue 5 ASCII Hex Sound mode 6 ASCII Hex CRC All ASCII Hex values are a single value ranging from 0 to F NOTE This command has to be repeated at least every 15 seconds If no co...

Page 11: ...w low Continuously on 4 Alternating low high beeps low Low power rotation effect 5 Continuous 50Hz low Flashing 2Hz 10 duty 6 Reserved Reserved 7 Reserved Reserved 8 Disabled Reserved 9 Continuous 270...

Page 12: ...oHex r 4 cmd 3 toHex g 4 cmd 4 toHex b 4 cmd 5 toHex s cmd 6 toHex cmd 0 cmd 1 cmd 2 cmd 3 cmd 4 cmd 5 0xF cmd 7 r cmd 8 0 Transmit printf const char cmd char toHex uint8_t x if x 10 return 0 x else i...

Page 13: ...lightening water damage or other hazard voids liability of the manufacturer In the event that a product should fail to perform up to manufacturer specifications during the applicable warranty period p...